TYCO sprinkler installation (TYCO by Johnson Controls) starts with each model’s datasheet. It names the only wrench you may use, the tightening torque range in lb-ft and N·m, and the order for fitting the escutcheon or cover plate. A standard wrench or excess torque can distort the sprinkler inlet and cause leakage or impairment, and a sprinkler damaged by wrench slippage is replaced, never repaired.
This guide brings together the official installation instructions for the TYCO models AZEIDK GROUP supplies in Saudi Arabia: Series TY-B, the Royal Flush II concealed pendents TY3531 and TY3551, the RFII-C TY3582 concealed corridor sprinkler, the EC-8C TY4282 recessed corridor sprinkler, the Series DS-1 dry sprinklers and the RFII-MRI TY3537. If you are still choosing between brands, start with TYCO vs Victaulic sprinklers. This article picks up once the model is approved in the submittal.
Key takeaways
- Each model has a specified wrench: W-Type 6 for exposed TY-B, W-Type 7 for recessed, the RFII wrench for Royal Flush II and RFII-MRI, and the W-Type 40 for RFII-C.
- Torque is 7 to 14 lb-ft (9.5 to 19.0 N·m) for 1/2 in. NPT inlets, 10 to 20 lb-ft for 3/4 in. NPT, and 20 to 30 lb-ft for the 1 in. NPT DS-1 dry sprinkler.
- Never make up for insufficient escutcheon or cover plate adjustment by over- or under-tightening. Reposition the sprinkler fitting instead.
- While the protective cap is on a concealed sprinkler, the datasheet considers the system “Out of Service”.
- DS-1 dry sprinklers are made to a measured order length and must not be installed in elbows.
In this article
- Why does the datasheet specify the wrench and torque?
- TYCO sprinkler installation table: wrench and torque by model
- How is a TY-B sprinkler installed, exposed and recessed?
- Installing Royal Flush II, RFII-C and RFII-MRI concealed sprinklers
- What is different about the EC-8C corridor sprinkler?
- DS-1 dry sprinkler installation: length, fitting and sealing
- Handling and protection rules before handover
- Frequently asked questions
- Summary
Why does the datasheet specify the wrench and torque?
A sprinkler is a precision device: a glass bulb filled with heat-sensitive fluid, a sealing assembly, a frame and a deflector. That is why TYCO datasheets require replacing any sprinkler damaged by dropping, striking, wrench twist or wrench slippage.
On torque, the datasheets state that levels above the listed range may distort the sprinkler inlet, with consequent leakage or impairment. Every datasheet also says not to compensate for insufficient adjustment by under- or over-tightening, and to readjust the position of the sprinkler fitting. The datasheets also refer installers to TFP700 for the “Installer Warning” on handling sprinklers and system components.
TYCO sprinkler installation table: wrench and torque by model
The values below come from each model’s official datasheet. Always check the latest revision before the submittal is approved, as the manufacturer updates its datasheets from time to time.
| Model | Type and inlet | Wrench | Torque | Datasheet |
|---|---|---|---|---|
| TY-B: TY1151, TY1251, TY3151, TY3251, TY4851, TY4951 | Upright and pendent, 1/2 in. NPT | W-Type 6 (end A) exposed; W-Type 7 recessed | 7–14 lb-ft (9.5–19.0 N·m) | TFP151 |
| TY-B: TY4151, TY4251 | Upright and pendent, K8.0, 3/4 in. NPT | W-Type 6 (end B) exposed; W-Type 7 recessed | 10–20 lb-ft (13.4–26.8 N·m) | TFP151 |
| Royal Flush II: TY3531, TY3551 | Concealed pendent, 1/2 in. NPT | RFII wrench only (P/N 56-000-1-075) | 7–14 lb-ft (9.5–19.0 N·m) | TFP181 |
| RFII-C: TY3582 | Concealed corridor, 1/2 in. NPT | W-Type 40 only (P/N 56-000-1-076) | 7–14 lb-ft (9.5–19.0 N·m) | TFP263 |
| EC-8C: TY4282 | Recessed corridor, K8.0, 3/4 in. NPT | W-Type 6 (end B), or W-Type 7 with recessed escutcheon | 10–20 lb-ft (13.6–27.1 N·m) | TFP226 |
| DS-1 dry: TY3155, TY3255, TY3355 | Upright, pendent, horizontal sidewall, 1 in. NPT | Pipe wrench on inlet band or casing, or W-Type 7 on wrench flat | 20–30 lb-ft (26.8–40.2 N·m) | TFP500 |
| RFII-MRI: TY3537 | Non-magnetic concealed, 1/2 in. NPT | RFII wrench only (P/N 56-000-1-075) | 7–14 lb-ft (9.5–19.0 N·m) | TFP262 |
Wrench part numbers per the datasheets: W-Type 6, P/N 56-000-6-387; W-Type 7, P/N 56-850-4-001.
