The SFFECO 1230 fire suppression system is an engineered total flooding system that uses the clean agent FK-5-1-12 (widely known in the market as Novec 1230), stored in cylinders superpressurized with nitrogen to 25 bar (360 psi). It comes in six cylinder sizes, from model SF 1230-038 up to SF 1230-850, and is designed with the manufacturer’s flow calculation software for rooms whose contents cannot tolerate water, such as server rooms, control rooms and archives.
For how clean agent systems are designed, kept safe and maintained, see our FM-200 fire suppression system guide.
This guide brings together what the SFFECO 1230 product page at AZEIDK and the system’s UL listing state: models and fill ranges, working pressure and temperature, the listing, how it compares with FM-200 systems, and what a consultant checks before approving the submittal.
Key points
- The agent is FK-5-1-12, which the product page describes as electrically non-conductive and residue-free.
- Six models, SF 1230-038 to SF 1230-850, with UL nominal capacities of 38, 65, 130, 277, 395 and 895 lb (the product page lists the largest as 850 lb), and cylinder volumes from 14.5 to 345 litres.
- Cylinders are pressurized to 25 bar (360 psig); the listed operating temperature range is 0 to 130 °F (about -18 to 54 °C).
- The system is UL listed under file EX15997, held by Saudi Factory for Fire Equipment Co (SFFECO), Riyadh.
- NFPA 2001 is the usual technical reference; the binding requirements in Saudi Arabia are the Saudi Building Code and Civil Defense regulations.
In this article
- What is the SFFECO 1230 fire suppression system?
- SFFECO 1230 models and cylinder sizes
- UL listing and what the product page says about FM
- Where does SFFECO 1230 fit?
- SFFECO 1230 or FM-200? A practical comparison
- Design and approval in Saudi Arabia
- Common mistakes when selecting a 1230 system
- Frequently asked questions
- Summary
What is the SFFECO 1230 fire suppression system?
It is a stored-pressure clean agent system made by SFFECO (Saudi Factory for Fire Equipment). Each cylinder is filled with FK-5-1-12 liquid and pressurized with nitrogen to 25 bar at 21 °C. On release the liquid travels through the pipe network and vaporizes at the nozzles, bringing the room to its design concentration and extinguishing the fire without water and without residue to clean up.
The product page describes the system as engineered: the number and size of cylinders, pipe diameters and nozzle positions are worked out for each room by a hydraulic calculation, not taken from a fixed table. Release can be electrical, pneumatic or mechanical. It sits within AZEIDK’s special fire suppression systems in Saudi Arabia.
The UL listing describes the units as total flooding protection against Class A surface-burning, Class B flammable liquid and Class C fires within an enclosure. The system is therefore not meant for open areas or rooms that cannot be sealed.
SFFECO 1230 models and cylinder sizes
The UL listing gives each model a range of agent weight it may be filled with, and the hydraulic calculation selects the model whose range covers the required quantity. The table summarizes the listing and the product page:
| Model | Fill range (lb) | Notes from the product page |
|---|---|---|
| SF 1230-038 | 15 to 38 | Smallest cylinder, 14.42 kg |
| SF 1230-065 | 26 to 65 | Small and medium rooms |
| SF 1230-130 | 52 to 130 | Medium size |
| SF 1230-277 | 111 to 277 | Optional liquid level indicator |
| SF 1230-395 | 157 to 394 | Optional liquid level indicator |
| SF 1230-850 | 366 to 854 | Largest cylinder, 178.17 kg, optional level indicator |
Cylinder water volume runs from 14.5 litres to 345 litres and the valve outlet from 1 inch to 3 inches (25.4 to 76.2 mm). These figures matter when planning the cylinder room: the large models are heavy, need a floor rated for the load and a clear route for removing a cylinder for refilling.
Why not always choose the largest cylinder?
Filling a large cylinder close to its minimum can push it outside the listed range, and one large cylinder may not distribute agent well across a long room or two spaces such as the ceiling void and the raised floor. The decision comes from the calculation software, not from estimation.
UL listing and what the product page says about FM
SFFECO 1230 units appear in the UL directory under clean-agent extinguishing system units (GAQF), file EX15997, with Saudi Factory for Fire Equipment Co, Riyadh, as the listee. The listing requires the system to be designed and installed to the manufacturer’s design, installation, operation and maintenance manual and with the flow calculation software it names.
The AZEIDK product page also states UL 2166, FM 5600 and compliance with NFPA 2001. Practical advice for consultants and contractors: check the current listing in UL Product iQ and the FM Approvals guide before approval, and confirm that the valves, actuators and nozzles in the submittal are the ones listed with the system, because the listing covers the assembly, not the cylinder alone.
Where does SFFECO 1230 fit?
The product page lists server and data rooms, control rooms and laboratories, museums and heritage sites, and oil and gas facilities, as well as electrical rooms, archives and telecom rooms. These rooms share three features:
- Contents that water would damage or that are hard to replace, such as servers, panels and records.
- An enclosure that can be sealed so the concentration holds for the required time.
- A need to restart operations quickly, since the agent leaves no residue.
