A fire risk assessment is a structured study of a building or facility that answers three questions: what could start a fire here, who would be at risk if it did, and are the existing protection measures enough? It is usually requested by insurers, investors and managers taking over an existing building, or by facilities that want to know where to spend the safety budget first instead of replacing everything.
This guide explains the steps, what the report should contain, how it differs from system inspection and Civil Defense approval, and how it becomes a prioritised action plan. AZEIDK provides a site technical survey and assessment service and an existing systems assessment and scope service.
Key points
- A risk assessment does not replace Civil Defense approval and the Salamah certificate, but it shows what is missing before inspection.
- It covers ignition sources, combustible materials, people at risk, alarm, suppression, escape and management.
- The useful output is a list of actions ranked by priority with an owner and a date, not just a description of the building.
- The assessment is reviewed after a change of use, an extension or an incident, and periodically.
Assessment, inspection and approval: the difference
| Activity | Question it answers | Who needs it |
|---|---|---|
| Fire risk assessment | Where is the risk and what comes first? | Owner, management, insurer |
| Existing systems assessment | Do the systems work and match the design? | Anyone taking over or upgrading a building |
| Maintenance and periodic testing | Are the systems ready today? | Every licensed facility |
| Civil Defense approval and Salamah | Does the facility meet the requirements? | Licensing and operation |
Existing systems assessment is covered in existing building fire systems assessment, and periodic checks in fire protection maintenance checklist.
Fire risk assessment steps
- Gather information: drawings, occupancy, number of people by day and night, current licence and maintenance records.
- Identify ignition sources: electrical boards and wiring, kitchens, generators, welding, chargers and smoking. The usual ones are in causes of fire in facilities.
- Identify what will burn: stock, furniture, packaging, flammable liquids and finishes.
- Identify people at risk: visitors, sleeping occupants, people with disabilities, night-shift workers and contractors.
- Review protection: alarm, sprinklers, extinguishers, fire doors, exits, emergency lighting and ventilation.
- Review management: evacuation plan, training, safety log and hot work permits.
- Evaluate and rank: likelihood and impact for each hazard, then a proposed action.
- Record and review: a signed, dated report with a review date.
How to rank priorities
A practical approach sorts every finding into three levels:
- Immediate: anything that directly threatens life, such as a locked exit, a failed alarm panel, a closed sprinkler valve or flammable storage in an escape route.
- Near term: anything that weakens protection, such as missing detectors in an added area, fire doors that do not close or expired extinguishers.
- Planned: improvements needing budget and design, such as upgrading a conventional alarm to addressable or protecting a server room.
The owner then knows where to spend first; near-term items link to corrective maintenance and technical support, and planned items to engineering design and calculations.
What the report should contain
- A description of the facility, its use and occupant numbers.
- A list of hazards with photos and locations on the drawing.
- The status of each protection system and its last service date.
- An action table with priority, owner and date.
- The assessor’s name, the date and the next review date.
The facility keeps the report with its fire safety log book as a reference at inspection or insurance renewal; some insurers have their own requirements, as in FM Global requirements.
Frequently asked questions
Is a fire risk assessment required for a Salamah licence?
The licence depends on meeting Civil Defense requirements and approved protection systems. The assessment is a management and technical tool that helps you get there, and insurers or owners may request it.
How often should it be reviewed?
After any change of use, extension or incident, and periodically at an interval management sets according to the level of risk.
Does the assessment include testing the systems?
It reviews their condition and records. Full system testing is part of periodic maintenance or an existing systems assessment.
Not sure where to start in an existing building or running facility? Ask AZEIDK for a survey visit and get a prioritised list of findings with a clear scope of work. Contact AZEIDK
Related guides
- Nursery Requirements in Saudi Arabia: Fire Safety, Alarms, Exits and CCTV
- Fire Protection Project Timeline in Saudi Arabia: From Award to Civil Defense Certificate
- Fuel Storage Tank Fire Protection with Foam: Foam Chambers and Pourers Under NFPA 11
- PBX Maintenance and Common Faults: Line Outages, Voice Quality and IP Phones







