The Context Plus XFP addressable fire alarm panel is the range most designers pick for small and medium buildings: one or two loops and up to 126 devices per loop. The range, however, has three models that differ in loops, zone indicators, power supply, battery size and enclosure, and the wrong choice shows up later in the battery calculation or when a panel network is requested. This guide compares the XFP501E, XFP501 and XFP502 using the Context Plus catalogue published on the AZEIDK site, and explains when XFP is enough and when to move to ZFP or FirePlus.
AZEIDK is the exclusive agent for Context Plus in Saudi Arabia and supplies, installs and programs XFP panels as part of its fire alarm systems. All panels are listed in the addressable fire alarm category.
Key points
- Three models: XFP501E with one loop and 16 zones in a plastic enclosure, XFP501 with one loop and 32 zones, and XFP502 with two loops and 32 zones in a metal enclosure.
- Each loop takes up to 126 addressable devices and up to 40 loop-powered sounders at 10 mA.
- Power supply is 1.4 A on the 16 zone model with batteries up to 3.2 Ah, and 3 A on the 32 zone models with batteries up to 7 Ah.
- The network links up to eight main panels in any mix over two-wire RS485 cable up to 1 km.
- The range is certified by the LPCB to EN54 parts 2 and 4.
In this article
- What is the difference between the three XFP models?
- What do all XFP models share?
- How to choose between 16 and 32 zones
- XFP panel networks and repeaters
- Loop cable and isolator requirements
- When is XFP enough, and when to move to ZFP or FirePlus?
- Common mistakes when selecting an XFP panel
- Frequently asked questions
- Conclusion
What is the difference between the three XFP models?
| Item | XFP501E/X/CON | XFP501/X/CON | XFP502/X/CON |
|---|---|---|---|
| Loops | 1 | 1 | 2 |
| Zonal LED indicators | 16 | 32 | 32 |
| Enclosure | Plastic | Metal | Metal |
| Power supply | 1.4 A | 3 A | 3 A |
| Maximum battery | 3.2 Ah VRLA | 7 Ah VRLA | 7 Ah VRLA |
| Batteries specified for LPCB approved systems | 2 × Yuasa NP3.2-12 | 2 × Yuasa NP7-12 | 2 × Yuasa NP7-12 |
| Conventional sounders at 20 mA | 40 | 80 | 80 |
| Network card | CFP761 | AFP711 | AFP711 |
| Off-board printer | Not available | Available (AFP709 kit) | Available (AFP709 kit) |
| Approx. size and weight | 380 × 235 × 77 mm, 1.9 kg | 410 × 250 × 80 mm, 4.5 kg | |
Source: the Context Plus XFP and ZFP catalogue and the product pages for the single loop 16 zone XFP and the single loop 32 zone XFP.
What do all XFP models share?
- A loop with 500 mA maximum current, onboard loop isolators with LED indication when active, and auto-polling from each loop end.
- Two programmable conventional sounder circuits with a 6800 ohm end-of-line resistor, two programmable inputs, and three programmable relay outputs rated 1 A at 30 V DC plus a fault relay.
- A backlit two-line, 40-character display, 40 characters of custom text per device and a 999-event log.
- Three access levels: general, authorised user and engineer, by keypad or keyswitch.
- EN54-2 functions: zone dependency types A, B and C, phased evacuation and output delays, alarm counter, day/night mode, investigation delay, individual device sensitivity and earth fault monitoring.
- Commissioning and maintenance functions: loop auto-learn, monitor a point, test outputs, one-person walk test and loop continuity test.
How to choose between 16 and 32 zones
Devices per loop are the same on both models (126), so the real difference is not the number of detectors but three other things:
- Zone indicators: if the building needs more than 16 zones shown on the panel front (many floors, or separate areas on one floor), choose the 32 zone model.
- Power and battery: the 16 zone model is limited to a 3.2 Ah battery and a 1.4 A supply. With a heavy sounder and output load, or a long standby period in the specification, the battery may not be enough. Run the load calculation as in fire alarm battery calculation before fixing the model.
- Printer and mounting: an off-board printer is only possible on the 32 zone models. The 16 zone panel mounts on the surface or semi-flush without an extra bezel, while the 32 zone panels need the AFP385 bezel for flush mounting.
