UPS Battery Room Fire Protection in Data Centers: Lead-Acid and Lithium-Ion, Detection and Suppression

UPS Battery Room Fire Protection in Data Centers: Lead-Acid and Lithium-Ion, Detection and Suppression

Battery room fire protection in data centers has become a design item in its own right as UPS systems move to lithium-ion batteries. The hazard is not only flame: thermal runaway can spread from cell to cell and release flammable gases that may build up in the room. Published reviews of the 2026 edition of NFPA 855, the standard for stationary energy storage systems and a reference document rather than a Saudi legal requirement in itself, point to hazard mitigation analysis, large-scale fire testing, and acceptance of early detection by smoke or thermal imaging.

For how clean agent systems are designed, kept safe and maintained, see our FM-200 fire suppression system guide.

This article brings together what published references say about UPS battery rooms, the results of FM’s 2026 report on UPS battery safety, and what they mean for fire alarm systems and fire fighting systems in battery rooms within the data centers and server rooms sector.

Key points

  • Lithium-ion batteries can go into thermal runaway and vent flammable gas; in FM’s tests hydrogen and carbon monoxide were the main components.
  • In FM’s test, sprinklers did not stop thermal runaway propagation when the unit enclosure blocked water, and succeeded after the unit design was modified.
  • A 2021 Vertiv paper notes that IFC 2018, NFPA 1 2018 and NFPA 855 require 3 ft spacing for battery groups above 50 kWh, unless the authority grants a waiver based on a UL 9540A report.
  • According to a published review of the 2026 edition, NFPA 855 moves toward hazard mitigation analysis for most systems and accepts early detection by smoke or thermal imaging. In Saudi Arabia the binding rules come through the Saudi Building Code and Civil Defense.
  • Small UPS systems may fall below NFPA 855 thresholds; the designer confirms this from capacity and chemistry.
In this article
  1. Why UPS battery rooms need specific protection
  2. What FM’s UPS battery report found
  3. What the codes say about lithium battery rooms
  4. Battery room fire protection: detection and suppression
  5. UPS battery room checklist
  6. Frequently asked questions
  7. Summary

Why UPS battery rooms need specific protection

A UPS room packs a lot of stored energy into a small space, runs around the clock and often sits next to the data hall or electrical rooms. A fire there threatens the backup power source at the very moment the facility may need it.

The two common chemistries behave differently. Valve-regulated lead-acid (VRLA) batteries have long been used in UPS rooms, with ventilation and spacing requirements set by the manufacturer and the adopted code. Lithium-ion offers more energy in less space, but its thermal runaway hazard calls for a different approach to detection, suppression and ventilation.

What FM’s UPS battery report found

In April 2026 FM published the technical report “UPS Battery Safety: Fire and Explosion Hazard Assessment and Mitigation”, testing a lithium-ion UPS unit (NMC prismatic cells, 3.7 V, 60 Ah). Key results:

ItemPhase I (original design)Phase II (modified design)
Sprinkler activationAbout 24 minutesAbout 12 minutes
OutcomeIneffective at stopping thermal runaway propagation; the enclosure blocked waterThermal runaway stayed in the initiating module; no visible flames after 24 minutes
Peak heat release rate2,400 kWFire contained to the first module

The test used a design density of 0.3 gpm/ft² (12 mm/min), which the report does not present as a general recommendation. Design changes included compartmenting each module, perforating the unit door and adding insulation between adjacent modules.

Gas and explosion hazard

The report estimates each cell vents about 0.109 m³ of gas in thermal runaway, with hydrogen at about 35.7% and carbon monoxide at about 26.25%, and a lower flammable limit of 7.35%. It then calculates the minimum room volume or exhaust rate needed to keep concentrations below the hazardous level if one module releases all its gas. The practical message: room size and ventilation are part of the fire protection, not just an HVAC decision.

