Dry or Wet Barrel Fire Hydrant: AFC F-7700, F-8700 and FW-9000 and When to Choose Each

Dry or Wet Barrel Fire Hydrant: AFC F-7700, F-8700 and FW-9000 and When to Choose Each

A fire hydrant is the point where Civil Defense crews take water from a site’s underground fire main. The first decision when you select one is dry barrel or wet barrel. In Saudi Arabia AZEIDK supplies both designs from American Fire Control (AFC): the F-7700 and F-8700 dry barrel hydrants and the FW-9000 wet barrel hydrant. The manufacturer’s catalogue shows all three as UL Listed and FM Approved.

This article explains how the two designs differ, what to read in the datasheet, and when each one makes sense on a Saudi project.

Key takeaways

  • A dry barrel hydrant keeps the main valve below ground and drains its barrel after closing. A wet barrel hydrant is always full of water.
  • F-7700 has a flanged inlet and F-8700 a mechanical-joint inlet, both 6 inch.
  • FW-9000 is a wet barrel hydrant with a 6 inch flanged inlet and a separate operating valve on each outlet.
  • All three: 250 psi maximum working pressure, factory tested to 500 psi, one 4.5 inch pumper outlet and two 2.5 inch hose outlets.
  • UL file EX28963 lists F-7700 and F-8700 (base-valve design) and FW-9000 (wet-barrel design).
In this article
  1. What a fire hydrant does, and how it differs from a hose cabinet
  2. Dry barrel vs wet barrel fire hydrant: how they work
  3. AFC dry and wet barrel hydrants side by side
  4. F-7700 or F-8700?
  5. Which one for a Saudi project?
  6. What to check in the datasheet and submittal
  7. Installation, testing and maintenance
  8. FAQ
  9. Summary

What a fire hydrant does, and how it differs from a hose cabinet

A hose cabinet inside a building is used by occupants or the safety team with a small hose reel. A hydrant stands outside on the underground main and serves the fire brigade: the pumper connects to its large outlet, or crews run 2.5 inch hose lines directly from it. It is built for higher flows and pressures and usually needs protection from vehicle impact because it sits next to roads and truck yards.

In Saudi Arabia the binding requirements are the Saudi Fire Code SBC 801 and the General Directorate of Civil Defense rules on hydrant location and supply. NFPA 24 (Standard for the Installation of Private Fire Service Mains and Their Appurtenances) and the AWWA standards are technical references the designer adopts, with the edition fixed in the project specification.

Dry barrel vs wet barrel fire hydrant: how they work

Dry barrel

The main valve sits at the bottom of the hydrant, at the level of the buried main, and is operated through a long stem from the nut on top of the bonnet. On closing, a drain port opens and the barrel empties. The design was created to prevent freezing, but it has a second benefit: the part above ground carries no water under pressure in normal service.

AFC’s catalogue describes a breakaway design near ground level on F-7700 and F-8700. If a vehicle hits the hydrant, the breakaway section fails, the main valve stays closed below ground, and the hydrant can be repaired without excavation. The seat and disc can also be serviced without digging, according to the catalogue.

Wet barrel

The barrel stays full of water and the operating parts are above ground. Each outlet has its own valve, so one outlet can be opened while the others stay closed. AFC states that the FW-9000 is intended for locations where freezing is not an issue and is designed to reduce the risk of main valve damage if it is struck.

AFC dry and wet barrel hydrants side by side

ItemF-7700 (dry)F-8700 (dry)FW-9000 (wet)
Inlet6 inch flange6 inch mechanical joint (AWWA C153)6 inch flange, ASME B16.5 Class 150
Design standardAWWA C502AWWA C502AWWA C503
Max working pressure250 psi250 psi250 psi
Factory test500 psi500 psi100% to 500 psi
OutletsOne 4.5 inch pumper, two 2.5 inch hose outlets
CoatingEpoxy inside and outside to AWWA C550
Water in barrelDrained after closingDrained after closingAlways full
Bury depth42 to 84 inch in 6 inch stepsNot applicable (flanged above ground)

Source: AZEIDK product pages and the AFC fire hydrant submittal (AZEIDK brand page). The catalogue lists NH threads on the dry barrel outlets and notes that other outlet threads or pumper configurations may be available to suit the project.

F-7700 or F-8700?

