Requirements for Restaurants in Malls in Saudi Arabia: Hood Suppression, Mall Fire Alarm Interface and Landlord Approval

Requirements for Restaurants in Malls in Saudi Arabia: Hood Suppression, Mall Fire Alarm Interface and Landlord Approval

Requirements for restaurants in malls come in two layers: the Restaurant Requirements of the Ministry of Municipalities and Housing together with SBC 801 and Civil Defense, then the mall management’s own requirements that protect the whole building. The kitchen is the riskiest space in a mall restaurant, so management usually reviews the hood suppression design, its link to the building alarm and the sprinkler changes before allowing the unit to trade.

For the steps to obtain the Salamah certificate from Civil Defense on the Salamah platform, see our guide; our page on Saudi Civil Defense requirements covers the general requirements for buildings and facilities.

This article explains what a mall restaurant or food kiosk needs in safety systems during fit-out, and what changes compared with a street-front restaurant. AZEIDK supplies kitchen fire suppression systems and installation services for restaurants in commercial complexes, across its restaurants and commercial kitchens and malls and commercial buildings sectors.

Key takeaways

  • The 2025 Restaurant Requirements list commercial and mixed-use buildings among the permitted restaurant locations (clause 3.1) and require Civil Defense approval before licensing (2.1.2).
  • Food kiosks in commercial complexes: at least 6 m from any entrance or gathering point, at least 1.8 m of pedestrian clearance, and no more than 4 m high (3.3).
  • In normal practice a mall restaurant’s hood system reports to the building alarm panel and shuts off fuel or power to the appliances on discharge; the approved drawing sets the details.
  • Décor and false ceilings mean relocating sprinklers and detectors with mall approval.
  • The unit’s safety drawing is approved before work starts, not after.
In this article
  1. Requirements for restaurants in malls: what the document says about commercial complexes
  2. Mall restaurant versus street restaurant
  3. Hood suppression in mall restaurants
  4. Sprinklers and detectors during fit-out
  5. Food courts and kiosks
  6. Fit-out steps for a mall restaurant
  7. Work hours and coordination inside the mall
  8. Common mistakes when fitting out a mall restaurant
  9. FAQ
  10. Conclusion

Requirements for restaurants in malls: what the document says about commercial complexes

The Restaurant Requirements (Ministerial Decision 4600653138/1) use the term “commercial complexes”. One of the location options in clause 3.1 is a unit inside a commercial or mixed-use building in a permitted area. Kiosks inside commercial complexes have clear siting rules in clause 3.3: at least 6 m from any building entrance or gathering point, at least 1.8 m of pedestrian clearance, and a maximum height of 4 m.

These distances protect the mall’s escape routes: a frying or coffee kiosk next to a main entrance narrows the way out in an emergency. The general clauses still apply, including SBC 801 (4.9.1) and non-combustible ceilings in food preparation areas (4.5.8).

Mall restaurant versus street restaurant

ItemStreet-front restaurantRestaurant inside a mall
Fire alarmOwn system where the drawings require itTied into the building system by or with approval of the mall’s contractor
SprinklersPer code and building typeExisting mall network; changes go through management
Hood system signalTo the restaurant panel or a local bellTo the building panel and control room
Cooking energyGas or electricSet by mall management and building design
Hood exhaust ductUsually a direct routeRouted through the building, coordinated with the mall’s mechanical design
ApprovalsCivil Defense and BaladyMall management plus Civil Defense and Balady

Hood suppression in mall restaurants

A mall restaurant hood usually covers a frying and grilling line that runs all mall hours. The system is designed for the actual appliances under the hood, to NFPA 17A and NFPA 96 with UL 300 listed equipment, as explained in UL 300, NFPA 17A and NFPA 96. AZEIDK supplies Ansul R-102, Hood Safer and American Fire Control systems.

In a mall three coordination points are added: the discharge signal reaches the building panel through a monitor module installed or approved by the mall’s contractor; fuel or power to the appliances is shut off on discharge with manual reset; and the manual pull station sits on the staff exit route, not behind the appliances. Installation steps are covered in kitchen suppression installation.