What the codes say about lithium battery rooms

NFPA 855, 2026 edition

According to a review published by Energy-Storage.news, a secondary source rather than the standard text, the edition moves toward hazard mitigation analysis (HMA) as the default for most energy storage installations, large-scale fire testing alongside UL 9540A, acceptance of early detection by smoke detection or thermal imaging for lithium-ion storage, and requirements for an emergency response plan with periodic review. Exact clauses and values are checked in the standard edition named in the project specification.

The same review notes that small systems, such as a small server room in an office building, may fall below the thresholds, giving a general illustration of systems below 20 kWh for lithium-ion and below 70 kWh for VRLA. These figures are illustrative only and are not design limits; the exact thresholds come from the standard’s own table and the adopted code.

Spacing and UL 9540A

A 2021 Vertiv white paper explains that IFC 2018, NFPA 1 2018 and NFPA 855 require 3 ft spacing for battery groups above 50 kWh, and that a UL 9540A test report can support a waiver request to the authority. It distinguishes UL 9540A, a third-party fire test method, from UL 9540, a certification for the storage system.

In Saudi Arabia, legal requirements come through the Saudi Building Code and Civil Defense approvals; these standards enter through the project specification and the designer’s and consultant’s decisions.

Battery room fire protection: detection and suppression

Detection

  • Addressable smoke detectors in the room, connected to the building fire alarm panel, with airflow from cooling considered when setting positions and spacing.
  • Battery management system (BMS) temperature and fault signals reported to the control room, so faults are known before they become fires.
  • Ventilation stopped or started on alarm as the design decides, since some scenarios need gas extraction rather than shutdown.

Suppression

  • Vertiv states that water is the preferred suppression method for these systems, and FM’s results show sprinkler effectiveness depends on water reaching the burning module.
  • The system may be wet pipe or a pre-action sprinkler system, depending on the designer’s decision and the room.
  • FM’s report did not test clean agents, so the role of special suppression in lithium battery rooms is set by the designer from the risk analysis and the supplied system’s UL 9540A results, not by copying the data hall solution.

UPS battery room checklist

  1. Battery chemistry and total capacity in kWh, compared with NFPA 855 and the adopted code.
  2. UL 9540A report and UL 9540 certification for the supplied system, where available.
  3. Fire separation between the battery room, data hall and electrical rooms.
  4. Spacing between battery groups and access routes for maintenance and firefighting.
  5. Detection layout, connection to the alarm panel and to the BMS.
  6. Suppression system, density and ability to reach the modules.
  7. Ventilation or emergency exhaust, and room volume checked against potential gas release.
  8. Emergency response plan, operator training and annual review.

For lithium battery storage outside data centers, such as warehouses and shops, see our article on lithium battery storage. For small UPS units in network rooms see Legrand UPS for network rooms, and for the rest of the data hall see our data center fire protection guide.

Frequently asked questions

Do sprinklers put out lithium battery fires?

In FM’s 2026 test, sprinklers succeeded after the UPS unit design was modified and failed to stop propagation when the enclosure blocked water. The result depends on the system and how water reaches it.

Which gases does a lithium battery vent in thermal runaway?

In FM’s report, hydrogen was about 35.7% and carbon monoxide about 26.25% of the vent gas from the tested cells.

Does NFPA 855 apply to a small server room UPS?

It may not, if capacity is below the standard’s thresholds. The designer checks the standard’s table for the chemistry and capacity.

What is the difference between UL 9540 and UL 9540A?

UL 9540A is a third-party fire test method that evaluates system behaviour; UL 9540 is a certification of the energy storage system itself.

Is a standard smoke detector enough in a battery room?

Smoke detection is the basis, and reviews of the 2026 edition of NFPA 855 note that thermal imaging detection is also accepted, as a reference value. BMS signals reported to the control room complete the picture.

Summary

A UPS battery room is not an ordinary electrical room. Protection starts with knowing the chemistry, capacity and test results of the supplied system, then separation and spacing, then detection and suppression that actually reach the modules, ventilation that deals with vent gas, and an emergency plan the operations team knows.