Evacuation Plans and Fire Drills: Preparation, Execution and Records

Evacuation Plans and Fire Drills: Preparation, Execution and Records

Fire alarm and sprinkler systems detect a fire and limit it, but they do not get people out of the building. What gets them out is a plan they know, trained people who guide them, and a drill that exposed the weak points before the real event. That is why evacuation plans and fire drills are part of the safety system, not a paper annex to it.

This guide covers what the Saudi code addresses in this area, the difference between a fire safety plan and an evacuation plan, and how to prepare the plan, run drills and document the results.

Key takeaways

  • The Saudi Fire Protection Code SBC 801 covers fire safety and evacuation plans (clause 404), emergency evacuation drills (405) and employee training (406).
  • The evacuation plan describes how people get out; the fire safety plan describes how fires are prevented and reported and how systems are managed. A facility needs both.
  • Drill frequency depends on use: in the IFC model text schools drill more often than offices, and hotels and healthcare facilities drill on every shift; the Saudi text is the binding reference.
  • Wall-mounted evacuation plans have an international standard, ISO 23601, with symbols from ISO 7010.
  • A drill that is not documented, with its findings closed out, has not done its job.
In this article
  1. What the Saudi code covers
  2. Evacuation plan versus fire safety plan
  3. Preparing an evacuation plan step by step
  4. Wall-mounted evacuation plans
  5. How often should drills be held?
  6. Running the drill
  7. Documentation and follow-up
  8. Common mistakes with evacuation plans and fire drills
  9. FAQ
  10. Conclusion

What the Saudi code covers

SBC 801 includes an emergency planning and preparedness chapter whose clauses cover fire safety and evacuation plans (404), emergency evacuation drills (405) and employee training and responsibilities (406). SBC 801 shares its chapter titles and structure with the International Fire Code (IFC), so designers use the IFC model text to understand the expected content, while the binding wording and figures are those of the Saudi text.

In the IFC model text, these plans are required for specific uses, including assembly, educational, healthcare and hotel occupancies, high-rise buildings and large covered malls, and for business, factory and mercantile buildings above a set occupant load. The plan is reviewed at least annually and whenever the use, the internal layout or the people responsible for it change.

Evacuation plan versus fire safety plan

The two documents are often confused. The model text separates them clearly.

The evacuation plan answers: how do we get out?

  • Escape routes, and whether evacuation is total or phased by floor or zone.
  • Procedures for staff who stay to operate critical equipment before leaving.
  • Assisted rescue for people who cannot use the normal routes.
  • Accounting for employees and occupants after evacuation.
  • Preferred and alternative ways to alert occupants and report the fire.
  • A description of the voice alarm tone and pre-recorded messages, where provided.

The fire safety plan answers: how do we prevent and manage?

  • Procedures for reporting a fire or emergency.
  • The life safety strategy: notification, relocation and evacuation.
  • A site plan showing the assembly point, hydrants and fire service access routes.
  • Floor plans showing exits, routes, manual call points, extinguishers, hose cabinets and the alarm panel.
  • The main hazards arising from normal use.
  • The people responsible for maintaining protection systems and for housekeeping and control of combustibles.

Preparing an evacuation plan step by step

  1. Gather the inputs: approved building drawings, occupants per floor and by time of day, and existing systems: alarm, voice evacuation, emergency lighting, stair pressurisation.
  2. Choose the strategy: immediate total evacuation, phased evacuation starting with the fire floor and adjacent floors, or defend-in-place for some groups, as in hospitals.
  3. Assign roles: emergency coordinator, floor wardens, roll-call staff at the assembly point, and someone to meet Civil Defense crews and brief them.
  4. Plan for people with disabilities: areas of refuge, who accompanies whom, and how they communicate. See fire telephones and areas of refuge.
  5. Set the assembly point: away from the building and from the fire appliance route, reachable without crossing a busy road.
  6. Write procedures in plain language, in more than one language where the workforce is multinational.
  7. Distribute and train: at induction and then periodically, keeping training records.

