Mall fire extinguishers are a shared responsibility between mall management and tenants. Management equips the public corridors, atriums, back-of-house service corridors, loading dock, car parks and the electrical and control rooms; each tenant equips its own unit according to its trade and the fit-out guidelines issued by management. The type follows the hazard: ABC dry powder or foam for corridors and shops, Class K for food court kitchens, CO2 or FM-200 for electrical and control rooms, and wheeled units for large car parks and the loading dock where the design calls for them.
To compare extinguisher types and choose the right one for each hazard, see our fire extinguishers selection guide for facilities in Saudi Arabia.
A mall is open to thousands of visitors a day, its shops change with every new lease, and it combines restaurants, back-of-house stores and multi-level parking. This guide explains how responsibility splits between management and tenants, the right type for each zone, how to keep corridors looking clean without hiding the extinguisher, and what to review before a Civil Defense inspection.
Key points
- Zone the mall: public corridors and atriums, tenant units, food court kitchens, service corridors and stores, loading dock, car parks, and electrical and control rooms.
- Class A travel distance must not exceed 22.9 m in every zone, including inside large shops.
- Restaurant kitchens need a Class K unit within 9.1 m of the cooking appliances.
- Control room and building management system: CO2 or FM-200, not powder.
- The tenant fit-out guide should state extinguisher types and positions so every shop follows the same rule.
In this article
Who equips what: management or tenant?
Common areas, meaning corridors, atriums, stairs, service corridors, car parks and plant rooms, are equipped by mall management and maintained under one contract. Inside a shop the tenant provides the extinguishers its trade needs, following the fit-out guide issued by management, and management checks this before the shop opens. This split closes two common gaps: a large shop with no internal unit because the tenant relied on the corridor, or a corridor with no unit because management assumed the shops were enough.
For all systems in commercial buildings see our malls and commercial buildings page.
Mall fire extinguishers by zone
| Zone | Main hazard | Suitable type |
|---|---|---|
| Public corridors and atriums | Class A | ABC powder or foam in recessed cabinets |
| Clothing, furniture and soft furnishing shops | Class A (fabric, cartons) | ABC powder or foam |
| Electronics shops | Electrical equipment | CO2, with powder or foam for the back store |
| Food court kitchens | Class K | Wet chemical Class K, with the hood suppression system |
| Service corridors and back stores | Class A (cartons, packaging) | ABC powder |
| Loading dock and refuse area | Class A and B | ABC powder, wheeled unit as designed |
| Multi-level car parks | Class A and B | ABC powder on columns, wheeled units for large areas |
| Electrical rooms, control room and BMS | Class C and electronics | CO2 or FM-200 |
For fire classes see the fire triangle and fire classes.
Layout in corridors and atriums
In the NFPA 10 table for Class A hazards, travel distance must not exceed 22.9 m along the walking path, each unit of A covers about 139 m² in ordinary hazard and about 93 m² in extra hazard, and no single unit is credited with more than about 1,045 m². The designer sets the hazard class for each zone, so a public corridor is treated differently from a back store full of cartons.
In long public corridors, units usually sit at corridor junctions, beside stairs, lifts and emergency exits, and at the entrances to service corridors. An open atrium cannot take a unit in the middle, so units go around its edges with every point kept within distance.
Appearance or visibility?
Mall operators prefer clean corridors without projecting equipment, which is fine as long as the extinguisher is visible or clearly signed. A recessed cabinet with a stainless steel front gives the look they want, and the vision panel version keeps the extinguisher visible without opening the door. The mistake is hiding the unit behind an advertising panel or inside a decorative cupboard with no sign. See fire extinguisher cabinets and the fire extinguisher sign.
Food court and restaurants
Every restaurant that fries or cooks with oil needs a wet chemical (Class K) extinguisher no more than 9.1 m from the cooking appliances, per the NFPA fact sheet, in addition to the hood suppression system that protects them. The extinguisher complements the system and does not replace it. See the Class K kitchen extinguisher and kitchen fire suppression systems.
