Mixing Firefighting Foam Concentrates of Different Types or Brands: When It Is Allowed and How to Refill a Foam Tank

Mixing Firefighting Foam Concentrates of Different Types or Brands: When It Is Allowed and How to Refill a Foam Tank

Mixing firefighting foam concentrates of different types or brands in one tank is not allowed as a general rule, except with documented compatibility test results and approval by the authority having jurisdiction. The mixture has never been performance-tested, and adverse interactions can appear long after mixing inside the tank, not at the moment of filling.

The question usually comes up when a foam tank is topped up after partial use or expiry, or when the supplier changes. This guide sets out what manufacturers and regulators say, when mixing may be acceptable, and how to refill a tank safely using Safe Guard AFFF or another concentrate.

Key points

  • Rule of thumb: do not mix concentrates of different types or manufacturers in storage.
  • Chemguard notes that NFPA 11 (2002 edition) allowed mixing in specific cases, based on documented test results and authority approval.
  • Mixing is considered only for two concentrates of the same type and the same proportioning rate (1% with 1%, 3% with 3%).
  • Synthetic is not mixed with protein, hydrocarbon-only with alcohol-resistant, or regular with low-temperature foam.
  • Finished, expanded foam can be applied alongside other foams on the same fire; the issue is mixing concentrates in the tank.
In this article
  1. Why is mixing foam concentrates in a tank avoided?
  2. What do standards and regulators say about mixing firefighting foam?
  3. When can firefighting foam be mixed, and when not?
  4. How to refill a foam tank without mixing
  5. Testing the old concentrate before topping up
  6. Supply of foam concentrate and foam tanks
  7. Questions to ask before buying a replacement foam
  8. Frequently asked questions
  9. Summary

Why is mixing foam concentrates in a tank avoided?

A foam concentrate is a carefully balanced chemical blend: surfactants, solvents, stabilizers and sometimes polymers. Each manufacturer tests its own product to gain listing or approval. A blend of two products has been tested by no one, and its performance may differ widely from either component.

A technical bulletin from the foam manufacturer Dr. Sthamer warns that adverse changes in a mixture may occur a long time after mixing, and that a positive compatibility test does not guarantee long-term stability or performance. It sums up the principle as: do not mix unless you ultimately have to.

In bladder tanks this matters even more, since the concentrate sits in the bladder for years and any sediment or viscosity change affects the ratio controller. For how proportioning works, see foam proportioning and bladder tanks.

What do standards and regulators say about mixing firefighting foam?

  • NFPA 11: Chemguard states that NFPA had not allowed mixing of concentrates in storage, and that the 2002 edition of NFPA 11 made allowances under certain circumstances: documented test results and approval by the authority having jurisdiction.
  • Canadian regulation CAR 325.47: as quoted in Transport Canada rooftop heliport guidance, foam concentrates of different types or manufacturers are not mixed unless shown to be interchangeable and compatible.
  • US military specification MIL-F-24385: Chemguard notes that concentrates on its qualified products list are compatible by definition of the specification.

These are foreign references; in Saudi Arabia the Saudi Building Code (SBC) and Civil Defense, as the approving authority, are binding. Clause numbers and wording vary between NFPA 11 editions, so refer to the edition named in the project documents.

The practical message from these sources is the same: mixing is an exception that needs written evidence, and responsibility lies with whoever decides to add. The maintenance file should therefore keep everything that proves the existing concentrate’s type, source and date, so the refill decision rests on data rather than a faded label on an old drum.

When can firefighting foam be mixed, and when not?

CaseVerdictReason
Two batches of the same productLess problematic; test the older batchSame formulation, but old stock may have changed
3% AFFF from two brandsOnly with manufacturer compatibility certification and authority approvalThe blend was never tested
1% AFFF with 3% AFFFNoDifferent proportioning rate; the ratio controller is set for one
AFFF with AR-AFFFNoAlcohol-resistant foam has different application rates
Synthetic with protein foamNoDifferent chemical base
Regular with low-temperature foamNoDifferent formulation and limits of use

Chemguard gives an example of the risk with alcohol-resistant concentrates: a system designed at 0.14 gpm/ft² topped up with a concentrate listed at 0.16 gpm/ft² would not provide the protection it was designed for.

