Context Plus SigTEL Fire Telephone System: 8-Line Master Controller and Floor Outstations

Context Plus SigTEL Fire Telephone System: 8-Line Master Controller and Floor Outstations

A fire telephone system is a dedicated two-way voice line that links the control room or fire command room to fixed outstations in stairs, lobbies and refuge areas, so firefighters, fire marshals and building management can talk during a fire without relying on mobile phones or the office PBX. The Context Plus SigTEL system is built from a 4, 8 or 16-line master controller, red fire telephone outstations and green refuge outstations, running on 24 VDC with standby batteries. This guide walks through the product family as the datasheets describe it, where each part goes and how the system is tested at handover. SigTEL is part of the AZEIDK fire alarm systems range in Saudi Arabia.

Key takeaways

  • The ECU-8 master controller serves 8 lines and expands to 16 with one ECU-8S expansion unit.
  • Type A fire telephone outstations are red with a handset; Type B refuge outstations are green or stainless steel, for people who cannot evacuate easily.
  • Each outstation runs on 2-core 1.5 mm² fire-rated cable, up to 1 km long, according to the Context Plus catalog.
  • Two 12 V 7 Ah batteries give 24 hours standby and 3 hours in use, per the datasheet.
  • Context Plus states that SigTEL meets the requirements of BS 5839-9, the British code for emergency voice communication systems, when installed correctly.
In this article
  1. What is a fire telephone system, and how is it different from voice evacuation?
  2. The Context Plus SigTEL product family
  3. How do you size the fire telephone master controller?
  4. Where do fire telephone and refuge outstations go?
  5. Cabling and standby power
  6. How is a fire telephone system tested at handover?
  7. What should a fire telephone quotation include?
  8. Frequently asked questions
  9. Conclusion

What is a fire telephone system, and how is it different from voice evacuation?

Owners often mix up three voice systems in one building. A voice evacuation (voice alarm) system broadcasts recorded or live messages one way to every floor. The PBX handles daily staff calls. A fire telephone is a full duplex link between a fixed point on site and a master controller in the control room, and it keeps working when mains power or the mobile network inside the building fails.

BS 5839-9 calls this category emergency voice communication (EVC). The SigTEL catalog splits outstations into two types: Type A fire telephones used by firefighters and fire marshals, and Type B refuge points where a disabled person, or anyone who needs help on the stairs, waits for assistance. Both types can sit on the same controller.

Whether a specific building needs a fire telephone is decided by the code adopted for the project, the Civil Defense approval and the consultant’s specification. We cover the regulatory and refuge side in a separate article; this one focuses on the product and how to select it.

The Context Plus SigTEL product family

AZEIDK lists almost the full SigTEL family among its Context Plus products. Here is each part and what its datasheet says:

PartModelRoleKey datasheet points
8-line master controllerECU-8Receives calls from outstations and calls them back8 lines, expands to 16 with ECU-8S, line names up to 15 characters, auto-learn
Other master controllersECU-4, ECU-16, ECU-8NTSame role at 4 or 16 lines; ECU-8NT has no handsetLCD display, fail-safe fault relay rated 30 V 1 A
Desk controllerECU-224Extra control point with handset and display in a security room or receptionUp to 14 on a network, connects through an ECU723 card
Fire telephone outstationEVC301RPOType A in a red steel cabinetTrue duplex speech; locking and non-locking versions
Key-lockable fire telephoneEVC301RLKType A behind a locked door to stop misuseRed steel RAL 3000, IP20
Refuge outstationEVC302GSType B for disabled refuge areasStainless or green steel; surface, flush or weatherproof options
Hands-free refuge outstationEVC302GFType B operated by a push buttonFlush mounting, output to trigger CCTV, induction loop terminals
Roaming handset and jack plateEVC301/PH and EVC301/JPHandset carried by the response team and plugged into fixed platesOne handset can serve several plate locations
Network cards and PC kitECU722, ECU723, ECU423Link several controllers and program names from a PCVoice on one loop, data on RS485, 1 km total network length

How do you size the fire telephone master controller?

Start by counting outstations on the drawings: every fire telephone or refuge point takes its own line on the controller. A six-storey building with one fire telephone and one refuge point on each main stair landing needs roughly 12 lines, so you would pick an ECU-8 with an ECU-8S expansion, or an ECU-16 if it is offered. Always keep spare lines for drawing changes during construction.

Large campuses and multi-building sites need a network. The SigTEL catalog describes up to four networked master controllers for systems of up to 64 lines, while the ECU722 network card page mentions up to 14 master controllers and the controller page refers to systems of up to 224 lines with desk controllers. The difference comes from the networking method and cards used, so ask the supplier to confirm the approved capacity for your exact configuration in the submittal before approval.

Also decide where the controller sits. The catalog mentions anti-tamper enclosures for controllers in public areas, and an ECU-224 desk unit can be added in the security room so more than one person can answer.

