Talentum UV/IR2 Flame Detector 16591

Talentum UV/IR2 flame detector by FFE (UK) with one ultraviolet and two infrared sensors. Solar blind and immune to arc welding and lightning, it detects fires up to 25 m (EN 54-10 Class 1) indoors and outdoors.
Brand

Product Details

Product Overview

The Talentum UV/IR2 flame detector (model 16591) by FFE, UK, is designed to protect areas where open fires may be expected. It detects most flames, from hydrocarbon fires with 4.3 µm emissions to invisible fires such as hydrogen.

It combines one ultraviolet (UV) sensor with two infrared (IR) sensors. The signals are processed and checked for flame characteristics, and only the simultaneous detection of UV and IR light signals an alarm. False alarms from flickering sunlight, arc welding and lightning are eliminated by the combined UV and dual IR processing. Relay contacts or a 4-20 mA signal are selectable as standard.

ModelTalentum UV/IR2: EN version 16591-00, FM version 16591-20
Detection technologyUV sensor (185 to 260 nm) and two IR sensors (1.0 to 2.7 µm)
Detection rangeHigh (Class 1): 0.1 m² n-heptane fire at 25 m. Low (Class 3): 0.1 m² n-heptane at 12 m
Field of view90° minimum cone (viewing angle not to exceed ±30° to meet EN 54-10)
OutputsProgrammable relays (latching or non-latching) or 4-20 mA; relay rating 0.75 A, 48 V DC, 30 W (resistive loads only)
Supply voltage14 to 30 V DC
Current consumptionQuiescent 3, 4 or 8 mA; alarm 9, 20 or 28 mA depending on mode
Power-up time2 seconds max.
HousingDie cast zinc alloy (ZA12), blue, 142 x 108 x 79 mm, 1.75 kg
Cable entries2 x 20 mm, wiring 1.0 to 4.0 mm²
Ingress protectionIP65
Operating temperatureEN: -10 to +55 °C; FM: -20 to +60 °C; relative humidity 95% non-condensing
ApprovalsEN 54-10; FM version 16591-20
AccessoriesAdjustable mounting bracket 07127-00, stainless steel weather shield 12545-00, Talentum Test Torch 1800-101, air purge kit 12556-00

Applications

  • Aircraft hangars
  • Refineries, petrochemical sites and power plants
  • Fuel loading racks and storage tanks
  • Compressor stations, engine rooms and generators
  • High voltage equipment
  • LNG and LPG production and tunnels

FAQ

When should I choose UV/IR2 over IR3?

The UV/IR2 needs UV and IR at the same time, so it suits sites with arc welding, lightning or strong sunlight reflections. The IR3 tolerates lens contamination by oil and dust and suits hydrocarbon fuel fires. The final choice depends on the site and the fuel.

Does it work outdoors in direct sun?

Yes. The datasheet lists it as solar blind and suitable for indoor and outdoor areas.

Is there a flameproof version?

Yes. The Talentum UV/IR2 Ex d, model 16521, has an aluminium IP66 housing with ATEX certification.