In a factory there is no single extinguisher that suits everything. A production hall is not a raw material store, and an electrical panel room is not the diesel tank next to the generator. Choosing fire extinguishers for factories starts with a simple question: what can burn in each area? Type, size, number and mounting position follow from the answer.
To compare fire extinguisher types and what each one is for, see our guide to choosing the right extinguisher for each hazard.
This guide explains how to choose extinguishers for the different areas of a factory in Egypt’s industrial cities, such as 10th of Ramadan, 6th of October, Sadat City and Borg El Arab, with a table linking each area to a suitable type from the PYRAMID extinguisher range that AZEIDK Egypt supplies as part of its fire extinguisher solutions.
Key takeaways
- Choose the extinguisher by the fire class expected in each area, not by what is in stock or cheapest.
- ABC dry powder is the most widely used type in production halls and stores, but it leaves residue and is not chosen for sensitive electronics.
- Electrical panel rooms are usually protected with CO2 extinguishers, and flammable liquid areas with AFFF foam or powder.
- Large hazards such as fuel stores and generators may need wheeled units: 25 and 50 kg powder or 25 and 45 L foam.
- Number and spacing are worked out from the extinguisher rating and hazard level, and civil protection requirements for the activity are the final reference.
In this article
- Map the hazards before choosing fire extinguishers for factories
- Extinguisher selection by factory area
- Powder, CO2 or foam: when to use each
- Wheeled and automatic extinguishers in factories
- Number, travel distance and mounting height
- Common mistakes
- Extinguishers are part of factory protection, not all of it
- Frequently asked questions
- Conclusion
Map the hazards before choosing fire extinguishers for factories
Before buying any extinguisher, walk the factory with the site plan and divide it into areas by the materials in them: ordinary solids such as paper, cardboard, wood and plastic (Class A); flammable liquids such as diesel, oils, solvents and paints (Class B); live electrical equipment (treated as Class C in US standards); and cooking oils in a kitchen or canteen, if there is one.
This map is the basis for everything that follows, and it is also what gets reviewed when the facility file goes to civil protection. The binding reference in Egypt is the 2026 Egyptian fire code and the requirements of the General Directorate of Civil Protection for the specific industrial activity. NFPA 10 is used as the technical reference for distribution and mounting.
Extinguisher selection by factory area
| Area | Main hazard | Suggested PYRAMID extinguisher | Notes |
|---|---|---|---|
| Production halls | Solids, sometimes machine oils | ABC powder, 6, 9 or 12 kg | Add foam or powder near machines using large amounts of oil |
| Raw material and finished goods stores | Cardboard, wood, plastics | ABC powder 6 to 12 kg, wheeled for large areas | Mount at aisles and entrances, not inside the stacks |
| Electrical panel and transformer rooms | Electrical equipment | CO2 6 or 10 kg, or automatic Fire Search CO2 | Powder is not chosen for sensitive electronics |
| Generator room and diesel tank | Flammable liquids | AFFF foam or powder, wheeled depending on hazard size | Check the quantity of stored fuel |
| Paint and solvent store | Flammable liquids | AFFF foam 9 L, or wheeled 25 and 45 L | Class B travel distance is shorter than Class A |
| Workshops and maintenance rooms | Mixed materials | ABC powder 6 kg, CO2 next to machine panels | Review welding and cutting work |
| Admin offices | Paper and office equipment | ABC powder or CO2 depending on location | CO2 next to the server room |
The table is a starting point. The final choice in each area depends on material quantities, storage method and what civil protection requires for the activity.
Powder, CO2 or foam: when to use each
ABC dry powder extinguishers
PYRAMID powder extinguishers are stored-pressure units in 1, 3, 6, 9 and 12 kg sizes for Class A, B and C fires. The datasheet gives fire ratings from 5A-21B for the 1 kg unit to 43A-183B for the 12 kg unit. They conform to EN 3 and Egyptian standard ES 8442/2021, are approved by the Egyptian Organization for Standardization and Quality (EOS) and carry the Egyptian quality mark. Their main drawback is that the powder leaves residue that is hard to clean from precision machines and electronics. Details are in PYRAMID dry powder extinguishers.