Wall-mounted evacuation plans

The plan by the lift lobby or in the corridor is the first thing a visitor sees. ISO 23601:2020 sets the design rules for these escape and evacuation plan signs, and refers to ISO 7010 for registered safety signs. Practices that make a plan useful:

  • Orient the plan to match the viewer, so what is on their right on the plan is on their right in reality.
  • A clear “You are here” marker, with the nearest and alternative escape routes drawn.
  • Standard symbols for extinguishers, manual call points, hose cabinets and exits.
  • The assembly point shown and the last revision date written on the plan.

Plans work together with exit signs and emergency lighting along the same route, as covered in emergency and exit lighting.

How often should drills be held?

Clause 405 of SBC 801 covers evacuation drills; check the required frequency in the adopted Saudi text. For guidance, here are examples from the frequency table in the IFC model text as published by US jurisdictions that adopt it:

Use (IFC model text)Frequency
Assembly (A)Quarterly, employees
Business (B) above a set occupant loadAnnually
Educational (E)Monthly, all occupants
Institutional (I), such as healthcareQuarterly on each shift
Hotels (R-1)Quarterly on each shift, employees
High-rise buildingsAnnually

The principle: the less able occupants are to evacuate themselves, the more often they change, or the more shifts they work, the more frequent the drills. Schools are covered in our schools fire safety guide.

Running the drill

Start with an announced drill that walks staff through their roles and routes, especially in a new facility or after a major plan change. Once roles are settled, move to unannounced drills that test real reactions. In shift-based facilities the morning shift is not enough; the night shift is smaller, further from management and usually needs training most.

  • Vary the timing and conditions: a drill held at the same time every time tests nothing. Sometimes assume an exit is blocked or the fire is in the main stair.
  • Coordinate in advance: with the monitoring company or whoever receives alarm signals, so Civil Defense is not dispatched to a drill, and with building management if the facility is part of a larger building.
  • Start the alarm at the source: from a manual call point or the panel, to check that the sound or message reaches every area.
  • Observe and measure: place observers on floors, in stairs and at the assembly point to record time, congestion and wrong behaviour such as using lifts or going back for belongings.
  • Account for everyone: at the assembly point, against attendance and visitor lists.
  • Restore the building: reset the system and tell everyone you coordinated with that the drill is over.

The drill also tests systems: was the alarm heard in every room? Did voice evacuation messages play in every zone? Did access-controlled doors release? Did lifts recall?

Documentation and follow-up

The IFC model text calls for a record of each drill covering who conducted it, date and time, notification method, staff taking part, number of occupants evacuated, simulated conditions, problems encountered, weather, and time to complete evacuation. In practice, add:

  • A list of findings, an owner for each and a close-out date.
  • A maintenance ticket for every system fault found during the drill, handled under annual maintenance contracts.
  • Updates to the plan and wall plans if the drill revealed an error.
  • Records filed with the facility documents, as they may be requested at inspection or renewal.

Common mistakes with evacuation plans and fire drills

  • A plan copied from another facility that matches neither the building nor its occupants.
  • Wall plans not updated after a fit-out or an exit closure.
  • Drills at the same time every time, or with no observers and no timing.
  • People with disabilities, visitors and contractors left out of the plan.
  • No coordination with the monitoring party, so a call reaches Civil Defense.
  • Drills recorded but findings never closed.
  • An assembly point on the fire appliance route or too close to the building.

FAQ

Does every facility need an evacuation plan?

SBC 801 sets the uses that require plans; in the model text they apply to specific uses and to buildings above an occupant load. Even where not required, a plan is good practice for any facility with staff.

How often should the plan be updated?

At least annually under the model text, and whenever the use, layout or assigned people change.

Should Civil Defense be told before a drill?

The key is to coordinate with whoever receives your system’s alarm signals so the drill is not treated as a real call, and with any authority your facility licence requires.

Which standard covers wall-mounted evacuation plans?

ISO 23601:2020 for escape and evacuation plan signs, with ISO 7010 symbols.

What matters most in a drill record?

Time to evacuate, number of participants, problems found and the actions taken to fix them.

Conclusion

Evacuation plans and fire drills turn safety systems from equipment on the walls into behaviour people know. A written plan for this specific building, clear and current wall plans, and varied drills that are documented and closed out are what make a real evacuation shorter and safer.