How is a TY-B sprinkler installed, exposed and recessed?
TYCO Series TY-B sprinklers are the most common on projects, and the steps differ between exposed and recessed installation. For the full series specification (K-factors, temperature ratings, approvals) see our TY-B series article.
Exposed upright and pendent
- Install uprights only in the upright position and pendents only in the pendent position.
- Apply pipe thread sealant to the pipe threads and hand-tighten the sprinkler into the fitting.
- Tighten using only the W-Type 6 wrench on the wrench flats: end A for 1/2 in. models and end B for 3/4 in. models, pushing the wrench in to engage the wrenching area.
For wax-coated sprinklers the datasheet allows an 8 or 10 in. adjustable wrench. Open the jaws wide enough to pass over the flats without damaging the wax, close them onto the wrench flats only, and loosen them before removing the wrench. Where bare metal is exposed, the wax on the wrench flats and frame arms may be retouched, only at initial installation, using the temperature-coded wax stick.
Recessed pendent
- Fit the Style 10 (1/2 in. models) or Style 40 (3/4 in. models) mounting plate over the sprinkler threads, then hand-tighten with sealant.
- Tighten using only the W-Type 7 recessed sprinkler wrench on the wrench flats.
- After the ceiling or finish coat is in place, slide the closure over the sprinkler and push it onto the mounting plate until its flange meets the ceiling.
The datasheet warns that a missing escutcheon may delay sprinkler operation in a fire, so no recessed sprinkler should be handed over without one.
Installing Royal Flush II, RFII-C and RFII-MRI concealed sprinklers
A concealed sprinkler comes in two parts: the sprinkler/support cup assembly and the cover plate/retainer assembly. This allows the sprinklers to be installed and pressure tested before the ceiling is closed, with the cover plate fitted after finishing. The steps are closely aligned across the Royal Flush II, RFII-C and RFII-MRI datasheets:
- Install only in the pendent position, with the sprinkler centerline perpendicular to the ceiling.
- Remove the protective cap.
- Apply sealant to the pipe threads and hand-tighten the sprinkler.
- Tighten using only the specified wrench: the RFII wrench for TY3531, TY3551 and TY3537, and the W-Type 40 for TY3582. The RFII wrench has a 7/8 in. (23 mm) square, accepts a 1/2 in. socket drive, and its arrows align with the frame arms.
- Refit the protective cap by pushing it up until it bottoms out on the support cup. It protects the deflector and arms during ceiling work and can mark the center of the clearance hole by gently pressing the ceiling material against it.
- Once the ceiling is complete with a 2-1/2 in. (63.5 mm) clearance hole, remove and discard the cap and check that the deflector moves up and down freely. If it does not, replace the whole sprinkler; do not repair it.
- Screw on the cover plate/retainer assembly until it contacts the ceiling, without lifting the ceiling panel. If it will not engage the cup or reach the ceiling, reposition the sprinkler fitting.
Two points sites often miss. First, the datasheet treats the system as “Out of Service” while the protective cap is in place, so caps must come off before handover and be coordinated with impairment procedures. Second, the nominal 3/32 in. (2.4 mm) air gap between the cover plate lip and the ceiling is necessary for operation; if the ceiling is repainted, the paint must not seal it.
For TY3551 an optional Air and Dust Seal fits onto the retainer before the cover plate, with its bevel oriented as shown in the datasheet. For where concealed and recessed sprinklers each fit, see our concealed sprinkler article.
What is different about the EC-8C corridor sprinkler?
The EC-8C TY4282 throws water in an elongated pattern along the corridor, which adds an orientation step. TFP226 requires:
- The deflector parallel to the mounting surface, in the pendent position.
- When tightening, the marking on the deflector pointed toward the 28 ft (8.5 m) coverage length, that is, along the corridor.
- At least 12 ft (3.7 m) between EC-8C sprinklers in the long throw direction to prevent cold soldering, and no two short throw directions facing each other.
- Only a Style 30 (up to 1/2 in. adjustment) or Style 40 (3/4 in.) escutcheon for recessed installation, with the W-Type 7 wrench.
DS-1 dry sprinkler installation: length, fitting and sealing
DS-1 dry sprinklers are used where the sprinkler or part of its connecting pipe may be exposed to freezing, such as freezers and cold rooms. TFP500 gives the most detailed instructions of the group:
- Order length: each dry sprinkler is made to a length measured for its location per the datasheet figures and rounded to the nearest 1/4 in. It cannot be adjusted on site, so a length schedule goes with the order.
