Control room fire protection differs from protecting a closed server room, because a control room is occupied by operators around the clock. It is therefore usually protected with a clean agent system (HFC-227ea or FK-5-1-12) designed within safe exposure limits for people, with a pre-discharge alarm and a hold-off button within the operator’s reach, while a new carbon dioxide total flooding system is not installed there.
For how clean agent systems are designed, kept safe and maintained, see our FM-200 fire suppression system guide.
This guide explains how to choose the right system for control rooms in factories, utility plants and operations and monitoring rooms, using the special fire suppression systems AZEIDK supplies, and how to coordinate detection and release with the way the room actually works.
Key points
- A control room is normally occupied, so it gets a clean agent at a design concentration within the exposure limits NFPA 2001 sets.
- Since the 2005 edition of NFPA 12, new CO2 total flooding systems are not installed in normally occupied spaces.
- Protection covers the room, the raised floor and the ceiling void where they contain cables or equipment.
- The hold-off button and time delay are part of running the room, and operators must be trained on them.
- The binding references in Saudi Arabia are the Saudi Building Code and Civil Defense requirements, with NFPA 2001 as the technical reference.
In this article
- Why do control rooms need special treatment?
- Suppression options for control rooms
- Operator safety in control room fire protection
- Spaces to protect in a control room
- Room integrity and integration with other systems
- A written procedure for operators
- Regulatory framework in Saudi Arabia
- Common mistakes in control room protection
- Frequently asked questions
- Summary
Why do control rooms need special treatment?
The control room is the heart of a factory, plant or large building: monitoring screens, system panels, controller cabinets and dense cabling under a raised floor. Four factors make suppression selection different from a closed equipment room:
- Permanent occupancy: operators are present on every shift and may need minutes to shut processes down safely before leaving.
- Water is unwelcome: water on consoles and cabinets stops operations for longer than a small fire would.
- Cost of downtime: losing the control room can mean losing a production line or a whole plant.
- Hidden spaces: a fire can start in a cable under the floor or inside a cabinet before anyone sees it.
For industrial sites in general see factories and industrial facilities.
Suppression options for control rooms
| System | Agent | Suitability for an occupied room | Examples supplied by AZEIDK |
|---|---|---|---|
| Halocarbon clean agent | HFC-227ea (FM-200) | Suitable when the design concentration is within NFPA 2001 exposure limits | Context Plus 227, American Fire Control FM-200 |
| Halocarbon clean agent | FK-5-1-12 | Suitable on the same condition | SFFECO 1230 system |
| Carbon dioxide | CO2 | New total flooding systems are not installed in normally occupied spaces | Suits other unoccupied spaces on the site |
| Condensed aerosol | Aerosol generators | Check the product listing and manual for occupancy limits | FirePro |
Choosing between HFC-227ea and FK-5-1-12 for a control room does not turn on one factor: it depends on what the consultant has specified, cylinder room space, refill availability and whether the site already has a system using a given agent. The general comparison is in clean agent suppression comparison, and hazard-based selection in special hazard suppression selection.
Operator safety in control room fire protection
NFPA 2001 sets limits on people’s exposure to clean agents, and its 2018 edition, as summarized in an EFCOG code review, added a requirement for an egress time study to verify that people leave the space within the permitted exposure time. Check the wording of the edition adopted for the project. In a control room that means the designer needs information from operations: how many operators are on a shift, how long a safe shutdown takes before leaving, and where the nearest exit is from each console.
The answers become system features:
- Two-stage alarm: the first stage alerts operators when the first detector operates; the second starts the countdown when a second detector confirms.
- Time delay: gives time to leave before discharge, set according to the egress study and the design.
- Hold-off and abort button: such as the Context Plus EP215 hold-off/abort button, placed where the responsible operator can reach it without pressing it by accident.
- Manual release at the exit: for when an operator sees the fire before the detectors do.
- Visual and audible signals and signs at the entrances showing the room is gas protected.
These features run from the extinguishing control panel, such as the Context Plus EP203 panel, and the sequence is explained in gas suppression release sequence.
Spaces to protect in a control room
The room itself
The net room volume is calculated after the deductions the manufacturer’s manual allows, and nozzles are laid out to cover the whole area without aiming directly at operator seating or light suspended ceiling tiles.
