Novec 1230 agent quantity calculation (the chemical FK-5-1-12) for a server room uses the same total flooding equation as other clean agents: weight in kilograms equals the net volume divided by the agent’s specific vapour volume, multiplied by the design concentration over (100 minus the concentration). FK-5-1-12 has its own constants in ISO 14520-5, k1 = 0.0664 and k2 = 0.000274, and the actual concentration at the highest temperature is then checked against the safe exposure limit.
For how clean agent systems are designed, kept safe and maintained, see our FM-200 fire suppression system guide.
This article walks through each step with verified figures and an illustrative worked example. The final design is produced with the listed system’s own flow calculation software, which AZEIDK’s engineering design and calculations team provides for the SFFECO 1230 FK-5-1-12 system within our special fire suppression systems.
Key points
- Equation: W = (V / S) × (C / (100 − C)), with specific volume S = k1 + k2 × T in m³/kg and T in °C.
- FK-5-1-12 constants in ISO 14520-5 are 0.0664 and 0.000274, giving S of about 0.0719 m³/kg at 20°C.
- The standard’s table at 20°C gives 0.7322 kg/m³ for 5% and 0.5796 kg/m³ for 4%.
- ISO 14520-5 minimum design concentration is 5.3% for surface Class A fires and 5.9% for heptane; the NOAEL is 10%.
- The binding design concentration comes from the listed system’s design manual and the standard edition named in the specification.
In this article
- What is the Novec 1230 quantity formula?
- Specific volume and temperature for FK-5-1-12
- Novec design concentration: where does the figure come from?
- Worked example (illustrative only)
- Flooding factor: kilograms per cubic metre
- What the hand calculation does not cover
- Common mistakes
- Frequently asked questions
- Summary
What is the Novec 1230 quantity formula?
Novec 1230 is the well-known trade name for FK-5-1-12 (a fluoroketone), now produced by more than one manufacturer under different names, as explained in our article on Novec 1230 after 3M. A total flooding system fills an enclosure to a set concentration, and the equation used in ISO 14520 and NFPA 2001 is:
W = (V / S) × (C / (100 − C))
- W: agent weight, kg.
- V: net protected volume, m³.
- C: design concentration, % by volume.
- S: specific vapour volume at the design temperature, m³/kg.
The quantity does not rise linearly with concentration, because the agent displaces part of the air that leaves the room during discharge. Raising the concentration by half a point therefore adds slightly more than that share in weight.
Specific volume and temperature for FK-5-1-12
Specific volume changes with temperature as S = k1 + k2 × T. ISO 14520-5 gives k1 = 0.0664 and k2 = 0.000274 for FK-5-1-12. Compared with FM-200 (HFC-227ea), whose k1 is about 0.1269 as shown in our FM200 quantity calculation article, FK-5-1-12 vapour has a much smaller specific volume. The two agents therefore need different weights for the same room, and a weight calculated for one cannot be reused for the other.
| Temperature (°C) | Specific volume S (m³/kg) | Note |
|---|---|---|
| 16 | 0.0708 | Calculated from ISO 14520-5 constants |
| 20 | 0.0719 | Standard table value |
| 30 | 0.0746 | Calculated from ISO 14520-5 constants |
Design practice calculates the quantity at the lowest expected temperature in the enclosure, since S falls as it gets colder and more agent is needed. The concentration at the highest expected temperature is then calculated to check the exposure limit. In air-conditioned server rooms, both limits are agreed with the HVAC engineer rather than assumed.
Novec design concentration: where does the figure come from?
Design concentration starts from the lowest tested extinguishing concentration, multiplied by a safety factor. In ISO 14520-5 the minimum design concentration is the highest extinguishing value multiplied by 1.3:
| Hazard (ISO 14520-5) | Extinguishing concentration | Minimum design concentration |
|---|---|---|
| Surface Class A (highest value: PMMA) | 4.1% | 5.3% |
| Higher hazard Class A | – | 5.6% |
| Class B (heptane, cup burner) | 4.5% | 5.9% |
| NOAEL exposure limit | 10% | |
Projects designed to NFPA 2001 apply different safety factors by fire class and by edition, and the concentration is taken from the listed design manual of the system being installed, to the edition named in the specification. The hazard classification of server and electrical rooms is set by the designer; never copy a concentration from another project without review.
Worked example (illustrative only)
A server room of 6 × 5 × 3 m, no raised floor and no fixed solid objects to deduct:
- Net volume: V = 6 × 5 × 3 = 90 m³.