Moving from the XFP501 to the XFP502 is a device count decision: if the project exceeds one loop (126 devices), or you want two buildings or wings on separate loops of one panel, choose the XFP502.
XFP panel networks and repeaters
XFP uses an RS485 network on two-wire cable in two ways that cannot be mixed on the same network:
- Main panel network: up to eight main panels of any model with up to 1 km of cable. Each panel shows fires and faults from the others with the point description, accepts silence, reset and disablement commands, and remote panels can be programmed from a PC at one panel. Each main panel needs a network card: CFP761 for the 16 zone panel and AFP711 for the 32 zone panels.
- Repeater network: up to eight XFP510-16 or XFP510-32 repeaters on one non-networked main panel with up to 500 m of cable; the repeater comes with its card fitted.
The cards and the XFP507 programming kit are on the XFP network cards and programming kit page. Network design for compounds is covered in networked fire alarm panels, and repeater locations in fire alarm repeater panels.
Loop cable and isolator requirements
The catalogue calls for fire resistant screened cable of at least 1 mm², a maximum of 1 km per loop, no more than 20 ohm per conductor and no more than 0.27 µF capacitance. It recommends an isolator at least every 20 devices and at structural fire barriers and zone boundaries. See loop isolators in addressable systems and addressable loop design.
When is XFP enough, and when to move to ZFP or FirePlus?
| Item | XFP | ZFP | FirePlus |
|---|---|---|---|
| Loops | 1 or 2 | 1 to 8 | 1 to 6 |
| Interface | Two-line display, 16 or 32 zone LEDs | Full colour touchscreen, up to 200 zone LEDs | 32 zone LEDs, optional board up to 64 |
| Stated approval | EN54-2 and 4 by the LPCB | EN54-2 and 4 by Intertek | UL certificate in the submittal for ULP-CON1L to ULP-CON4L |
| Network | Up to 8 main panels | Up to 128 nodes | Networkable |
Rule of thumb: XFP for small and medium buildings up to two loops on an EN54 specification. If the project needs more than two loops or a touchscreen with many zone indicators, look at the ZFP panel; if the specification requires a UL listed panel, look at FirePlus. The three ranges are compared with Honeywell Gent in Context Plus vs Honeywell Gent.
Common mistakes when selecting an XFP panel
- Choosing the 16 zone model because it is cheaper, then finding the 3.2 Ah battery cannot meet the required standby time.
- Asking for a printer on the 16 zone panel, which does not support one.
- Forgetting a network card for each main panel, or trying to mix main panels and repeaters on one network.
- Loading the loop with more than 40 loop-powered sounders, or skipping isolators every 20 devices.
- Using unscreened cable or a conductor smaller than 1 mm² for the loop.
Frequently asked questions
How many devices can an XFP loop take?
Up to 126 addressable devices per loop, including up to 40 loop-powered sounders at 10 mA.
Is the XFP panel approved?
The catalogue states LPCB certification to EN54 parts 2 and 4. If the specification requires UL listing, check the FirePlus range.
Can a 16 zone panel be networked with a 32 zone panel?
Yes. The XFP network accepts up to eight main panels in any mix, with a CFP761 card in the 16 zone panel and an AFP711 card in the 32 zone panel.
How many repeaters can be fitted?
Up to eight repeaters on one non-networked main panel, with up to 500 m of cable.
How is an XFP panel programmed?
From the panel front or with the XFP507 Windows software over the RS232 port. General programming steps are in addressable fire alarm panel programming.
Conclusion
The XFP501E suits small buildings with one loop and a light load, the XFP501 when you need 32 visible zones, a larger battery or a printer, and the XFP502 when the project exceeds 126 devices. Beyond two loops, or with a UL requirement, ZFP or FirePlus is the better fit.
Need the right XFP model for your building? Send the drawings, BOQ, floor count and required zones, and the AZEIDK team will propose the model, cards and batteries with supply, installation and programming. Request a quote from AZEIDK
Related guides
- Smoke Detector Sensitivity Testing and Cleaning on Addressable Systems (NFPA 72)
- Business Routers and VPN Gateways: How to Choose a Router for Your Office or Branches
- CCTV Cameras for Factories: Covering Production Lines, Stores and Fences, and Integrating with the Fire Alarm
- Fire Extinguishers in Schools: Right Type for Each Space, Quantity, Mounting and Inspection