Victaulic is a US company based in Easton, Pennsylvania, with roots going back to 1919, that makes mechanical pipe joining products, valves and fire sprinklers. AZEIDK supplies its FireLock sprinklers: the K16.8 early suppression fast response (ESFR) storage sprinkler, K11.2 storage sprinklers, V27 K5.6 sprinklers and horizontal sidewall sprinklers. This page covers the range and what to check before approval.
Key takeaways
- The manufacturer is Victaulic Company of Easton, Pennsylvania, in mechanical pipe joining since 1919, whose products include fire sprinklers.
- AZEIDK’s Victaulic range covers storage sprinklers for warehouses and standard and sidewall sprinklers for general buildings.
- Victaulic data sheet 44.11 (updated May 2026) gives the V4702 ESFR as quick response, K16.8, 155°F and 200°F ratings and 175 psi maximum working pressure, with cULus listing and FM approval.
- Approvals vary by model, temperature rating, finish and escutcheon, so rely on the latest data sheet and the agency listings.
- Commodity, storage arrangement, ceiling height and the design standard (NFPA 13 or FM Data Sheets) decide which storage sprinkler fits.
Who is Victaulic?
Victaulic says its history dates to 1919, when the patent was filed for the coupling that later carried its name, and that its headquarters is in Easton, Pennsylvania. Its products include couplings, fittings, flow control valves, fire sprinklers and hydronic balancing equipment.
Victaulic sprinkler data sheets carry an approvals table for each model and advise checking the agency websites for the latest certification status. The listing is reviewed for the model, temperature rating and finish required, not for the series in general.
Victaulic sprinklers AZEIDK supplies
- The V4702 ESFR storage sprinkler: a quick-response pendent sprinkler with a K-factor of 16.8, 155°F (68°C) and 200°F (93°C) ratings and 175 psi maximum working pressure, for wet-pipe storage systems.
- FL-SR/ST K11.2 storage sprinklers: V3403 upright and V3407 pendent, standard response, for control mode density/area (CMDA) designs, with ratings from 135°F (57°C) to 286°F (141°C).
- V27 K5.6 sprinklers: V2703 standard-response upright, V2704 quick-response upright, V2707 standard-response pendent and V2708 quick-response pendent. The publication on our product page is marked as a discontinued submittal, so confirm current availability and the latest data sheet before specifying.
- FL-QR/SW horizontal sidewall sprinklers: quick response with K-factors of 2.8, 4.2, 5.6 and 8.0 (V2826, V4226, V2710 and V3410), with approvals that vary by model.
| Product line | Typical use | Key specification or approval as published |
|---|---|---|
| V4702 ESFR | High-piled and rack storage warehouses | K16.8, quick response, 155°F and 200°F, 175 psi; cULus and FM per data sheet 44.11 |
| FL-SR/ST V3403 and V3407 | Storage under density/area design | K11.2, standard response; cULus and FM per Victaulic data sheet 44.51 |
| V27, V2703 to V2708 | Offices, hospitals and general buildings | K5.6, upright or pendent, standard or quick response; source publication marked discontinued, confirm current status |
| FL-QR/SW, V2826 to V3410 | Rooms and corridors with wall-run piping | K2.8 to K8.0, quick response; approvals vary by model |
Where it fits in Saudi projects
ESFR and K11.2 storage sprinklers serve warehouses, distribution centers and logistics facilities, where storage height and commodity drive the protection method. ESFR sprinklers are suppression-mode storage sprinklers, while K11.2 storage sprinklers work in control mode.
V27 sprinklers suit offices, hospitals, factories and general buildings, while horizontal sidewall sprinklers serve rooms and corridors where ceiling piping is impractical, such as hotel rooms and apartments. The approved design under the Saudi Fire Protection Code (SBC 801) and Civil Defense requirements sets the sprinkler type and layout.
What to check before approval
- The design basis, NFPA 13 or FM Data Sheets, and a sprinkler with the matching cULus listing or FM approval.
- For storage: commodity, arrangement, storage and ceiling height, which decide whether ESFR or a density/area design applies and the pressure needed.
- The temperature rating against the highest expected ceiling temperature, especially under metal roofs in summer.
- The K-factor and minimum operating pressure against the hydraulic calculations.
- Escutcheons for recessed installation, since the approval is tied to the escutcheon named in the data sheet.
- The latest data sheet for each model, as older submittals may be superseded or models discontinued.
How AZEIDK helps
AZEIDK supplies Victaulic sprinklers within our fire fighting systems solutions. Engineering design and calculations set the density and pressure, and technical selection of systems and equipment matches the model and temperature rating. We also support Civil Defense approval and keep systems ready through annual maintenance contracts.
For more detail, see our guides to the NFPA 13 standard, high-rack warehouse protection with ESFR, sprinkler system types and UL listing vs FM approval, or browse our products page.
FAQ
Who is Victaulic?
Victaulic is a US company based in Easton, Pennsylvania, whose history dates to 1919, when the patent was filed for the mechanical coupling that carries its name. It makes couplings, fittings, valves and fire sprinklers. AZEIDK supplies its FireLock sprinklers for storage and general buildings as shown on our product pages.
Is the V4702 ESFR sprinkler right for my warehouse?
That depends on the commodity, storage arrangement, storage and ceiling height, roof slope and design standard. Victaulic’s data sheet describes the V4702 as a quick-response K16.8 storage sprinkler and refers to NFPA 13 and FM Data Sheets in its application tables. The designer checks the listing limits for the actual case before selecting it.
Are Victaulic sprinklers UL listed and FM approved?
It varies by model. The V4702 data sheet lists cULus and FM, data sheet 44.51 gives both for the K11.2 storage sprinklers, and sidewall approvals vary by model, arrangement and finish. Check the approvals table in the latest data sheet for the model and confirm it on the agency websites.
How does ESFR differ from the K11.2 storage sprinklers?
ESFR is a suppression-mode storage sprinkler: its fast-response element opens it early and its large K-factor delivers a heavy discharge. The K11.2 sprinklers are standard response and work in control mode under a density/area design. Storage height, ceiling height and commodity decide which suits the project.
When are horizontal sidewall sprinklers used?
They are used where ceiling piping is impractical. They mount on the wall and throw water across the room, as in hotel rooms, apartments and corridors. AZEIDK offers them with K-factors from 2.8 to 8.0, and the design sets their coverage and spacing according to the listing of the chosen model.
Designing a sprinkler system for a warehouse or building? Send us the drawings and storage data, and we will propose the right Victaulic sprinklers and review their approvals with you. Contact the AZEIDK team