The FirePlus fire alarm panel from Context Plus is an analogue addressable panel offered in six models, ULP-CON1L to ULP-CON6L, covering 1 to 6 loops. It handles up to 126 devices per loop and 64 zones, with a 5.6 A power supply and batteries up to 24 Ah, uses the XP95 and Discovery protocols and can be networked for larger systems. Models and accessories are on the FirePlus addressable panels, 1 to 6 loops page within AZEIDK’s fire alarm systems.
For how conventional and addressable systems compare, see our guide to choosing a fire alarm system for Saudi projects.
This guide explains the six models, when an extender card or a separate battery cabinet is needed, what the UL certificate in the submittal actually covers, and how to size loops and accessories on a Saudi project, based on the product page and the submittal published on the AZEIDK site.
Key points
- Six models: ULP-CON1L, ULP-CON2L and ULP-CON3L expandable to 4 loops; ULP-CON4L with 4 loops; ULP-CON5L and ULP-CON6L requiring a separate ULP-BCG battery cabinet.
- Capacity: 126 devices and 500 mA per loop, 64 zones, loop length up to 1 km on 1.5 to 2.5 mm² cable.
- 32 zonal LEDs as standard; the ULP-32LED board adds zones 33 to 64.
- The UL certificate in the submittal lists the 1 to 4 loop models; the 5 and 6 loop models appear in the product schedule.
- Programming from the front panel or with ConfigManager Plus, including cause and effect.
In this article
- What is the FirePlus fire alarm panel?
- FirePlus models: ULP-CON1L to ULP-CON6L
- FirePlus technical specifications
- Expansion cards and accessories
- What does the FirePlus UL certificate cover?
- Programming: ConfigManager Plus or the front panel?
- Choosing the right FirePlus model
- Common mistakes with FirePlus panels
- FirePlus panels from AZEIDK
- FAQ
- Summary
What is the FirePlus fire alarm panel?
FirePlus is the Context Plus range of intelligent addressable panels, described on the product page as suitable for small and large detection applications. It works with Context Plus addressable detectors and interfaces on the XP95 and Discovery protocols. The submittal on the AZEIDK site states compatibility with the Context Plus range of UL listed detectors and interfaces.
Within the brand it sits above the one and two loop XFP range and below the ZFP range, which reaches 8 loops with a touchscreen. It is typically proposed for mid-size to large buildings where six loops is enough and a very large panel network is not needed.
In Saudi Arabia, requirements by occupancy come from Section 907 of the Saudi Fire Code SBC 801, with NFPA 72 used as a technical reference where the designer adopts it. The project specification decides which approval the panel and devices must carry.
FirePlus models: ULP-CON1L to ULP-CON6L
| Model | Loops | Expansion | Batteries |
|---|---|---|---|
| ULP-CON1L | 1 | Expandable to 4 loops | In the cabinet |
| ULP-CON2L | 2 | Expandable to 4 loops | In the cabinet |
| ULP-CON3L | 3 | Expandable to 4 loops | In the cabinet |
| ULP-CON4L | 4 | No further loop expansion | In the cabinet |
| ULP-CON5L | 5 | Separate battery cabinet required | ULP-BCG cabinet |
| ULP-CON6L | 6 | Separate battery cabinet required | ULP-BCG cabinet |
Per the submittal schedule, every model ships with 32 zonal LEDs and a 5.6 A PSU. Loop expansion follows a set sequence: one to two loops by adding a ULP-1L/XT card, two to three loops with a ULP-1L/XT plus the ULP-TB termination board, and three to four loops with a ULP-1L/XT.
FirePlus technical specifications
| Item | Value per product page and submittal |
|---|---|
| Devices per loop | Up to 126 |
| Loop current | 500 mA per loop |
| Zones | Up to 64 |
| Loop cable | 2 core, 1.5 to 2.5 mm², 1 km maximum |
| Power supply | 5.6 A, operating range 20 to 28.2 V DC |
| Mains input | 195 to 264 V AC |
| Batteries | 2 x 12 V sealed lead acid, 24 Ah maximum |
| Quiescent current, 1 loop panel | 220 mA |
| Supervised alarm output | 24 V DC, 1 A maximum, 10 k EOL |
| Protected auxiliary output | 24 V DC at 2 A |
| Module communication | RS485 internal and external |
| Cabinet | 505 x 407 x 150 mm, 1.2 mm mild steel, IP30 |
| Environment | -5 to +40 °C, 25% to 95% RH non-condensing |
The quiescent and alarm figures feed straight into the battery calculation; see our fire alarm battery calculation guide. If the result exceeds 24 Ah, the answer is an additional power supply or a load redistribution, not a battery larger than the charger is rated for.
Expansion cards and accessories
- ULP-1L/XT: one-loop extender card.
- ULP-TB: termination board, used only when extending a two loop panel to three loops.
- ULP-NIC: two-wire network interface card for panel networking.
- ULP-RDC and ULP-REP: SmartTerminal repeater driver card in the main panel, and the repeater itself with a 2 A PSU.
- ULP-HLI: high level interface board converting internal communication to RS232, RS485 and Modbus outputs, the usual route to a building management system.
- MB3170: serial-to-Ethernet gateway for LAN and WAN connections, used with the ULP-HLI.
