Conventional fire alarm systems
Talentum UV/IR2 Ex d Flameproof Flame Detector 16521
Brand
Talentum
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Civil Defense, Salamah & Balady TransactionsSubmitting and following up Salamah licences (instant and non-instant) and Balady requests, preparing technical reports and closing inspection notes→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The Talentum UV/IR2 flame detector (model 16591) by FFE, UK, is designed to protect areas where open fires may be expected. It detects most flames, from hydrocarbon fires with 4.3 µm emissions to invisible fires such as hydrogen.
It combines one ultraviolet (UV) sensor with two infrared (IR) sensors. The signals are processed and checked for flame characteristics, and only the simultaneous detection of UV and IR light signals an alarm. False alarms from flickering sunlight, arc welding and lightning are eliminated by the combined UV and dual IR processing. Relay contacts or a 4-20 mA signal are selectable as standard.
| Model | Talentum UV/IR2: EN version 16591-00, FM version 16591-20 |
|---|---|
| Detection technology | UV sensor (185 to 260 nm) and two IR sensors (1.0 to 2.7 µm) |
| Detection range | High (Class 1): 0.1 m² n-heptane fire at 25 m. Low (Class 3): 0.1 m² n-heptane at 12 m |
| Field of view | 90° minimum cone (viewing angle not to exceed ±30° to meet EN 54-10) |
| Outputs | Programmable relays (latching or non-latching) or 4-20 mA; relay rating 0.75 A, 48 V DC, 30 W (resistive loads only) |
| Supply voltage | 14 to 30 V DC |
| Current consumption | Quiescent 3, 4 or 8 mA; alarm 9, 20 or 28 mA depending on mode |
| Power-up time | 2 seconds max. |
| Housing | Die cast zinc alloy (ZA12), blue, 142 x 108 x 79 mm, 1.75 kg |
| Cable entries | 2 x 20 mm, wiring 1.0 to 4.0 mm² |
| Ingress protection | IP65 |
| Operating temperature | EN: -10 to +55 °C; FM: -20 to +60 °C; relative humidity 95% non-condensing |
| Approvals | EN 54-10; FM version 16591-20 |
| Accessories | Adjustable mounting bracket 07127-00, stainless steel weather shield 12545-00, Talentum Test Torch 1800-101, air purge kit 12556-00 |
The UV/IR2 needs UV and IR at the same time, so it suits sites with arc welding, lightning or strong sunlight reflections. The IR3 tolerates lens contamination by oil and dust and suits hydrocarbon fuel fires. The final choice depends on the site and the fuel.
Yes. The datasheet lists it as solar blind and suitable for indoor and outdoor areas.
Yes. The Talentum UV/IR2 Ex d, model 16521, has an aluminium IP66 housing with ATEX certification.
View the product’s full specifications and technical information in the official catalogue.