TYCO or Victaulic sprinklers? AZEIDK supplies both brands in Saudi Arabia, but what each brand has on the site is different. The TYCO range covers the TY-B standard sprinkler and a set of special application sprinklers (concealed, recessed, non-magnetic and dry), while the Victaulic range covers the V27 standard sprinkler in two response types plus K11.2 and ESFR K16.8 storage sprinklers. So the practical question is not which brand is better, but which sprinkler each part of the project needs.
Both brands have their own pages, TYCO and Victaulic, and sit within AZEIDK’s fire fighting systems scope.
Key points
- Standard sprinklers: TYCO TY-B is standard response only, in K2.8, K5.6 and K8.0; Victaulic V27 is K5.6 in standard and quick response versions.
- Connections: TY-B has 1/2 or 3/4 in NPT; V27 has NPT, BSPT or an IGS grooved connection.
- Storage sprinklers on the site come from Victaulic: FL-SR/ST K11.2 and ESFR V4702 K16.8.
- Special application sprinklers on the site come from TYCO: Royal Flush II and RFII-C concealed, EC-8C recessed, the non-magnetic MRI model and the DS-1 dry sprinkler.
- Many projects use both brands, each sprinkler where it was designed to go.
Standard sprinklers: TYCO TY-B or Victaulic V27?
| Item | TYCO TY-B | Victaulic V27 |
|---|---|---|
| K-factor | K2.8, K5.6 and K8.0 | K5.6 |
| Response | Standard response | Standard (V2703, V2707) or quick (V2704, V2708) |
| Orientation | Upright and pendent, selected models recessed pendent | Upright, pendent and recessed pendent |
| Connections | 1/2 or 3/4 in NPT, ISO 7-1 on special request | 1/2 in NPT, 20 mm BSPT or IGS grooved |
| Bulb | 5 mm glass bulb | Per model datasheet |
| Working pressure | Per datasheet | Up to 250 psi under UL and 175 psi under FM, each sprinkler hydrostatically tested at 500 psi |
| Approvals listed | UL, C-UL, FM; LPCB, VdS and NYC for selected models | cULus, FM; LPCB and VdS for selected models |
The data comes from AZEIDK’s TYCO TY-B and Victaulic V27 product pages. Approvals vary by model and finish, so read them for the exact model, not the series.
In practice: if the specification calls for a quick response K5.6 sprinkler, the V27 offers it in the same series, while TY-B is a standard response series with smaller and larger K-factors (K2.8 and K8.0). If the network is grooved and you want a grooved sprinkler connection, the V27 offers IGS. Each series is covered in detail in our articles on TYCO TY-B sprinklers and the Victaulic V27 sprinkler.
Storage sprinklers: the Victaulic range
For warehouses and high-piled storage, AZEIDK lists Victaulic FL-SR/ST K11.2 storage sprinklers in upright V3403 and pendent V3407 versions, and the V4702 ESFR K16.8 pendent. The TYCO pages on the site do not list storage sprinklers, so if a project specifies a TYCO storage sprinkler, the model and its datasheet are requested at supply stage. Storage sprinkler selection is covered in our articles on the K11.2 storage sprinkler and the ESFR warehouse sprinkler.
Special application sprinklers: the TYCO range
- Concealed: Royal Flush II and the RFII-C corridor model, for ceilings where appearance matters; see our concealed sprinkler guide.
- Recessed corridor: EC-8C (TY4282); see our article on recessed and extended coverage sprinklers.
- Non-magnetic: RFII MRI (TY3537) for hospital MRI rooms; see MRI room sprinklers.
- Dry: DS-1 for cold rooms, freezers and canopies; see the DS-1 dry sprinkler.
How to choose between the brands
- Split the project by use: offices and corridors, storage, cold rooms, MRI rooms, architectural ceilings.
- Fix the K-factor and response for each area from the hydraulic design and the consultant’s specification.
- Pick the sprinkler that actually covers it from the listed models, rather than assuming one series covers everything.
- Match the approval to the exact model and finish.
- Plan wrenches and spares: the spare sprinkler cabinet needs sprinklers of every type used and the wrench for each.
Common mistakes
- Comparing brand names instead of two specific models.
- Assuming an approval applies to every model and finish in a series.
- Mixing sprinklers with different K-factors or response types in one area when the design does not allow it.
- Forgetting spare sprinklers and wrenches for each type used on the project.
Frequently asked questions
Which is better, TYCO or Victaulic sprinklers?
Neither is better in absolute terms. What matters is the right model for each area and its approval, and the two brands complement each other on many projects.
Is a quick response K5.6 sprinkler available from both brands?
Among the models listed on the site, the Victaulic V27 comes in quick response (V2704 and V2708), while TYCO TY-B is a standard response series.
Which storage sprinklers does AZEIDK list?
Victaulic FL-SR/ST K11.2 (V3403 and V3407) and the ESFR V4702 K16.8.
Which sprinkler suits an MRI room?
A non-magnetic sprinkler such as the TYCO RFII MRI (TY3537) listed by AZEIDK.
Can both brands be used on one project?
Yes, as long as each area uses one sprinkler type that matches the design and spares and wrenches are kept for each type.
Summary
Among the models AZEIDK lists, TYCO is stronger in special application sprinklers and offers TY-B in three K-factors, while Victaulic is stronger in storage sprinklers and offers the V27 in quick response with a grooved option. Choose for each area what was designed for it, and check the approval for the exact model. For sprinkler types in general, see our guide to sprinkler head types and K-factor.
Need sprinklers for a project? Send the drawings and BOQ with the use and K-factor of each area, and the AZEIDK team will recommend the right TYCO or Victaulic models. Contact AZEIDK
Related guides
- Civil Defense Requirements for Offices in Saudi Arabia: Extinguishers, Alarms, Exits and Salamah
- Is FM-200 Safe for Humans? Discharge, Evacuation Time and Re-entry
- Salamah Application Rejection Reasons: Common Civil Defense Licensing Mistakes and How to Fix Them Before Resubmitting
- HPE Aruba Instant On Switches in Saudi Arabia: 1930 and 1960 Series and AP25 and AP27 Access Points for Offices and Branches