- ULP-BCG: battery cabinet for the 5 and 6 loop models, 300 x 405 x 150 mm.
- ULP-32LED: 32-zone LED extender for zones 33 to 64.
Repeaters are usually requested at the building entrance or the security room. See our guide to the fire alarm repeater panel.
What does the FirePlus UL certificate cover?
The product page flags a point that is easy to miss: the UL certificate included in the submittal lists ULP-CON1L, ULP-CON2L, ULP-CON3L and ULP-CON4L only, while ULP-CON5L and ULP-CON6L appear in the product schedule and need a separate battery cabinet.
The UL Product iQ pages attached in the same file show these four models under file S36045 in the categories “EN 54 Part 2: Control and Indicating Equipment” and “EN 54 Part 4: Power Supply Equipment”. In other words, the attached certificate is UL certification to the EN 54 parts for the panel and its power supply, and the file does not include a listing to the US standard UL 864. If a specification explicitly calls for UL 864, ask the supplier for evidence before material approval.
In practice:
- Where the specification requires EN 54 verified by UL, the 1 to 4 loop models are covered by the attached certificate.
- Where a project needs 5 or 6 loops, the consultant should confirm the approval status of those models before approval, or split devices across two networked 4 loop panels.
- Do not mix devices from different approval systems on one loop; see UL vs EN 54 for fire alarm devices.
Programming: ConfigManager Plus or the front panel?
The product page states that cause and effect can be programmed from the panel front controls or with ConfigManager Plus, which the submittal describes as including many pre-engineered functions. Small projects may manage from the front panel. With several loops and dozens of outputs, the software is faster and more accurate, and it leaves a file that is handed to the owner and reused for later changes.
With up to 64 zones and text per device, programming quality shows in clear location text and sensible zoning. Review addressable fire alarm panel programming before handover.
Choosing the right FirePlus model
- Count devices: divide detectors, call points, loop-powered sounders and I/O units by 126, add spare capacity, and check the 500 mA loop current and cable length.
- Plan for growth: if the building will expand, ULP-CON1L to ULP-CON3L can grow to 4 loops with cards.
- Check the approval: 4 loops or fewer keeps the panel within the models named on the attached UL certificate.
- Batteries and space: 5 and 6 loop models need wall space for the ULP-BCG cabinet next to the panel.
- Define interfaces: ULP-NIC for networking, ULP-HLI with MB3170 for the BMS, and addressable loop modules for lifts and HVAC. See the addressable input/output module guide.
- Check the panel room: the operating range ends at 40 °C and the cabinet is IP30, so avoid hot, damp or exposed locations.
Common mistakes with FirePlus panels
- Approving a 6 loop model on the assumption that the attached certificate covers it, when it names the 1 to 4 loop models.
- Leaving the ULP-BCG battery cabinet out of the BOQ for 5 and 6 loop models.
- Extending a two loop panel to three loops without the ULP-TB board.
- Promising a BMS interface without a ULP-HLI card.
- Relying on 32 zonal LEDs in a building that needs more, without adding a ULP-32LED.
FirePlus panels from AZEIDK
AZEIDK is the Context Plus agent in Saudi Arabia and supplies FirePlus panels, cards and compatible devices with submittals and datasheets, plus design, installation, programming, testing, commissioning and maintenance. For the other families see ZFP touchscreen panels and the Context Plus brand page.
FAQ
How many devices does the FirePlus fire alarm panel support?
Up to 126 devices per loop, so up to 756 on the 6 loop model, with 500 mA per loop.
Can a FirePlus panel be expanded after installation?
Yes for the 1 to 3 loop models, which grow to 4 loops with the ULP-1L/XT card, plus the ULP-TB when going from two to three loops.
When does FirePlus need a separate battery cabinet?
On ULP-CON5L and ULP-CON6L, which use the ULP-BCG cabinet.
Is the FirePlus panel UL certified?
The UL certificate in the submittal lists the 1 to 4 loop models to EN 54 parts 2 and 4 under file S36045. Check the approval each project specification requires.
How many zones does FirePlus support?
Up to 64. It ships with 32 zonal LEDs and the ULP-32LED board adds zones 33 to 64.
How is FirePlus connected to a BMS?
Through the ULP-HLI board, which provides RS232, RS485 and Modbus outputs, with the MB3170 gateway where TCP/IP is needed.
Summary
FirePlus covers the ground between small panels and large networked panels: 1 to 6 loops, 126 devices per loop, 64 zones, and cards for networking, repeaters and BMS links. The right choice starts with the device count, then matches the model to the approval the specification requires, then settles batteries and accessories before supply.
Need to size a FirePlus panel and its accessories? Send us the device schedule and specification, and our technical supply team will prepare the offer with submittal and datasheets. Contact the AZEIDK team
Related guides
- Kitchen Fire Suppression System in Makkah: Hotel, Restaurant and Catering Kitchens Through the Seasons
- Hikvision in Saudi Arabia: CCTV and Access Control Systems
- Salamah Licence for Warehouses: Alarm and Firefighting Readiness
- CCTV Software for PC: Hikvision iVMS-4200 and Dahua SmartPSS, Adding Devices, Recording and Export