Sprinklers and detectors during fit-out

A restaurant unit is often handed over with sprinklers and detectors laid out for the empty shell. Once false ceilings, partitions and a cold room are built, the required sprinkler positions change, and so does the right detector: heat detectors in the kitchen, smoke detectors in the dining area. These changes follow approved drawings and mall approval, as explained in sprinkler relocation during shop fit-out.

Food courts and kiosks

In a food court several small kitchens sit side by side behind light partitions and share one seating area and one set of exits. Each kitchen therefore needs its own hood system and a wet chemical Class K extinguisher near the cook line, while the seating area stays under the mall’s coverage. Keeping kiosks 6 m from entrances and gathering points with 1.8 m of clearance is part of protecting evacuation. See kitchen fire extinguisher (Class K).

Fit-out steps for a mall restaurant

  1. Obtain the tenant requirements from mall management and the existing fire drawings for the unit.
  2. Prepare a safety drawing for the unit: hood system, sprinkler and detector changes, extinguishers and emergency lighting.
  3. Get the drawing approved by mall management and by Civil Defense as part of the shop’s file.
  4. Supply and install, coordinating work windows on the mall network and temporary isolations.
  5. Test with the mall representative: trial discharge per manufacturer instructions, signal received at the building panel, and energy shut-off.
  6. Hand over documents: as-built drawings, datasheets and the safety equipment installation certificate.

Who is responsible for which system between mall and tenant is covered in Salamah certificate for malls.

Work hours and coordination inside the mall

Fit-out works in a trading mall usually run at night or outside peak hours under a mall work permit. Any work that isolates part of the sprinkler network or disconnects detectors from the building panel is coordinated in advance, with the isolation period and who watches the area defined, then the system is restored and tested before the shift ends. Welding and cutting near combustibles usually needs a separate permit. This coordination protects the mall and neighbouring restaurants, and stops one unit’s fit-out from turning into a false alarm that disrupts the whole building.

Common mistakes when fitting out a mall restaurant

  • Starting décor and ceilings before the safety drawing is approved, then opening them up again to move sprinklers and detectors.
  • Installing the hood system without wiring its signal to the building panel, so a discharge never reaches the mall control room.
  • Isolating the unit’s sprinklers for days during works without telling mall management or taking interim precautions.
  • Changing or adding cooking appliances after opening without checking hood nozzle coverage.
  • Placing display fridges or signs in the pedestrian clearance around a kiosk, against the 1.8 m rule.
  • Handing over the unit without as-built drawings and datasheets, which stalls the shop’s Salamah file.

After opening, maintenance of the hood system and extinguishers usually passes to the tenant, while the main building systems stay with mall management. The lease should therefore state who maintains each system, and the six-monthly hood system reports should be sent to mall management, as covered in mall fire system maintenance contracts.

FAQ

What are the requirements for restaurants in malls?

The 2025 Restaurant Requirements, SBC 801 and Civil Defense approval, plus mall management requirements such as linking hood suppression to the building alarm and approving sprinkler changes.

Does a food court restaurant need hood suppression?

Yes, if it has grease-producing appliances under the hood, such as fryers, grills and griddles.

What distance is required for a kiosk inside a mall?

Clause 3.3: at least 6 m from any entrance or gathering point, at least 1.8 m of pedestrian clearance, and no more than 4 m high.

Who connects the kitchen system to the mall’s fire alarm?

It is done through a monitor module on the building system, usually by the mall’s contractor or one it approves, coordinated with the hood system installer.

Can I move the unit’s sprinklers myself during fit-out?

No. Any change to the sprinkler network follows approved drawings and mall approval, then is tested before the network goes back into service.

Conclusion

Requirements for restaurants in malls combine what the municipal rules, the code and Civil Defense require with what mall management needs to protect the whole building. A restaurant that starts with an approved safety drawing before décor finishes fit-out faster and avoids opening ceilings again to move sprinklers or change the hood system.

Fitting out a restaurant or kiosk in a mall? Send us the unit layout, appliance list and mall requirements; we design, supply and install the hood system and the required changes. Talk to the AZEIDK team

References: Restaurant Requirements 1446H / 2025 (Ministry of Municipalities and Housing); Kitchen Hood Suppression Systems Construction Guide (Arlington Fire Rescue, 2021 IFC edition)