Recycling Plant and Scrap Yard Fire Protection: Thermal Camera Detection, Hydrants and Surveillance

Recycling Plant and Scrap Yard Fire Protection: Thermal Camera Detection, Hydrants and Surveillance

Recycling plant fire protection is different from protecting any other factory, because the raw material is the fuel: piles of plastic, paper, cardboard, tyres, wood and scrap, sometimes mixed with lithium batteries thrown away by mistake. Fires usually start with slow heating inside a pile or a spark from a shredder, then spread across an open yard where the core of the pile is hard to reach.

This guide explains how to lay out the yard to limit the risk, how to detect fires early with thermal cameras and surveillance, what the water and hydrant network needs, and how this ties to AZEIDK’s security and surveillance systems and fire fighting systems within the industrial facilities sector.

Key points

  • Most recycling yard fires start inside a pile or at shredders and balers, not in the building.
  • Pile size and spacing are the first line of defence against fire spread, before any suppression system.
  • Thermal cameras detect surface heating day and night but cannot see the core of a pile, so manual temperature checks still matter.
  • An external hydrant network with adequate flow and pressure is the main protection for open storage.
  • In Saudi Arabia SBC 801 and Civil Defense requirements are binding. Foreign guidance is a good-practice reference only.
In this article
  1. Why do recycling plants and scrap yards catch fire?
  2. Recycling plant fire protection starts with yard layout
  3. Early detection: thermal cameras and surveillance
  4. Inside the building: sorting, shredding and baling
  5. After hours: the highest-risk period
  6. Hydrants and water around the yard
  7. Licensing and maintenance
  8. FAQ
  9. Summary

Why do recycling plants and scrap yards catch fire?

Three causes recur. The first is self-heating: organic material and compressed paper decompose and warm up over time, especially in large, old piles. The second is mechanical sparks: shredders, balers and sorting lines create friction and sparks, and a metal object or small gas cylinder may pass through with the material. The third is batteries: lithium batteries mixed with waste can ignite when crushed or punctured, as covered in our article on lithium battery storage.

Firefighting is harder because a burning pile has to be pulled apart with machinery before water reaches its core, which can take hours.

Recycling plant fire protection starts with yard layout

The Saudi Building Code has no dedicated chapter for recycling yards at this level of detail. The UK Environment Agency guidance on fire prevention plans for permitted sites, updated on 11 January 2021, gives practical figures that designers and operators can use as a reference:

ItemUK guidance
Maximum pile height4 m
Maximum length or width20 m
Spacing between pilesAt least 6 m
Spacing from buildings and site boundaryAt least 6 m
Quarantine areaAt least 50% of the largest pile volume, reachable within 1 hour
Storage timeLess than 6 months for combustible waste
Water for a 300 m³ pileAt least 2,000 L/min for 3 hours
HydrantsWithin 100 m of the site access

These figures are not mandatory in the Kingdom, but they show the design logic: smaller piles mean smaller fires, spacing stops flame spread, and a quarantine area lets burning material be pulled away.

Early detection: thermal cameras and surveillance

Smoke detectors do not work in open yards. The practical alternative is camera monitoring: thermal cameras watch pile surfaces and alert when temperature exceeds a threshold set by the operator, while standard cameras let a supervisor verify the alarm before sending the team. The UK guidance lists CCTV flame detection and temperature probes as automated options and warns that surface readings do not accurately reflect core temperature.

We followed how thermal imaging is entering listed fire detection in our news item on the first thermal cameras listed to UL 2684. Whether such cameras form part of a project’s fire alarm system remains a decision for the consultant and the competent authority.

AZEIDK designs and installs CCTV systems for industrial sites and yards, including pole positions, coverage angles, recording and the monitoring room, as described in CCTV for factories.

Inside the building: sorting, shredding and baling

Sorting halls need different protection from the yard. Long conveyors suit linear heat detection, electrical panel rooms need detection and clean suppression, and bale storage inside buildings is protected by sprinklers according to the commodity and storage height. The hazard classification is set in the engineering design: plastic bales differ from paper and cardboard, and share some features with the risks covered in plastic factory fire protection.

At the shredder itself, suitable extinguishers and a nearby hose cabinet are advisable, with a procedure to stop the machine as soon as smoke is seen.

After hours: the highest-risk period

Many yard fires are found at night or during holidays, when nobody is there to see smoke. The UK guidance requires detection to work during working hours and when the site is closed, and detection systems to be certified under a recognised scheme. It also asks operators to turn piles routinely, set their own triggers for temperature or its rate of rise, and sample at least 10% of bales stored for more than 3 months.

In practice, thermal camera alerts should reach a monitoring room or a guard on duty, with adequate yard lighting and continuous recording that later helps locate the point of origin. A fixed closing routine helps: stop and clean the shredders, keep material away from hot motors, and confirm the hydrant network valves are open.

Hydrants and water around the yard

An open pile fire is fought with water and machinery together, so the yard needs an external hydrant network around the storage areas, with flow and pressure set by hydraulic design and a water source that lasts the required duration. AZEIDK supplies the American Fire Control FW-9000 wet barrel hydrant, and our guide to fire hydrants and landing valves covers the types. After installation, performance is checked with a hydrant flow test.

Licensing and maintenance

The facility needs a Civil Defense safety licence according to its activity. AZEIDK prepares the system requirements through its Civil Defense approval support service, handles the technical report through an approved engineering consultancy office, and issues the safety equipment installation certificate. After start-up, hydrants, pumps and extinguishers need regular maintenance, because dust and debris on these sites wear equipment faster.

FAQ

What causes most recycling plant fires?

Self-heating inside piles, sparks from shredders and balers, and batteries crushed with the material. The fix starts with yard layout and sorting, before suppression systems.

Are thermal cameras enough to detect a pile fire?

They detect surface heating early but cannot see inside the pile. They should be backed by regular temperature checks on large and old piles and a clear response procedure.

What spacing is right between scrap piles?

The Saudi code sets no specific figure for these yards. The UK guidance gives at least 6 m between piles and from buildings, and the designer sets the right distance for the material and site.

Does a recycling yard need sprinklers?

Open yards are not normally sprinklered. They rely on hydrants and monitoring. Indoor storage and sorting areas may need sprinklers depending on classification and storage height.

Can AZEIDK deliver surveillance and hydrants together?

Yes, AZEIDK installs both CCTV and fire fighting systems, though maintenance contracts are separate: one for fire systems and another for CCTV and low current systems.

How is the yard monitored after closing?

Thermal camera alerts go to a monitoring room or a guard on duty, with lighting and continuous recording, plus a daily closing routine that stops and cleans machines and checks the water network.

Summary

At a recycling plant, safety starts on the ground: limited pile sizes, clear spacing, a quarantine area and sorting that keeps batteries out. Then comes early thermal detection and a water network that can run for hours. This order costs far less than trying to extinguish a large pile once fire has reached its core.

Setting up a recycling yard or reviewing its protection? Send us the site plan and material types, and we will review surveillance, hydrants and licensing requirements with you. Contact the AZEIDK team

References: Fire prevention plans: environmental permits (Environment Agency, GOV.UK, updated 11 January 2021)
Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.