MOMAH Warehouse Requirements in Saudi Arabia: Fire Safety Clauses and Civil Defense Approval Before Licensing

MOMAH Warehouse Requirements in Saudi Arabia: Fire Safety Clauses and Civil Defense Approval Before Licensing

The Ministry of Municipalities and Housing warehouse requirements govern how warehouses, stores and low and medium hazard self-storage units are licensed on the Balady platform. They make Civil Defense approval a condition before the licence is issued and refer every fire protection requirement to the Saudi Fire Protection Code, SBC 801.

For the steps to obtain the Salamah certificate from Civil Defense on the Salamah platform, see our guide; our page on Saudi Civil Defense requirements covers the general requirements for buildings and facilities.

This article summarises the safety and fire clauses of the document as published on the Ministry website (Ministerial Decision 4600327053/1 dated 8/10/1446 AH) and explains what an owner or tenant should prepare before applying. For fire fighting and fire alarm systems in warehouses and help with Civil Defense requirements, see AZEIDK’s warehouses and logistics page and the Civil Defense approval support service.

Key points

  • The requirements cover low and medium hazard warehouses, stores and self-storage units, not high hazard warehouses.
  • Civil Defense approval is required before the municipal licence is issued, together with a valid commercial registration covering the activity.
  • The fire protection clause refers to the full SBC 801 requirements and sets no design figures of its own.
  • A mezzanine may grow from one third to one half of the floor area where an approved automatic suppression system and audible alarm are installed.
  • Worker housing inside the warehouse is prohibited, the guard room must be outside, and any open flame is banned.
In this article
  1. What do the warehouse requirements cover?
  2. Civil Defense approval before the Balady licence
  3. Fire clauses in the warehouse requirements
  4. What the requirements leave to SBC 801
  5. Daily operation: extinguishers, evacuation plan and aisles
  6. Common mistakes that delay a warehouse licence
  7. Checklist before applying for the licence
  8. FAQ

What do the warehouse requirements cover?

The document applies to warehouses, stores and self-storage units. It classifies storage by hazard with reference to SBC 201, section 311:

  • Medium hazard (S1): storage of materials such as cartons and plastics.
  • Low hazard (S2): storage of non-combustible materials such as building materials, appliances and non-combustible raw materials.

High hazard warehouses that store or handle flammable, explosive, toxic or radioactive materials are outside its scope, and the document places them within the areas of the Saudi Authority for Industrial Cities and Technology Zones (MODON). Their Civil Defense licensing is covered in our article on hazardous materials storage licences.

The class also affects the site: S2 warehouses may be built on the plot boundary on two sides only, while S1 warehouses may not be built on the boundary on any side.

Civil Defense approval before the Balady licence

Issuing, renewing, amending, suspending and cancelling the licence follow the Municipal Licensing Procedures Law and its executive regulation. The core licensing conditions are:

  1. Civil Defense approval before the licence is issued.
  2. A valid commercial registration that includes the activities to be licensed.
  3. Approval of the supervising authority for the activity, where one exists.
  4. Compliance with the spatial and municipal requirements in the document.

Operating before licensing, under a different activity or after expiry is prohibited, and a facility closed by the municipality may not reopen until the violation is corrected and the municipality agrees. Civil Defense licensing for warehouses on Salamah is covered in Salamah licence for warehouses, and the municipal licence steps in Balady licence issue and renewal.

Fire clauses in the warehouse requirements

The fire protection clause itself is short: refer to all requirements of the Saudi Fire Protection Code, SBC 801. Several other clauses are directly linked to fire safety:

ClauseWhat it saysWhat it means in practice
Fire protectionRefer to all SBC 801 requirementsSprinklers, alarm and extinguishers are designed to the code and occupancy
MezzanineUp to one third of the floor, or up to one half with an approved automatic suppression system and audible alarmA larger mezzanine depends on approved suppression and alarm
Emergency exitsProvide exits required by Civil Defense rules; no equipment in themNo racks or raised or protruding equipment in exit paths
Fire appliance accessEnough space on site for fire appliances to manoeuvre, per the approved site planConsidered in the site layout and loading areas
CeilingsFire resistant materials not affected by humidityChecked when selecting roofing materials
Housing and flamesNo worker housing inside, guard room outside, no open flame, gas or charcoalNo kitchens or stoves in storage areas
LightingGas lighting prohibited inside and outsideElectric lighting to approved specifications

Wall-mounted air conditioning units on storage buildings also need an external steel frame so they cannot fall outward during a fire, and offices and staff facilities must meet SBC 201 safety requirements.

What the requirements leave to SBC 801

The warehouse requirements do not say when sprinklers are required, which detectors to use or how many extinguishers to install. These follow from SBC 801 according to occupancy, area, storage height and commodity, and the engineering office checks them in the safety drawings. A sound sequence is:

AZEIDK designs and installs fire fighting systems and fire alarm systems for warehouses to the code and authority requirements.

Daily operation: extinguishers, evacuation plan and aisles

  • Provide suitable numbers and types of fire extinguishers according to Civil Defense classifications and the operations carried out.
  • Post signs explaining the evacuation plan and make sure staff follow it in a fire or emergency.
  • Train all staff in safety and first aid and keep a first aid kit on site.
  • Do not store goods in aisles, external setbacks, roofs or areas not designated for storage.
  • Mark forklift routes on the floor, separated from pedestrian paths.
  • No smoking outside designated areas.

In self-storage facilities internal corridors between units must be at least 1.5 m wide and each unit between 4 and 24 m². CCTV must be installed in line with the security camera law and its executive regulation.

Common mistakes that delay a warehouse licence

  • Storing goods that change the hazard class after the design was approved, such as adding plastics to a warehouse designed as S2.
  • Adding or enlarging a mezzanine without approved automatic suppression and audible alarm.
  • Blocking an emergency exit with racks or equipment, or using aisles and setbacks for temporary storage.
  • Keeping a guard room or worker housing inside the warehouse building.
  • Applying before the fire systems are installed and tested, which delays Civil Defense approval.

Checklist before applying for the licence

  1. Confirm the stored goods place the warehouse in S1 or S2, not high hazard.
  2. Approve the site plan with fire appliance access and emergency exits.
  3. Have the fire systems designed to SBC 801 by a qualified engineering office, then installed and tested before requesting Civil Defense approval.
  4. Install extinguishers and evacuation plan signs, see fire evacuation plan board.
  5. Remove any housing or flame source from inside the warehouse.
  6. With Civil Defense approval in hand, apply on Balady with a valid commercial registration.

FAQ

Do the warehouse requirements need Civil Defense approval?

Yes. Civil Defense approval must be obtained before the municipal licence is issued.

Do they say when sprinklers are required?

No. They refer fire protection to SBC 801, which sets this by occupancy, area and storage arrangement.

What is the difference between S1 and S2 warehouses?

S1 is medium hazard, for materials such as cartons and plastics. S2 is low hazard, for non-combustible materials such as building materials, by reference to SBC 201.

Can workers live inside a warehouse?

No. Worker housing inside warehouses is prohibited and the guard room must be outside.

Do the requirements cover hazardous materials warehouses?

No. High hazard warehouses are excluded and are placed within MODON areas.

Can a warehouse mezzanine be enlarged?

Yes, from one third to one half of the floor area where the floor has an approved automatic suppression system and audible alarm.

Preparing a warehouse for licensing? Send us the area, goods and storage method, and AZEIDK will review the fire systems needed, install and test them and follow up the Civil Defense requirements. Contact AZEIDK

Sources: Warehouse and Storage Requirements (Arabic PDF) (Ministry of Municipalities and Housing, 2025)