The two dry barrel models share the same design, appearance and performance. The difference is the inlet:

  • F-7700, flanged inlet: per the datasheet, compatible with ASME B16.5 Class 150, ISO PN16 and DIN 2503 PN16. It suits any main that ends in a flange.
  • F-8700, mechanical-joint inlet: to AWWA mechanical joint and ANSI/AWWA C153/A21.53. Common on ductile iron underground mains, where it connects with a gland and bolts rather than a flange.

Pick the model that matches the fitting the hydrant will sit on in the underground layout, then set the bury depth (dimension G in the catalogue) to the actual depth of the main on site.

Which one for a Saudi project?

Freezing is not a factor in most of the Kingdom, so the decision is mostly practical:

  • Operation: on a wet barrel hydrant each outlet has its own valve, so a second hose can be connected while the first is flowing. On a dry barrel hydrant one nut opens the main valve and unused outlets stay capped.
  • Impact risk: in truck yards and car parks next to roads, the breakaway design of the dry models is a clear advantage because the main valve stays underground.
  • Cold high ground: AFC gives an operating range starting at 0 °C for FW-9000. If the site can drop below that, choose a dry barrel hydrant.
  • Maintenance: wet barrel hydrants are simpler, with parts above ground. Dry barrel hydrants need a check that the drain works and the barrel empties after use.
  • Project specification: sometimes the owner or consultant names the type. Then the job is to match the model to the specification.

What to check in the datasheet and submittal

  1. Listing and approval: check the exact model in UL Product iQ (AFC file EX28963) and the FM Approvals guide, not only the logo on the catalogue.
  2. Inlet type and size: flange or mechanical joint, and flange drilling against the mating fitting.
  3. Bury depth: dimension G for the dry models, taken from the drawings and actual levels.
  4. Outlet threads: the thread the specification and the authority require. A wrong thread means Civil Defense hoses will not connect.
  5. Pressure: the highest system pressure, including pump churn, must stay within 250 psi.
  6. Accessories: an isolation valve on the hydrant branch, the right connecting piece and impact protection where needed.

AZEIDK’s technical selection team reviews these points against the bill of quantities and prepares the submittal for the consultant.

Installation, testing and maintenance

The hydrant is installed on a branch of the underground main with an isolation valve, so it can be serviced without shutting the network down. After installation the lines are flushed and hydrostatically tested to the project specification and adopted standard, and a flow test confirms network capacity where required. See our guide to fire hydrant flow testing.

Routine maintenance covers ease of operation, caps and chains, leaks, and on dry barrel hydrants a check that the barrel drains after closing. NFPA 25 includes hydrant inspection and testing within the water-based systems program, applied together with the manufacturer’s instructions and Civil Defense requirements. These items are part of AZEIDK’s preventive maintenance contracts.

FAQ

What is the difference between a dry and a wet barrel fire hydrant?

A dry barrel hydrant has its main valve below ground and drains after closing. A wet barrel hydrant stays full of water and has a valve on each outlet.

Are AFC hydrants UL Listed and FM Approved?

According to AFC’s catalogue, yes, and F-7700, F-8700 and FW-9000 appear in UL file EX28963. Check the model and size in the official directory before approval.

What is the working pressure of an AFC fire hydrant?

250 psi maximum, with a factory test to 500 psi on all three models.

What is the difference between F-7700 and F-8700?

Same design; F-7700 has a flanged inlet and F-8700 a mechanical-joint inlet for ductile iron mains.

How many outlets does an outdoor fire hydrant have?

On these AFC models, three: one 4.5 inch pumper outlet and two 2.5 inch hose outlets.

Do I need a dry barrel hydrant in Saudi Arabia?

Not for freezing in most regions, but it helps near roads and car parks thanks to the breakaway design, and on sites that can drop below 0 °C.

Summary

Choosing a fire hydrant starts with dry or wet barrel, then inlet type, bury depth and outlet threads, then verification of the listing for that exact model. The FW-9000 is simpler and gives a valve on each outlet; the F-7700 and F-8700 keep the main valve underground and suit sites exposed to impact. For the hydrant’s role in the wider network see our fire hydrants and landing valves guide, AZEIDK fire fighting systems, and American Fire Control in Saudi Arabia.

Need fire hydrants for your project? Send the inlet type, the depth of the underground main and the outlet thread you need, and we will send the matching AFC model with its datasheet and submittal. Contact the AZEIDK team

References: Submittal for Fire Hydrant, American Fire Control (AZEIDK brand page) (AFC, includes UL Product iQ record EX28963), and the AZEIDK product pages for F-7700/F-8700 and FW-9000