Jack Pump vs 3PUMP is not a question of which brand is better. It is a question of what your project specifies. The Jack Pump fire pumps AZEIDK offers are UL Listed and come in three types: end suction, split case and vertical turbine. 3PUMP comes as a complete package (electric + diesel + jockey) on one base; its documented models are Non-UL, with UL/FM versions available on request.
Both brands are listed under AZEIDK fire pumps. AZEIDK supplies fire pumps from SFFECO, WATEX and Jack Pump. When a project specification calls for another brand, AZEIDK’s supply team works on sourcing it to the required specification and approvals. AZEIDK also supplies 3PUMP packages in Saudi Arabia in several types and capacities.
Quick summary
- Jack Pump: UL Listed pumps designed to UL 448 and NFPA requirements according to the manufacturer’s catalogue, in three series: VES, MSC and VTP.
- 3PUMP: a ready package with a main electric pump, a standby diesel pump and a jockey pump, each with its own controller.
- Documented 3PUMP models run from 500 to 1500 GPM and are Non-UL; UL/FM versions are available on request.
- If the specification requires a listed or approved pump, the deciding item is the approval written in the datasheet and the technical offer, not the brand name.
How do Jack Pump and 3PUMP differ in what is offered?
The first difference is the product itself. Jack Pump pages present the pump by type and series, with an electric or diesel driver chosen for the project. The 3PUMP page presents a complete package: a main electric-driven pump, a standby diesel-driven pump, a jockey pump for pressure maintenance and three individual LS controllers, according to the datasheets.
| Item | Jack Pump | 3PUMP |
|---|---|---|
| Product offered | Pump by series, electric or diesel driver | Complete package: electric + diesel + jockey on one base |
| Types | End suction VES, split case MSC, vertical turbine VTP | End suction in the documented models |
| Flow range shown | VES 50 to 1000 GPM, MSC 300 to 8000 GPM, VTP 50 to 5000 GPM | 500, 750, 1000 and 1500 GPM |
| Approval | UL Listed per the catalogue, designed to UL 448 and NFPA requirements | Documented models Non-UL; UL/FM versions on request |
| Data source | Jack Pump 2024 catalogue | 3PUMP datasheet for each model |
Jack Pump: three series by water source and flow
VES end suction
The VES series page lists 50 to 1000 GPM and 84 to 230 PSI discharge pressure, with a back pull-out design that allows internal parts to be serviced without removing suction and discharge piping. The casing is ductile iron and the impeller is bronze or stainless steel.
MSC split case
The MSC series covers large flows: 300 to 8000 GPM and 82 to 369 PSI according to the product page. The axially split casing lets the whole rotating assembly come out without disconnecting the piping or the driver, and the impeller is double entry.
VTP vertical turbine
When water comes from an underground tank, well or sump below the pump, the VTP series applies: 50 to 5000 GPM and 84 to 230 PSI, with the number of stages chosen for the required pressure and a smaller pump room footprint.
3PUMP packages: four documented models
The 3PUMP packages page lists these models from the official datasheets. All are end suction with a cast iron casing, bronze impeller, stainless steel shaft and mechanical seal, on a 415 V, 50 Hz, 3-phase supply:
| Model | Pump | Electric motor | Diesel engine | Jockey pump |
|---|---|---|---|---|
| 500 GPM at 8 bar | 3P 4×3-10.2 | 75 HP | POWER 4102, 84 HP | RV10-10, 40 GPM at 8.5 bar, 4 kW |
| 750 GPM at 9 bar | 3P 5×4-10.2 | 100 HP | POWER 4105BZ, 108 HP | RV10-10, 30 GPM at 9.5 bar, 4 kW |
| 1000 GPM at 10 bar | 3P 5×4-10.2L | 150 HP | POWER 6102BZQ, 150 HP | RV10-12, 40 GPM at 10.5 bar, 4 kW |
| 1500 GPM at 10 bar | 3P 6×5-12.4 | 250 HP | POWER 6120Ti, 240 HP | RV10-12, 40 GPM at 10 bar, 4 kW |
These models are not UL listed or FM approved. UL/FM versions are available on request, and the model and approval are confirmed in each project’s technical offer. More detail in 3PUMP fire pump packages.
Jack Pump vs 3PUMP: when to choose each
- The specification requires a UL Listed pump: the Jack Pump series offered are listed per the catalogue. If you prefer 3PUMP, ask for the UL/FM version explicitly and check the approval on the datasheet.
- You want one integrated package in a single supply: a 3PUMP package brings the electric pump, diesel pump, jockey pump and controllers in one offer.
- Required flow above 1500 GPM: the Jack Pump MSC series reaches 8000 GPM and VTP 5000 GPM.
- Water stored in an underground tank below the pump room: the VTP vertical turbine pump is designed for this.
- Flow and pressure match a 3PUMP model: 500, 750, 1000 or 1500 GPM, and the project does not require a listed pump.
In every case the starting point is the hydraulic calculation: flow and pressure fix the size before the brand. See fire pump types for NFPA 20 basics, and Jack Pump or WATEX for a comparison of two listed pumps.
What to check in the technical offer before approval
- Rated flow and pressure, and the 150% point on the performance curve.
- The written approval: UL Listed, FM Approved or Non-Listed, and whether it matches the specification.
- Driver type and power, and whether the jockey pump and controllers are in the scope.
- Casing, impeller and shaft materials and the seal type.
- Supply voltage, flange sizes and pump room space.
Frequently asked questions
Are Jack Pump fire pumps UL listed?
The VES, MSC and VTP series offered by AZEIDK are UL Listed according to the Jack Pump catalogue and designed to UL 448 and NFPA requirements.
Are 3PUMP packages UL or FM approved?
The documented 500 to 1500 GPM models are Non-UL. UL/FM versions are available on request and confirmed in the technical offer.
What does a 3PUMP package include?
A main electric pump, a standby diesel pump, a jockey pump and a controller for each, on one base.
Which brand fits a large flow such as 2500 GPM?
Documented 3PUMP models stop at 1500 GPM, while the Jack Pump MSC series reaches 8000 GPM and VTP 5000 GPM.
Which is better, Jack Pump or 3PUMP?
There is no general answer. Required flow and pressure, the approval in the specification and the water source decide.
Need a fire pump for your project? Send the required flow, pressure and the approval in your specification, and the AZEIDK team will propose a suitable model from the brands available. Contact AZEIDK
Related guides
- What Is Firefighting Foam? AFFF, AR-AFFF and Where Each Type Is Used
- Electric Vehicle Fires in Showrooms and Workshops: Battery Risks, Early Detection, Suppression and Charging Areas
- Fire Alarm Supplier in KSA: Distributor vs Supplier vs Contractor and How to Verify Authorization
- SFFECO 1230 Fire Suppression System with FK-5-1-12 Clean Agent: Models, Cylinder Sizes, UL Listing and When to Choose It