- Lowest expected temperature: 16°C, so S = 0.0664 + 0.000274 × 16 = 0.0708 m³/kg.
- Design concentration (for illustration): 5.3%, the ISO 14520-5 minimum for surface Class A.
- Weight: W = (90 / 0.0708) × (5.3 / 94.7) ≈ 71.2 kg.
- Check at the highest temperature, 30°C: S = 0.0746, giving an actual concentration of about 5.6%, below the 10% NOAEL.
At 20°C instead of 16°C the result would be about 70.1 kg, so the temperature assumption alone moves the quantity by more than a kilogram. Adding a 40 cm raised floor void would add 12 m³ and raise the quantity in the same proportion.
Selecting the cylinder
The cylinder comes from the manufacturer’s table. The SFFECO 1230 system uses cylinders of 38, 65, 130, 277, 395 and 850 lb according to the product page. 71.2 kg is about 157 lb, within the SF 1230-277 fill range of 111 to 277 lb recorded in the system’s UL listing. The final number of cylinders, nozzles and pipe sizes comes from the listed calculation software.
Flooding factor: kilograms per cubic metre
For a quick estimate, divide the equation by the volume: W / V = C / ((100 − C) × S). The table below is calculated from the ISO 14520-5 constants for three concentrations the standard lists, at 16°C and 20°C:
| Concentration | kg/m³ at 16°C | kg/m³ at 20°C |
|---|---|---|
| 5.3% | 0.791 | 0.779 |
| 5.6% | 0.838 | 0.825 |
| 5.9% | 0.886 | 0.872 |
Multiply the factor by the net volume for an approximate quantity: a 90 m³ room at 16°C and 5.3% needs about 71.2 kg. This helps compare quotations and review a BOQ, but it does not replace the designer’s calculation, the altitude correction or the pipe network calculation.
What the hand calculation does not cover
- Pipe network: pipe and nozzle sizes and discharge time come from the listed hydraulic calculation software; the UL listing for SFFECO systems names a specific program for 1230 systems.
- Altitude: an altitude correction factor is applied from the standard’s table and the system manual.
- Room integrity: the right quantity is useless if the room leaks, so the calculation is completed by a room integrity test.
- Connected spaces: ducts that cannot be closed and ceiling or underfloor voids are added to the volume unless isolated.
Common mistakes
- Using FM-200 constants instead of FK-5-1-12 constants.
- Calculating at the normal air-conditioned temperature instead of the lowest expected temperature.
- Deducting racks and movable equipment from the net volume.
- Forgetting the raised floor void when the designer decides to protect it.
- Taking a concentration from an old catalogue without checking the edition adopted on the project.
Frequently asked questions
How many kilograms of Novec does a 90 m³ server room need?
In our illustrative example at 5.3% and a lowest temperature of 16°C, about 71.2 kg. The actual figure depends on the approved design concentration, the temperatures and the system’s calculation software.
Why is the Novec weight different from FM200 for the same room?
Each agent has a different specific volume and design concentration, so weights cannot be transferred between agents.
Is Novec safe for people in the room?
ISO 14520-5 gives a NOAEL of 10% for FK-5-1-12, above typical design concentrations. Pre-discharge alarms and evacuation procedures still apply.
What is the specific volume formula for FK-5-1-12?
S = 0.0664 + 0.000274 × T, with T in °C and S in m³/kg.
Is a hand calculation enough for approval?
No. Hand calculations are for estimating and checking; drawings submitted for approval rely on the listed calculation software of the chosen system.
Summary
A correct Novec quantity needs four correct inputs: net volume, lowest temperature, a design concentration from an approved reference, and the FK-5-1-12 constants. After that come the exposure limit check, cylinder selection, the network calculation and the integrity test.
Related reading: FM200 Nozzles, American Fire Control FM-200 System and Server Room Fire Suppression in Banks.
Need a clean agent quantity checked for a server room? Send us the room dimensions, raised floor details and temperature limits, and we will prepare a preliminary calculation and an offer for a suitable FK-5-1-12 system. Contact the AZEIDK team
Related guides
- Building Occupancy Certificate on Balady in Saudi Arabia: Conditions, Steps and the Fire System Documents Needed Before Occupancy
- Patch Cord Guide: Cat6, Cat6A and Fibre, Lengths, Colours and When to Replace
- Fitting Out a New Fuel Station with Safety Systems: From Drawing Review to Installation, Handover and Salamah
- Fire Safety in High-Rise Residential Towers