Conventional fire alarm systems
Talentum UV/IR2 Ex d Flameproof Flame Detector 16521
Brand
Talentum
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Civil Defense, Salamah & Balady TransactionsSubmitting and following up Salamah licences (instant and non-instant) and Balady requests, preparing technical reports and closing inspection notes→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The Talentum IR3 flame detector (model 16589) by FFE, UK, is designed to protect areas where open fires may be expected. It detects almost all flames, from hydrocarbon fires with 4.3 µm emissions to invisible fires such as hydrogen. The detector responds to flickering, low frequency (1 to 15 Hz) infrared radiation emitted by flames, even if the lens is contaminated by a layer of oil, dust, water vapour or ice.
Three IR sensors respond to different wavelengths so the detector can tell real flames from spurious sources of radiation, and false alarms from flickering sunlight are avoided by filters and signal processing. Relay contacts or a 4-20 mA signal are selectable as standard.
| Model | Talentum IR3: EN version 16589-00, FM version 16589-20 |
|---|---|
| Detection technology | Three infrared sensors (IR3), operating wavelength 1.0 to 2.7 µm |
| Detection range | High (Class 1): 0.1 m² n-heptane fire at 25 m. Low (Class 3): 0.1 m² n-heptane at 12 m |
| Field of view | 90° minimum cone (viewing angle not to exceed ±30° to meet EN 54-10) |
| Outputs | Programmable relays (latching or non-latching) or 4-20 mA; relay rating 0.75 A, 48 V DC, 30 W (resistive loads only) |
| Supply voltage | 14 to 30 V DC |
| Current consumption | Quiescent 3 to 8 mA, alarm 9 to 28 mA depending on operating mode |
| Power-up time | 2 seconds max. |
| Housing | Die cast zinc alloy (ZA12), blue, 142 x 108 x 79 mm, 1.75 kg |
| Cable entries | 2 x 20 mm, wiring 1.0 to 4.0 mm² |
| Ingress protection | IP65 |
| Operating temperature | EN: -10 to +55 °C; FM: -20 to +60 °C; relative humidity 95% non-condensing |
| Approvals | EN 54-10; FM version 16589-20 (FM 3260) |
| Accessories | Adjustable mounting bracket 07127-00, stainless steel weather shield 12545-00, Talentum Test Torch 1800-101, air purge kit 12556-00 |
This 16589 version has a zinc alloy IP65 housing for ordinary indoor and outdoor sites. For hazardous areas, the flameproof Talentum IR3 Ex d model 16519 carries ATEX and IECEx certification.
Each sensor looks at a different IR wavelength. Comparing them lets the detector separate real flames from other radiation such as flickering sunlight, which cuts false alarms.
It has built-in automatic and manual test, and can be tested in the field with the Talentum Test Torch 1800-101. Full details are in the datasheet and user guide.
View the product’s full specifications and technical information in the official catalogue.