Control room and plant rooms
The mall control room houses the fire alarm panel, the building management system and monitoring equipment. NFPA 10 states that dry chemical extinguishers shall not be installed to protect delicate electronic equipment, so this room is protected with CO2 or FM-200. Electrical and transformer rooms use CO2 units, and the designer may add a trolley CO2 unit for larger rooms. See the FM-200 extinguisher.
What the tenant fit-out guide should say about extinguishers
The fit-out guide is the tool that makes every new shop open with the right extinguishers without reviewing each case from scratch. It helps to include:
- The minimum number of units by shop area, with the 22.9 m travel distance applied inside the shop.
- The type required by trade: powder or foam for general retail, additional CO2 for electronics, Class K for restaurants.
- Mounting method: wall bracket or cabinet, height, and the sign.
- Submission of the datasheet and certificate of conformity for each model before installation.
- Proof of a valid maintenance contract before opening, and a copy of the monthly check record to management.
Common faults in malls
- A shop opened with no internal unit, relying on the corridor extinguisher.
- A unit hidden behind an advertising panel or a seasonal display.
- Service corridors used as storage with the extinguisher behind cartons.
- A food court restaurant with powder only and no Class K unit.
- A powder unit in the control room.
- Service tags on different dates between shops and common areas. See fire extinguisher maintenance.
Mall extinguishers available from AZEIDK
Through its technical supply service, AZEIDK supplies extinguishers for common areas and shops, with the datasheet for each model:
- Falcon Gold recessed extinguisher cabinet: FG-400S with a full stainless steel front, FG-400SG with a stainless front and fiberglass vision panel, FG-400M in red powder-coated steel.
- FG 6 kg dry powder: rated 27A 144BC per the datasheet.
- FG 12 L foam: for solids and liquids in shops and stores.
- FG 6 kg wet chemical: for restaurant kitchens, rated 13A 75B.
- FG 6 kg CO2 and Falcon Gold portable FM-200 extinguishers: for electrical and control rooms.
- FG 50 kg wheeled dry powder: for large car parks and the loading dock.
AZEIDK’s own team maintains extinguishers under its periodic maintenance contracts.
FAQ
Is the tenant responsible for the extinguishers in its mall shop?
Usually yes, within the shop and following the fit-out guide issued by mall management, while management equips the common areas.
Which extinguisher suits a clothing shop in a mall?
ABC powder or foam for fabric and cartons, in a number that keeps travel distance within 22.9 m inside the shop.
Can a corridor extinguisher sit inside a decorative cupboard?
Yes, if it opens easily and carries a visible sign; a recessed cabinet with a vision panel is better.
What does a food court restaurant need?
A Class K unit within 9.1 m of the cooking appliances, with the hood suppression system and a unit for the rest of the restaurant.
Which extinguisher suits the mall control room?
CO2 or FM-200, because NFPA 10 does not allow dry chemical to protect delicate electronic equipment.
Do mall car parks need wheeled extinguishers?
In large car parks and at the loading dock the designer often adds them alongside the portable units on columns, depending on area and hazard.
Summary
Put the split of responsibilities between management and tenants in writing, zone the mall, match each zone to the right type, keep every unit visible or clearly signed whatever the interior design, and run the common areas under one maintenance contract. Review the layout whenever shops are re-divided or a new zone is added.
Related reading: Hotel Fire Extinguishers, Fire Extinguishers in Madinah and Fire Extinguishers in Khamis Mushait and Abha.
Running a mall or fitting out a shop in one? Send us the drawings and fit-out guide, and we will propose types, quantities and cabinets with a supply and maintenance offer. Contact the AZEIDK team
See the fire extinguishers and fire fighting systems AZEIDK supplies.
Related guides
- AFC ACV-300 Wet Alarm Check Valve: Models, Trim Components and Installation in Sprinkler Systems
- CCTV Advantages and Disadvantages: Benefits for Businesses and Homes, Privacy and Hacking Risks, and How to Reduce Them
- How to Wire CCTV Cameras: Connection Diagram from Camera to NVR/DVR, PoE vs Coax, Power and Monitor
- Saudi Quality Mark for Fire Equipment: What It Is and How It Relates to the SABER Certificate of Conformity