Conventional fire alarm systems
Talentum UV/IR2 Ex d Flameproof Flame Detector 16521
Brand
Talentum
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Civil Defense, Salamah & Balady TransactionsSubmitting and following up Salamah licences (instant and non-instant) and Balady requests, preparing technical reports and closing inspection notes→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The Talentum IR2 flame detector (model 16581) by FFE, UK, is designed to protect areas where open fires may be expected. It detects almost all flames, from hydrocarbon fires with 4.3 µm emissions to invisible fires such as hydrogen, and responds to flickering, low frequency (1 to 15 Hz) infrared radiation even if the lens is contaminated by oil, dust, water, vapour or ice.
Two IR sensors respond to different wavelengths to discriminate between flames and spurious sources of radiation, and filters plus signal processing avoid false alarms from flickering sunlight. The IR2 is specified for indoor areas and offers selectable relay contacts or a 4-20 mA signal as standard.
| Model | Talentum IR2: EN version 16581-00, NF version 16581-04 |
|---|---|
| Detection technology | Two infrared sensors (IR2), operating wavelength 1.0 to 2.7 µm |
| Detection range | High (Class 1): 0.1 m² n-heptane fire at 25 m. Low (Class 3): 0.1 m² n-heptane at 12 m |
| Field of view | 90° minimum cone (viewing angle not to exceed ±30° to meet EN 54-10) |
| Outputs | Programmable relays (latching or non-latching) or 4-20 mA; relay rating 0.75 A, 48 V DC, 30 W (resistive loads only) |
| Supply voltage | 14 to 30 V DC |
| Current consumption | Quiescent 3, 4 or 8 mA; alarm 9, 20 or 28 mA depending on relay or current loop mode |
| Power-up time | 2 seconds max. |
| Housing | Die cast zinc alloy (ZA12), blue, 142 x 108 x 79 mm, 1.75 kg |
| Cable entries | 2 x 20 mm, wiring 1.0 to 4.0 mm² |
| Ingress protection | IP65 |
| Operating temperature | -10 to +55 °C; relative humidity 95% non-condensing |
| Approvals | EN 54-10 with AFNOR and LPCB certification |
| Accessories | Adjustable mounting bracket 07127-00, stainless steel weather shield 12545-00, Talentum Test Torch 1800-101, air purge kit 12556-00 |
The IR2 uses two infrared sensors and its datasheet specifies it for indoor areas. The IR3 uses three sensors and is specified for indoor and outdoor areas. For an outdoor site exposed to sunlight, review the IR3 or UV/IR2.
Yes. The Talentum IR2 Ex d, model 16511, has a copper free aluminium IP66 housing with ATEX and IECEx certification for hazardous areas.
Yes. The relay output wires into a conventional panel zone, or the 4-20 mA output can feed a control system. Wiring details are in the datasheet and user guide.
View the product’s full specifications and technical information in the official catalogue.
Explore more products available in this category.