For data rooms in general see data center fire protection, and for electrical rooms electrical room fire protection.
SFFECO 1230 or FM-200? A practical comparison
In clean agents, AZEIDK supplies FK-5-1-12 systems such as SFFECO 1230 and HFC-227ea (FM-200) systems such as Context Plus 227 and American Fire Control. The comparison below uses the product pages only:
| Item | SFFECO 1230 | FM-200 systems (Context Plus 227) |
|---|---|---|
| Agent | FK-5-1-12 | HFC-227ea |
| Storage pressure | 25 bar (360 psig) | 24 bar (360 psi) or 34 bar (500 psi) |
| Cylinder range | 38 to 895 lb nominal (UL) | 35 to 1,200 lb |
| Fire classes | A, B and C in an enclosure | A, B and C in an enclosure |
| Listing | UL, file EX15997 | UL per product page |
On real projects the deciding factor is often not purely technical but three questions: what does the consultant’s specification call for, is the room already protected with a given agent that is being extended, and where will the refill come from after a discharge? Two agents cannot be mixed in one system, and a cylinder listed for one agent is not filled with another. For a wider comparison see clean agent suppression comparison.
What about FK-5-1-12 supply after 3M’s exit?
“Novec 1230” is a trade name associated with 3M. The AZEIDK product page names the system agent as FK-5-1-12 of the Chemori-FK5112 type. What matters for the owner is that the agent filled is the one the system listing and manufacturer’s manual allow, and that this is documented in the submittal. The market background is covered in Novec 1230 after 3M’s exit.
Design and approval in Saudi Arabia
The binding reference in the Kingdom is the Saudi Building Code, including the fire code SBC 801, together with the requirements of the General Directorate of Civil Defense. NFPA 2001 is used as the technical reference for details the designer adopts or the project specification calls for, such as design concentration, discharge time and hold time. See the NFPA 2001 guide.
What the consultant usually asks for in the approval file:
- Datasheet and listing page for every component: cylinder, valve, actuator and nozzle.
- Agent quantity calculation for the net room volume at the lowest and highest expected temperature, plus a hydraulic calculation with the manufacturer’s software.
- Pipe and nozzle layout, cylinder location and bracketing.
- Control panel and release sequence: two detectors on two zones, hold-off button, manual release, warning signals and HVAC shutdown.
- A room integrity test plan before handover, as described in room integrity testing.
AZEIDK’s engineering design and calculations service covers these calculations, and Civil Defense approval support follows the approval file.
Common mistakes when selecting a 1230 system
- Calculating on gross volume without treating voids separately: raised floors and ceiling voids are separate spaces that need their own calculation and nozzles when they are protected.
- Ignoring room openings: one unsealed cable opening can cut the hold time and fail the test.
- Mixing components from different makers: a valve or actuator not listed with the system voids the listing.
- Placing cylinders in a corridor or hot room: the operating temperature range is fixed in the listing and the cylinder location must stay within it.
- Forgetting the refill plan: after any discharge the room is unprotected until refilled, so ask about it before supply.
Frequently asked questions
What agent does the SFFECO 1230 system use?
FK-5-1-12, the clean agent known in the market as Novec 1230. The product page states it is electrically non-conductive and leaves no residue.
What cylinder sizes does SFFECO 1230 come in?
Six models. The UL listing gives nominal capacities of 38, 65, 130, 277, 395 and 895 lb (the product page lists the largest, SF 1230-850, as 850 lb), with water volumes from 14.5 to 345 litres.
What is the SFFECO 1230 cylinder pressure?
Cylinders are pressurized with nitrogen to 25 bar (360 psig) according to the UL listing.
Is the SFFECO 1230 system UL listed?
Yes, under UL file EX15997. Check the current listing in UL Product iQ and confirm every component submitted is listed with the system.
Can an FM-200 cylinder be filled with 1230 agent?
No. Each cylinder and valve is listed for a specific agent, and changing the agent needs a system listed for it and a new calculation.
Does a 1230 system work in a room that is not sealed?
No. It is a total flooding system that needs an enclosure able to hold the concentration, verified by a room integrity test before handover.
Summary
The SFFECO 1230 fire suppression system is a UL listed option for enclosed rooms with sensitive equipment, using FK-5-1-12. A sound selection starts with the agent quantity and the hydraulic calculation in the manufacturer’s software, then matching every component to the listing, then sealing and testing the room before handover.
Need a quotation for an SFFECO 1230 system? Send the room drawing, its dimensions, the equipment inside and the proposed cylinder location, and the AZEIDK team will prepare the calculations, datasheets and submittal. Contact AZEIDK
Related guides
- Foam Sprinkler System: Foam-Water Sprinkler and Deluge Systems from NFPA 16 to NFPA 11
- Home CCTV Cameras on Your Phone: Secure Hik-Connect and DMSS Setup, User Permissions and Connection Troubleshooting
- Dry or Wet Barrel Fire Hydrant: AFC F-7700, F-8700 and FW-9000 and When to Choose Each
- Fire System Maintenance for Sports Clubs: Halls, Pools, Pump Rooms, Stands and the Inspection Schedule