K11.2 Storage Sprinkler for Warehouses: Victaulic FL-SR/ST V3403 Upright and V3407 Pendent

K11.2 Storage Sprinkler for Warehouses: Victaulic FL-SR/ST V3403 Upright and V3407 Pendent

A K11.2 storage sprinkler has a larger orifice than an office sprinkler and delivers more water at the same pressure, which is why it is used in warehouses and storage areas that need higher water densities. In Saudi Arabia AZEIDK supplies Victaulic FireLock FL-SR/ST K11.2 storage sprinklers in two models: V3403 upright and V3407 pendent, both CMDA type with standard response.

This guide explains what CMDA means, how it differs from ESFR, the datasheet specifications, and the storage types Victaulic lists for these heads together with the reference standard for each.

Key points

  • V3403 upright and V3407 pendent, both CMDA, standard response (SR).
  • K-factor 11.2 imperial, 16.1 S.I.
  • Connection 3/4 in NPT, 20 mm BSPT or IGS grooved.
  • Maximum working pressure 175 psi, UL/FM minimum operating pressure 7 psi, 100% factory test at 500 psi.
  • Temperature ratings in the cULus and FM tables: 57, 68, 79, 93 and 141°C.
In this article
  1. What is a CMDA K11.2 storage sprinkler?
  2. CMDA storage sprinkler vs ESFR
  3. FL-SR/ST specifications from the datasheet
  4. Storage types Victaulic lists for this sprinkler
  5. Temperature ratings and IGS connection
  6. Installation and maintenance notes
  7. How AZEIDK helps
  8. FAQ
  9. Summary

What is a CMDA K11.2 storage sprinkler?

CMDA stands for Control Mode Density Area. The sprinkler controls the fire rather than suppressing it: the system is designed for a set water density over a calculated design area, so the heads contain the fire and limit its spread until the fire service deals with it.

K11.2 means the head flows roughly twice as much as a K5.6 head at the same pressure, since flow equals K times the square root of pressure. That makes high storage densities reachable without very high pressures. See our guide to sprinkler head types and K-factor.

CMDA storage sprinkler vs ESFR

ESFR (Early Suppression Fast Response) works differently: it aims to suppress the fire with large drops and very high flow, and is designed on a fixed number of heads at a minimum pressure. CMDA is designed on density and area, and here the response is standard.

  • ESFR: usually suitable where the ceiling, storage height and the standard’s limits allow it, and often reduces the need for in-rack sprinklers.
  • CMDA such as FL-SR/ST: more flexible with ceiling types and obstructions, but may need higher densities or in-rack sprinklers depending on commodity and height.

The choice is a design decision based on commodity, storage height and ceiling. For the bigger picture see fire protection for warehouses and logistics facilities.

FL-SR/ST specifications from the datasheet

ItemV3403V3407
OrientationUprightPendent
Type and responseCMDA, standardCMDA, standard
K-factor11.2 (16.1 S.I.)11.2 (16.1 S.I.)
Connection3/4 in NPT, 20 mm BSPT, IGS3/4 in NPT, 20 mm BSPT, IGS
Max working pressure175 psi (1200 kPa)175 psi (1200 kPa)
GuardV34/V36V34/V36
  • Factory test: 100% hydrostatic at 500 psi (34 bar).
  • Minimum operating pressure: 7 psi (0.5 bar) for UL and FM.
  • Materials: bronze deflector, load screw and pip cap, brass frame, PTFE coated beryllium nickel spring seal, 3.0 mm nominal glass bulb.
  • Finishes: plain brass, chrome, white polyester, flat black and custom colours.

When pressure is in bar, the datasheet notes that the S.I. K-factor is multiplied by 10 (16.1 becomes 161), a point to watch in metric hydraulic calculations.

Storage types Victaulic lists for this sprinkler

The performance section of the datasheet links each storage type to its NFPA reference and the matching FM Global data sheet:

Storage typeNFPAFM Data Sheet
Open frame single, double, multiple-row or portable racks, Class I-IV and Group A or B plasticsNFPA 132-0
Solid pile or palletized, Class I-IV and Group A or B plasticsNFPA 132-0
Idle palletsNFPA 138-24
Rubber tiresNFPA 138-3
Rolled paperNFPA 138-21
Flammable liquidsNFPA 307-29
AerosolsNFPA 30B7-31
Automotive components in portable racksNFPA 13 (control mode only)N/A

The table tells you where to find the design criteria; it does not replace them. Density, area, maximum storage height and any in-rack heads come from the standard and the approved design. In Saudi Arabia the binding requirements are SBC 801 and Civil Defense, with NFPA and FM as technical references. For tyre warehouses see tyre and rubber storage fire protection.

Temperature ratings and IGS connection

The listing tables show 57, 68, 79, 93 and 141°C for both models under cULus and FM. In non air conditioned Saudi warehouses the temperature under a metal roof can rise sharply in summer, so the rating should be based on a realistic ambient value at the ceiling, not the default office choice.

IGS is Victaulic’s installation-ready grooved sprinkler connection, installed with the V9 coupling using a 3/16 hex bit. The datasheet refers to instructions I-V9 for installation and publication 10.65 for the coupling.

Installation and maintenance notes

  • Depressurise and drain the system completely before installing, removing or adjusting any head, as Victaulic requires.
  • Use the correct wrench: V34 recessed, V34 open end, or the hex bit for V9.
  • In forklift aisles the V34/V36 guard protects heads from impact.
  • Stock must keep the required clearance below the deflector per the standard; goods stacked close to the head spoil the spray pattern.
  • Inspect and test periodically to the adopted standard and Victaulic instructions I-40.

These points often come up in Civil Defense warehouse inspections. See Salamah licence for warehouses.

How AZEIDK helps

AZEIDK supplies FL-SR/ST sprinklers in both models with datasheets and listing tables for the submittal, reviews model, temperature and connection on the drawings, and can extend the work to installation, testing and commissioning. See our warehouses and logistics page and Victaulic in Saudi Arabia.

FAQ

What does CMDA mean?

Control Mode Density Area: a fire control sprinkler whose system is designed for a set water density over a calculated design area.

What is the difference between V3403 and V3407?

V3403 is upright and sits above the pipe; V3407 is pendent and hangs below it. Both share K11.2, pressure rating and standard response.

What is the working pressure of the Victaulic K11.2 storage sprinkler?

Maximum 175 psi, UL/FM minimum operating pressure 7 psi, and each head is factory tested at 500 psi.

Is a K11.2 sprinkler a replacement for ESFR?

Not directly. They are designed in different ways, and commodity, storage height, ceiling and the adopted standard decide which one applies.

Can it protect idle pallets and tyres?

The datasheet lists these storage types with their reference standards, but density and allowable height come from the approved design.

What connection sizes are available?

3/4 in NPT, 20 mm BSPT, or IGS grooved with the V9 coupling.

Summary

The Victaulic FL-SR/ST K11.2 storage sprinkler is a CMDA option for warehouses, with V3403 upright and V3407 pendent. Its value shows when it is chosen from the commodity, storage height and ceiling temperature, using the datasheet’s application table as the starting point to the right standard.

Planning warehouse protection? Send the layout, commodity, storage height and roof type, and we will send suitable sprinklers and datasheets for your submittal. Contact the AZEIDK team