- Fitting: the 1 in. NPT outlet of a malleable or ductile iron tee to ANSI B16.3, or cast iron to ANSI B16.4. Never an elbow, as the sprinkler inlet can contact the inside of the elbow.
- Exposure length: on wet systems protecting a cold area, Table C gives the exposed barrel length from the fitting face to the heated-side surface to prevent freezing by conduction.
- Sealing the clearance space: the datasheet, citing NFPA 13, requires sealing around the barrel between the freezing area and the wet system area to stop condensation and ice build-up; the DSB-2 boot can provide the seal.
- Tightening: a non-hardening sealant such as TEFLON, then a pipe wrench on the inlet band or casing, or a W-Type 7 on the wrench flat, at 20–30 lb-ft. If removal is needed, use the same method and inspect the sprinkler.
Maximum working pressure for DS-1 is 175 psi (12.1 bar) per the datasheet. For DS-1 applications in detail, see our DS-1 dry pendent article.
Handling and protection rules before handover
These instructions repeat across the TYCO datasheets for all the models above, and they are what a supervisor usually checks before acceptance:
- Bulb check: never install a sprinkler with a cracked bulb or lost fluid. Held horizontally, a small air bubble should be visible, about 1.6 mm across for the lower temperature ratings.
- No paint: sprinklers and cover plates are never painted, plated, coated or altered after leaving the factory; modified sprinklers are replaced. Coloured cover plates are ordered factory-finished.
- Replace, do not repair: any sprinkler dropped, struck, damaged by wrench slippage, leaking or corroded is replaced.
- No reinstallation: for concealed sprinklers, a removed sprinkler or its replacement is not reinstalled without refitting the cover plate assembly, and a dislodged cover plate is replaced immediately.
- Daily use: nothing is hung from sprinklers, and they are cleaned only by gentle dusting.
- Spare wrenches: the spare sprinkler cabinet needs a wrench for each sprinkler type installed in the building; see our spare sprinkler cabinet article.
The datasheets place responsibility for inspection, testing and maintenance on the owner, in line with NFPA 25 and the authority having jurisdiction.
Frequently asked questions
What is the torque for a 1/2 in. TYCO sprinkler?
7 to 14 lb-ft (9.5 to 19.0 N·m) for 1/2 in. TY-B models, Royal Flush II, RFII-C and RFII-MRI, per each model’s datasheet.
Can I install a TYCO sprinkler with an ordinary adjustable wrench?
Only in one case named in the TY-B datasheet: wax-coated sprinklers, with an 8 or 10 in. adjustable wrench on the wrench flats only. For all other models use the wrench the datasheet specifies.
Which wrench is used for Royal Flush II?
Only the RFII wrench, P/N 56-000-1-075 per TFP181, which is also used for RFII-MRI. RFII-C uses the W-Type 40.
Why won’t the cover plate reach the ceiling?
The sprinkler fitting is outside the adjustment range. The datasheet fix is to reposition the fitting, not to change the tightening.
When should the protective cap come off a concealed sprinkler?
After the ceiling is finished and immediately before fitting the cover plate. While the cap is on, the datasheet considers the system out of service.
How do I order the right length of DS-1 dry sprinkler?
Measure the order length for each sprinkler per the TFP500 figures, round to the nearest 1/4 in., and send the length schedule with model, temperature rating, finish and escutcheon type.
Summary
Installing TYCO sprinklers correctly comes down to three things: the wrench specified for the model, torque within the datasheet range, and fitting the escutcheon or cover plate in the order the datasheet sets. Keep current datasheets on site, and hand over the wrenches with the spare sprinkler cabinet.
Need TYCO sprinklers with the right wrenches and escutcheons for your project? Send us your bill of quantities with models, temperature ratings, finishes and any dry sprinkler lengths, and we will prepare an offer with current datasheets as part of AZEIDK GROUP’s fire fighting systems. Contact AZEIDK GROUP
Related guides
- Context Plus SigTEL Fire Telephone System: 8-Line Master Controller and Floor Outstations
- Requirements for Restaurants in Malls in Saudi Arabia: Hood Suppression, Mall Fire Alarm Interface and Landlord Approval
- Door Access Control System Cost in Saudi Arabia: Reader, Lock, Exit Button, Controller and Software
- Fire Extinguisher Bracket (Stand / Holder): Wall, Floor and Vehicle Types and How to Choose by Extinguisher Size