Talentum IR2 Ex d Flameproof Flame Detector 16511

Talentum IR2 Ex d flameproof flame detector by FFE (UK) with two IR sensors and an aluminium IP66 housing for indoor hazardous areas. ATEX, IECEx, LPCB and EN 54-10 approved, with detection up to 25 m.
Brand

Product Details

Product Overview

The Talentum IR2 Ex d flame detector (model 16511) by FFE, UK, is the flameproof version of the IR2, designed to protect hazardous areas where open fires may be expected. It detects almost all flames, from hydrocarbon fires with 4.3 µm emissions to invisible fires such as hydrogen, even if the lens is contaminated by oil, dust, vapour or ice.

Two IR sensors discriminate between flames and spurious sources of radiation, and the datasheet specifies the detector for indoor areas. Relay contacts or a 4-20 mA signal are selectable as standard.

ModelTalentum IR2 Ex d: EN version 16511-00, NF version 16511-04
Detection technologyTwo infrared sensors (IR2), operating wavelength 1.0 to 2.7 µm
Detection rangeHigh (Class 1): 0.1 m² n-heptane fire at 25 m. Low (Class 3): 0.1 m² n-heptane at 12 m
Field of view90° minimum cone (viewing angle not to exceed ±20° to meet EN 54-10)
OutputsProgrammable relays (latching or non-latching) or 4-20 mA; relay rating 0.75 A, 48 V DC, 30 W (resistive loads only)
Supply voltage14 to 30 V DC
Current consumptionQuiescent 3, 4 or 8 mA; alarm 9, 20 or 28 mA depending on mode
HousingFlameproof (Ex d), copper free aluminium alloy, red, 158 x 149 x 137 mm, 2.3 kg
Cable entries3 x 20 mm, wiring 1.0 to 4.0 mm²
Ingress protectionIP66
Operating temperature-10 to +55 °C; relative humidity 95% non-condensing
ApprovalsEN 54-10, LPCB, ATEX and IECEx
AccessoriesAdjustable mounting bracket 07127-00, stainless steel Ex d weather shield 07279-00, Ex d air purge 12555-00, Talentum Test Torch 1800-101

Applications

  • Chemical plants and pharmaceutical production
  • LNG and LPG production
  • Engine rooms and coal handling
  • Spray booths, printing and waste recycling
  • Military and marine sites

FAQ

When should I choose IR2 Ex d over IR3 Ex d?

The datasheet specifies the IR2 Ex d for indoor hazardous areas such as engine rooms and enclosed plants, while the IR3 Ex d is specified for indoor and outdoor areas such as loading racks and tank farms.

Does it need a weather shield?

Dedicated Ex d accessories are available, including the 07279-00 weather shield and the 12555-00 air purge, depending on site conditions.

Technical Documents

Product Catalogue

View the product’s full specifications and technical information in the official catalogue.

This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.