The raised floor
If power and control cables run under the floor, it is a separate space with its own volume, nozzles and detectors, discharged together with the room.
The ceiling void
Treated the same way when it holds cable trays or equipment; if it is empty and sealed, the designer decides on it through the calculation.
Cabinets and consoles
In total flooding, agent may reach inside ventilated cabinets, but fully sealed cabinets may need a local solution or internal detection, decided by the designer with the cabinet supplier.
Room integrity and integration with other systems
Control room doors open and close constantly, which is the biggest challenge to hold time. Doors need self-closers, cable openings between the room, the floor void and corridors need sealing, and HVAC that draws air from outside the room is shut down on release. All of this is reviewed in the room integrity test before handover and after any change.
The suppression system is linked to the building’s main fire alarm panel, with alarm, release and fault signals passed from the extinguishing panel so that security or Civil Defense know the room’s status.
A written procedure for operators
A good system needs a written procedure posted in the room and taught to every new operator. An example of its content:
- Stage one (one detector): the operator checks the alarm source on screen or by sight, informs the supervisor and prepares for safe shutdown.
- Stage two (second detector confirms): the countdown starts, the agreed safe shutdown is carried out and everyone leaves.
- Using the hold-off button: only as the procedure allows, by the authorised person, informing security.
- After discharge: nobody re-enters until the room is ventilated and the fire is confirmed out, then maintenance is called to return the system to service.
The procedure is reviewed whenever the number of operators, the console layout or the exits change.
Regulatory framework in Saudi Arabia
The binding reference in the Kingdom is the Saudi Building Code, including the fire code SBC 801, together with the requirements of the General Directorate of Civil Defense. NFPA 2001 is used as the technical reference for clean agent design and NFPA 12 for carbon dioxide systems, where the designer or project specification adopts them. AZEIDK’s Civil Defense approval support follows the approval file, and engineering design and calculations covers the quantity and pipe network calculations.
Common mistakes in control room protection
- Copying a closed server room design to an occupied room without an egress study.
- Placing the hold-off button far from the operator, or where it can be pressed by accident.
- Leaving out the raised floor although it carries most of the cables.
- Doors without self-closers that stay open during shifts.
- Not training operators on the two alarm stages and when to use the hold-off button.
- Choosing CO2 for an occupied room because the agent is cheaper.
Frequently asked questions
What is the best suppression system for a control room?
There is no single system for every room, but a clean agent (HFC-227ea or FK-5-1-12) designed within NFPA 2001 exposure limits is the usual choice for occupied rooms.
Is a CO2 system suitable for a control room?
Since the 2005 edition of NFPA 12, new CO2 total flooding systems are not installed in normally occupied spaces, and a control room is one of them.
Must the raised floor in a control room be protected?
If cables or equipment run under it, it is a separate space needing its own calculation, nozzles and detectors within the same system.
What is the hold-off button for in a control room?
It pauses the countdown when an operator needs extra time; operators are trained on it and it is placed where they can reach it without pressing it by accident.
How do I know the room will hold the agent after discharge?
Through a room integrity test before handover, repeated after any change to doors or openings.
Is the suppression system linked to the main fire alarm panel?
Yes, alarm, release and fault signals pass from the extinguishing panel to the building’s main fire alarm panel.
Summary
Control room fire protection starts from the fact that the room is occupied: a clean agent within exposure limits, an egress study, a two-stage alarm, a hold-off button within the operator’s reach, protection of floor and ceiling voids, and a sealed room tested before handover.
Planning protection for a control room? Send the room drawing, raised floor and ceiling heights and the number of operators per shift, and the AZEIDK team will propose the system, calculations and release sequence. Contact AZEIDK
Related guides
- Snag List for Fire and Security Systems: Preparing and Closing It Before Handover
- Fire Protection for Stadiums, Event Venues and Assembly Spaces
- Recycling Plant and Scrap Yard Fire Protection: Thermal Camera Detection, Hydrants and Surveillance
- Hikvision Access Control: MinMoe Face Terminals, DS-K2801 Controller and Setup with iVMS-4200 and Hik-Connect