CO2 extinguishers
PYRAMID CO2 extinguishers come in 2, 3, 6, 10, 20 and 30 kg sizes and conform to EN 3 and Egyptian standard ES 735. They leave no residue, so they suit electrical panels and control rooms. However, OSHA does not recommend them for fires in solid materials, because these can reignite once the gas disperses, and they must not be used in an enclosed occupied space without respiratory protection.
AFFF foam extinguishers
PYRAMID AFFF extinguishers come as 6 and 9 L portable units and 25 and 45 L wheeled units, conforming to EN 3 and Egyptian standard ES 711. They suit areas where flammable liquids are the main hazard, such as oil and solvent stores and generator rooms.
Wheeled and automatic extinguishers in factories
In large stores and fuel areas a portable extinguisher may not be enough. This is where wheeled units come in: 25 and 50 kg powder (to EN 1866 and Egyptian standard ES 1494) and 25 and 45 L AFFF foam, while the CO2 range goes up to 20 and 30 kg. They need wide, level routes and someone trained to use them. When you need one and how to size it is covered in wheeled fire extinguishers.
Small enclosed spaces that are unoccupied most of the time, such as a main electrical panel inside a closed room, may suit PYRAMID automatic Fire Search extinguishers, available as 6 and 12 kg powder and 3, 6 and 10 kg CO2, which operate through a linear detection tube. Where to use them is covered in PYRAMID automatic Fire Search extinguishers.
Number, travel distance and mounting height
Under NFPA 10 (2022 edition), travel distance to a Class A extinguisher must not exceed 75 ft (22.9 m), and Class B extinguishers are spaced at a travel distance of 30 or 50 ft (9.1 or 15.2 m) depending on their rating and the hazard level. An extinguisher with a gross weight up to 18.14 kg is mounted with its top no higher than 1.53 m, heavier units no higher than 1.07 m, and the bottom at least 102 mm above the floor.
The European EN 3 rating on PYRAMID extinguishers (such as 43A) is not the same as a US NFPA rating, so the two must not be mixed in calculations. The full method is in how many fire extinguishers does a space need?
Common mistakes
- Using one extinguisher type across the whole factory, so the electrical room ends up with powder and the fuel area has no foam.
- Mounting extinguishers inside racking aisles or behind goods where nobody can see them.
- Leaving extinguishers on the floor with no bracket, exposed to forklift impacts and moisture.
- Buying extinguishers without the Egyptian quality mark or a clear data label.
- Skipping monthly checks and not recharging after partial use.
- Relying on extinguishers alone in a factory that needs a fire fighting network and an alarm system.
Extinguisher maintenance and recharging are covered in fire extinguisher maintenance and recharging.
Extinguishers are part of factory protection, not all of it
An extinguisher is a first-response tool for a small fire. It does not replace the fire fighting network and alarm system where the code requires them. A Federation of Egyptian Industries seminar discussed insurers asking factories for tested systems and maintenance records, as reported in the Egyptian fire code, insurance and factories. The full picture, from the pump room to the electrical rooms, is in fire protection for factories.
Frequently asked questions
Which extinguisher suits a production hall?
Usually ABC powder in 6, 9 or 12 kg, with foam or powder added near machines that use large amounts of oil.
Should I use a powder extinguisher in an electrical room?
CO2 is preferred for electrical panels and electronic equipment because it leaves no residue. Powder can damage sensitive equipment.
When does a factory need a wheeled extinguisher?
For large hazards such as fuel and solvent stores and wide open areas, where a portable unit does not have enough capacity.
How many extinguishers does a factory need?
The number comes from the hazard level, the extinguisher rating and the travel distance in each area, then is checked against civil protection requirements for the activity.
Are PYRAMID extinguishers approved in Egypt?
PYRAMID powder, CO2 and foam extinguishers conform to the Egyptian standards listed for each type, are approved by EOS and carry the Egyptian quality mark.
Conclusion
Choosing factory extinguishers is a small engineering task that matters: a hazard map for each area, the right type for each hazard, size, number and spacing worked out on the plan, then correct mounting and routine maintenance. That puts the right extinguisher in the right place when a worker needs it in the first minute.
Fitting out a new factory or reviewing an existing one? Send us the site plan, activity type and stored materials, and we will suggest types, sizes and positions from the PYRAMID range. Talk to the AZEIDK Egypt team