Where do fire telephone and refuge outstations go?

The product pages list fire fighting lobbies, stairwells, plant rooms and Civil Defense contact points for Type A outstations, and stair landings and lift lobbies for Type B refuge points. The final number and location in your project come from the approved design, not the catalog.

  • Locking or non-locking: in public areas such as malls and stadiums, the EVC301RLK reduces misuse, but the page reminds owners to issue the key to every responsible person.
  • Handset or push button refuge point: the EVC302GF works with an external button and no handset, which is easier for a wheelchair user.
  • Interfaces: controllers and outstations support disabled toilet alarms (NC951), hearing induction loops, strobes and a relay that switches a CCTV camera to the calling point.
  • Roaming handset: useful when the response team prefers one handset that plugs into several EVC301/JP plates instead of fixed handsets everywhere.

Cabling and standby power

The catalog is clear here: each line from controller to outstation is 2-core 1.5 mm² enhanced fire-rated cable up to 1 km, and the network between controllers is 4 x 2-core 1.5 mm² fire-rated cable with a total length of 1 km. Because the system is used during the fire itself, cable choice and fixing are part of system integrity; see our guide to fire alarm cables and circuit integrity. The network card page also recommends two separate cable routes, each carrying a voice and a data cable.

Master controllers take 230 V mains and run internally at 24 VDC. With two 12 V 7 Ah batteries the system keeps going for 24 hours standby and 3 hours in use after a mains failure, per the datasheet. If you add outstations or loads, work out quiescent current from the page data: 100 mA for the controller, 1 mA per Type A outstation and 3.2 mA per Type B outstation.

How is a fire telephone system tested at handover?

Testing happens during testing, commissioning and handover and usually covers these practical steps:

  1. Check the cables before connecting equipment. The catalog mentions an optional FiTT line tester for finding cable faults first.
  2. Run auto-learn so the controller detects all outstations, then give each line a clear name such as “Stair 2 Level 4” (up to 15 characters).
  3. Make a test call from every outstation to the controller and back, and confirm clear speech both ways.
  4. Simulate faults: open a line or cut mains power, and confirm the fault shows, the batteries take over and the fault relay operates.
  5. Test any agreed interface, such as CCTV or a strobe triggered by a call.
  6. Hand over a list of line names and locations with the as-built drawings in the handover file.

After commissioning, the system falls under the fire, safety and alarm maintenance contract, which is separate from the low current and CCTV contract. See preventive and periodic maintenance for the visit scope.

What should a fire telephone quotation include?

We do not quote prices here because cost depends on the project, but these factors drive it: the number and type of outstations (Type A or Type B, locking or not), controller size and expansion units, networking between buildings or extra desk controllers, fire-rated cable lengths, and interfaces with CCTV or toilet alarms. Ask for the datasheet of every model and a bill of quantities, and have the consultant check the outstation count against the approved drawings before supply.

Frequently asked questions

What is the difference between a fire telephone and a refuge point?

A fire telephone (Type A) is used by firefighters and fire marshals to talk to the control room. A refuge point (Type B) is used by someone waiting for help to evacuate, such as a wheelchair user, to speak to the control room.

Does the SigTEL fire telephone work during a power cut?

Yes. The datasheet gives 24 hours standby and 3 hours in use on two 12 V 7 Ah batteries.

How many lines can a fire telephone controller handle?

Controllers come in 4, 8 or 16 lines, and the ECU-8 expands to 16 with an ECU-8S. Larger systems link several controllers with network cards; confirm the final capacity in the submittal.

What cable does a fire telephone system use?

2-core 1.5 mm² fire-rated cable to each outstation, up to 1 km long, according to the Context Plus catalog.

Can a refuge point switch on a CCTV camera?

Yes. The EVC302GF has an output that closes during a call and can trigger a camera, and the controllers support CCTV relays.

Can a fire telephone replace a voice evacuation system?

No. Voice evacuation broadcasts to the whole building, while a fire telephone is a two-way link between one point and the control room. Whether you need one or both is set by the design and the adopted code.

Conclusion

A SigTEL fire telephone system comes down to three decisions: controller capacity based on the outstation count, the type of each outstation based on its location and user, and fire-rated cable on a protected route. Lock these into the submittal with the datasheets, then test every line in both directions before handover.

Need a fire telephone or refuge system for your project? Send your drawings or BOQ and the AZEIDK team will help you select, supply, install and test SigTEL models, with support for your Civil Defense approval file. Talk to the AZEIDK team

References: Context Plus SigTEL Fire Telephone / Disabled Refuge System catalog; AZEIDK SigTEL product pages (ECU-8, ECU-4/ECU-16/ECU-8NT, ECU-224, EVC301RPO, EVC301RLK, EVC302GS, EVC302GF, EVC301/PH, ECU722/ECU723/ECU423); BSI Knowledge: Understanding the emergency voice communication systems standard (BS 5839-9:2021).
Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.