Conventional fire alarm systems
FP Range 2-Zone Extender Card, FF387Z-2
Brand
Context Plus
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The FG SD-615 conventional photoelectric smoke detector includes an integrated sounder and is designed to detect smoke and provide a direct audible warning when the smoke concentration reaches the alarm threshold.
The detector uses infrared photoelectric sensing inside a specially designed chamber. The chamber allows smoke to enter while helping reduce the effect of external light.
When smoke enters the sensing chamber, smoke particles reflect infrared light toward the receiving sensor. Once the smoke reaches the specified concentration, the detector generates an alarm signal and activates the built-in sounder.
According to the catalogue, the detector is available in both 2-wire and 4-wire versions.
Key Features:
• Conventional photoelectric smoke detector.
• Integrated audible sounder.
• Infrared optical sensing technology.
• Audible warning when smoke reaches the alarm threshold.
• Flashing red LED standby indication.
• Sound output above 80dB at 1 metre.
• Wide operating-voltage range from 9 to 35V DC.
• Low standby-current consumption.
• Sensitivity range from 0.08 to 0.16dB/m.
• Available in 2-wire and 4-wire versions.
• Circular ceiling-mounted design.
Technical Specifications:
• Operating voltage: DC 9V to 35V.
• Standby current: Up to 80µA.
• Alarm current: Up to 40mA.
• Standby indication: Flashing red LED.
• Alarm sound level: Above 80dB at 1 metre.
• Sensitivity: 0.08 to 0.16dB/m.
• Temperature range: 0°C to 50°C.
• Environmental humidity: Up to 95% RH, non-condensing.
• Dimensions: 99mm diameter × 54.7mm high.
Product number: SD-615.