Fire rated doors in Makkah are mostly ordered for hotels and towers in the central area, pilgrim and Umrah housing, and residential buildings prepared for seasonal letting. In a building that fills with visitors within days, the protected stair door is part of the escape route itself: it must close by itself, open in the direction of exit without a key, and survive thousands of openings in a single season.
This guide covers where Makkah buildings need fire rated doors, how to choose doors and hardware for heavy use, how to prepare them for Civil Defense inspection and the season, and where to find the AZEIDK showroom in Al Aziziyah. AZEIDK supplies Falcon Gold fire rated steel doors and installs them as part of its fire rated doors and emergency exit solutions.
Key points
- A fire rated door is tested and rated as a complete assembly: leaf, frame, hinges, closer and lock together.
- The rating in minutes for each opening is set by the Saudi Building Code and the approved design, not chosen by the owner.
- In hotels and pilgrim housing the usual remarks are a stair door propped open, a weak closer and a lock that blocks exit.
- Magnetic holders linked to the fire alarm keep doors open at peak times and release them on alarm.
- The AZEIDK Makkah showroom is in Al Aziziyah on Sheikh Abdullah Al Khayyat Street.
In this article
- Where Makkah buildings need fire doors
- Choosing fire rated doors in Makkah for heavy use
- Linking doors to the hotel fire alarm
- Before the season and the inspection
- Doors and the Salamah licence
- AZEIDK Makkah showroom
- Supply and installation stages for fire rated doors in Makkah
- Common mistakes in hotel fire doors
- Fire doors and other building systems
- FAQ
Where Makkah buildings need fire doors
| Building | Usual locations | Watch out for |
|---|---|---|
| Central area hotels and towers | Protected stair doors, electrical, generator and pump rooms, refuse rooms | Round-the-clock traffic; closers and hinges must cope |
| Pilgrim and Umrah housing | Stair doors on each floor, central kitchens, service rooms | Guests unfamiliar with the building; exit signs and swing direction matter |
| Residential buildings let seasonally | Stair doors, meter and tank rooms | Group accommodation changes safety requirements |
| Central catering kitchens | Separation between kitchen, stores and corridors | Heat and grease on hardware |
| Malls and shops near the Haram | Exit doors, back stores, service rooms | Panic bar on the exit route, no key |
The approved fire protection drawing is the final reference for each opening. See also the hospitality sector page.
Choosing fire rated doors in Makkah for heavy use
| Item | Why it matters in Makkah |
|---|---|
| Required rating | From the approved drawing; differs between stair and service doors |
| Size and leaves | Wide corridors and luggage may need double-leaf doors |
| Door closer | Must fully close the door under constant use, adjusted to door weight |
| Panic bar | On exit doors, so the door opens by pushing without a key |
| Magnetic holder | Holds the door open at peak times and releases it on a fire alarm signal |
| Vision glass | If used, it must be part of the tested assembly |
See magnetic door holders with fire alarm and fire rated door price factors.
Linking doors to the hotel fire alarm
In large hotels, magnetic holders and electronic exit locks are connected to the fire alarm panel through control modules, so holders release on alarm and exit locks unlock according to the cause and effect matrix in the design. This interface is carried out by the fire alarm systems team together with the doors and tested before handover. For crowded hotels see also voice evacuation in Makkah hotels.
Before the season and the inspection
- Release each door from fully open and confirm it closes and latches unaided.
- Remove wedges; use an alarm-linked holder if the door must stay open.
- Check hinges, closer, frame and seals, and any damage from luggage trolleys.
- Make sure the rating labels on door and frame are not painted over or removed.
- Test the panic bar from the exit side.
NFPA 80, as an international reference, calls for annual inspection of fire door assemblies, while the binding rules in the Kingdom are the Saudi Building Code and Civil Defense requirements; see fire door inspection and maintenance. Doors are included in periodic maintenance contracts.
Doors and the Salamah licence
AZEIDK issues the safety equipment installation certificate for work it carries out and handles the technical report through an approved engineering consultancy office. See Civil Defense approval support.
AZEIDK Makkah showroom
| Branch | Address | Phone |
|---|---|---|
| Makkah Showroom, Al Aziziyah | Al Aziziyah District, Sheikh Abdullah Al Khayyat Street | +966 54 052 0353 |
Large projects are also coordinated with the General Administration in Jeddah on Prince Majed Road (Al Safa Tower Plaza). For general safety services in the city see safety and fire protection company in Makkah.
Supply and installation stages for fire rated doors in Makkah
- Door schedule: from the approved drawing: location, size, rating, swing and hardware, which can be checked through drawings and specifications review.
- Site measurement: actual openings measured before manufacture.
- Submittal: datasheet, catalogue and hardware details for the consultant.
- Installation: frame fixed to the wall per manufacturer instructions, then leaf, hardware and closer adjustment.
- Interface and testing: holders and locks linked to the fire alarm where used, closing and release tested before handover.
Common mistakes in hotel fire doors
- Site modifications: trimming the leaf, fitting an untested lock or adding glass voids the rating.
- Wall not matching the door: a rated door in an unrated wall does not give the separation required.
- Wrong closer force: too strong for elderly guests, too weak to close the door.
- Painted-over labels: pre-season repainting often hides the rating label.
- No check after the season: weeks of heavy use loosen hinges and closers.
Fire doors and other building systems
In tall hotel towers the design may include stair pressurisation or corridor smoke extraction. The door must seal well to hold the pressure difference and still open with acceptable force. These systems are part of smoke extraction and emergency ventilation and are tested with the doors before handover. In existing buildings prepared for pilgrims, start with an existing systems assessment months before the season, leaving time to manufacture made-to-measure doors.
FAQ
Where can I find fire rated doors in Makkah?
At the AZEIDK showroom in Al Aziziyah, Sheikh Abdullah Al Khayyat Street, +966 54 052 0353, with supply and installation.
What fire rating does my door need?
The Saudi Building Code and the approved drawing set it by location; confirm with the consultant before supply.
Can a stair door be kept open during the season?
Not with a wedge. Use a magnetic holder linked to the fire alarm, where the design allows.
Can any lock be fitted to a fire door?
No. The lock is part of the tested assembly, and exit doors need hardware that opens by pushing without a key.
Does AZEIDK maintain fire doors?
Yes, under periodic maintenance contracts: closer, hinges, frame and lock checks.
Preparing a hotel or pilgrim housing in Makkah? Send the door schedule or drawing and we will review it and propose doors and hardware. Contact AZEIDK
Related guides
- High-Temperature Smoke Exhaust Fans: Ratings, Selection and Fire Alarm Interface
- Tire Storage Fire Protection: Storage Methods, Sprinklers and Detection
- EZVIZ H9c Dual-Lens Camera: Specs, Installation, EZVIZ App Setup and Where It Fits
- Safety and Fire Fighting Company in Makkah: Fire Alarm, Fire Fighting, Extinguishers and Civil Defense Procedures