How to refill a foam tank without mixing

  1. Identify the existing concentrate: brand, type, concentration and manufacturing date from drum labels, handover records or the datasheet.
  2. Order the same product: if available, top up with it after testing a sample of the old concentrate.
  3. If the supplier changes: the safest option is to drain and clean the tank according to the tank manufacturer’s manual, then fill with the new product.
  4. If draining is not possible: obtain a compatibility certificate from the new concentrate’s manufacturer, based on a sample of the existing product, and authority approval before adding.
  5. Record the change: mark the new product and fill date on the tank and in the maintenance log.

The Sthamer bulletin recommends checking any mixture annually if mixing has taken place, to catch changes in quality or performance.

Testing the old concentrate before topping up

Even when topping up with the same product, the concentrate already in the tank is checked first: appearance, sediment and viscosity, then a laboratory sample test as the manufacturer specifies. The shelf life stated in the datasheet is also reviewed. If the sample shows changed properties, full replacement is the better course.

For foam types and their applications, see foam fire suppression systems in Saudi industrial facilities.

Supply of foam concentrate and foam tanks

Through its technical supply service, AZEIDK supplies Safe Guard AFFF at 3% and 6% in 20 L and 200 L packs, with 1% coming soon, each with its datasheet. See SafeGuard in Saudi Arabia. Bladder tanks are also available, including the WATEX UL-listed foam bladder tank and SFFECO and Falcon Gold tanks. These systems serve industrial facilities and warehouses storing flammable liquids.

Inspection of foam tanks and concentrate is part of preventive and scheduled maintenance contracts.

Questions to ask before buying a replacement foam

When the foam supplier or brand changes, avoiding a mix starts with the purchase order. Check these points with the supplier before delivery:

  • Type: AFFF, AR-AFFF or other, matched to the facility’s hazard.
  • Concentration: 1%, 3% or 6%, matched to the existing ratio controller setting.
  • Equipment compatibility: whether the ratio controller, tank or monitor is listed with this concentrate where the system is approved as an assembly.
  • Datasheet: storage temperature limits, shelf life and periodic test method.
  • Packaging: 20 L for manual filling and extinguishers, 200 L for large tanks.
  • Refill plan: whether the tank will be drained and cleaned or topped up with the same product, and who does it.

These questions stop a product that looks right on paper from arriving for a system it does not suit.

Frequently asked questions

Can firefighting foam from two brands be mixed?

Not as a general rule. It is considered only for two concentrates of the same type and rate, with a manufacturer compatibility certificate based on a sample and authority approval.

Can 3% foam be mixed with 6% foam?

No. The proportioning rates differ, and the system’s ratio controller is set for one concentration.

Can a foam tank be topped up with the same product?

Yes, that is the normal approach, after sampling the old concentrate and checking its shelf life.

What if the foam supplier changes?

The safest route is to drain and clean the tank per the tank manufacturer’s manual and fill with the new product, or obtain a compatibility certificate and authority approval.

Can two different foams be used on the same fire?

Generally yes. The Sthamer bulletin states expanded foam can be applied with other foams without adverse interaction; the concern is mixing concentrates in the tank.

How often should stored foam concentrate be tested?

Per the manufacturer’s instructions and the maintenance programme; Sthamer recommends checking any mixture annually if mixing has occurred.

Can AFFF be mixed with alcohol-resistant AR-AFFF?

No. Chemguard states hydrocarbon-only foam is not mixed with alcohol-resistant foam, since listed application rates differ and the blend may not give the designed protection.

Can two batches of the same product be mixed?

This is less problematic as the formulation is the same, but the Sthamer bulletin recommends a performance and quality check on the older batch first.

Summary

Mixing firefighting foam in a tank is a technical decision that needs evidence, not a routine refill step. The tank should hold one known product, topped up with the same product, or drained and cleaned when the supplier changes. Any exception goes through a manufacturer compatibility certificate and authority approval.