Printing Press Fire Protection in Egypt: Paper Stores, Detection, Extinguishers and Inks

Printing Press Fire Protection in Egypt: Paper Stores, Detection, Extinguishers and Inks

A printing house and a paper and cardboard store hold large amounts of one easily ignited material, stacked in rolls, bales and pallets close to the roof, next to inks, cleaning solvents and printing and cutting machines that run for long hours. Printing press fire protection therefore needs early detection that finds a fire while it is small, extinguishers suited to paper and inks, and a fire network that reaches deep into the store.

This article covers the hazard zones in book, packaging and cardboard printers and paper stores in Egypt, the role of fire detection and alarm systems from Context Plus and TANDA, PYRAMID extinguishers, and the fire fighting network supplied by AZEIDK Egypt.

Key takeaways

  • High stacks of paper rolls and cardboard bales are the largest fire load, and fire spreads upward quickly between stacks.
  • Inks and press cleaning solvents are Class B fires and need nearby AFFF foam or powder.
  • High stores are covered by beam detectors such as TANDA TX7130 and Context Plus 55000-268; press halls by smoke or heat detectors depending on dust.
  • ABC powder is the base extinguisher for paper fires, with wheeled units for large stores.
  • Aisles between stacks and clearance below the roof are part of protection, not only of tidiness.
In this article
  1. Printing press fire protection: why paper is a special hazard
  2. Hazard zones in a printing house and paper store
  3. Early detection in paper and cardboard stores
  4. The right extinguishers for a printing house
  5. Fire water network and pumps
  6. Storage and daily operation
  7. What should the shift do when the alarm sounds?
  8. The Egyptian framework
  9. Common mistakes in printing houses and paper stores
  10. Frequently asked questions
  11. Conclusion

Printing press fire protection: why paper is a special hazard

A single sheet burns fast and goes out, but paper stacked in rolls or bales burns differently: fire gets between the layers and keeps going, and can stay alight inside after the surface looks out. High stacks let fire climb quickly, and a narrow aisle between two stacks acts like a chimney pulling flames to the roof.

The press hall adds another hazard: some printing inks and cylinder cleaning solvents are flammable, and rags soaked in them are sometimes left by the machine. Cutting and folding machines produce fine paper dust that settles on machines and electrical panels.

Hazard zones in a printing house and paper store

ZoneHazardTypical fit
Paper roll and bale storeLarge fire load, high stacksBeam detectors, hose cabinets, hydrants around the building, wheeled extinguishers
Press hallInks, solvents, panels, motorsABC powder and AFFF foam, CO2 at panels
Ink and solvent storeFlammable liquidsAFFF foam, separation from paper store
Cutting, folding and bindingPaper dust and offcutsABC powder, heat detectors where dust is heavy
Finished goods storeCardboard and print on palletsBeam or smoke detectors by height, powder extinguishers
Electrical and compressor roomsElectrical fireCO2 extinguishers, smoke detectors

Early detection in paper and cardboard stores

The goal in a paper store is to detect a fire before it reaches the top of the stack. Point detectors on a high roof are hard to install and maintain, so a beam detector such as TANDA TX7130 or Context Plus 55000-268 is used. Beam spacing and mounting height are covered in beam detector spacing; keep stacks and overhead cranes out of the beam path.

In the press hall, optical smoke detectors suit relatively clean areas and heat detectors suit cutting and folding areas with heavy dust. A Context Plus addressable panel pinpoints the alarm, which helps in a printing house with connected halls and stores. Selection basics are in smoke and heat detectors.

The right extinguishers for a printing house

Paper and cardboard fires are Class A, so a 6, 9 or 12 kg ABC powder extinguisher from PYRAMID is the base in halls and stores, complying with EN3 and Egyptian standard ES 8442/2021. Large stores add 25 or 50 kg wheeled powder units to EN 1866 and Egyptian standard ES 1494.

Next to presses and the ink store, add a 6 or 9 L AFFF foam unit for ink and solvent fires, and a CO2 unit next to electrical panels. NFPA 10 limits travel distance to a Class A extinguisher to 22.9 m, and to a Class B unit in extra hazard areas to 9.1 m for 40-B or 15.25 m for 80-B. For units up to about 18 kg the top is no higher than 1.53 m, with at least 102 mm floor clearance. Details in how many extinguishers you need.

Fire water network and pumps

A fire in a large paper stack found late will not be put out with extinguishers, because it keeps burning between the layers. A paper store or large printing house therefore needs a fire network with a 3PUMP pump set (electric, diesel standby and jockey), Falcon Gold hose cabinets placed so the hose reaches deep between stacks, AFC FW-9000 hydrants around the building, and a fire department (Siamese) connection. 3PUMP sets supplied in Egypt are Non-Listed; UL/FM versions are manufactured and supplied on request.

Does a paper store need sprinklers? The consultant decides under the Egyptian code based on store area, storage height and arrangement. Vertically stacked rolls in particular need specific treatment in design. See also fire protection for warehouses.

Storage and daily operation

  • Keep clear aisles between stacks so a hose can reach any point.
  • Keep clearance between the top of the stack, the roof and the detectors.
  • Separate the ink and solvent store from the paper store.
  • Put solvent-soaked cleaning rags in a closed metal container.
  • Clear paper dust and offcuts around machines and electrical panels.
  • Do not stack bales in front of extinguishers, hose cabinets or the alarm panel.
  • Inspect extinguishers and detectors under a maintenance contract.

What should the shift do when the alarm sounds?

The best system does little if staff do not know what to do in the first minutes. When the alarm sounds, the person in charge reads the detector or call point location on the panel display, and a trained person goes there with the nearest extinguisher. A small, early fire can be tackled with the extinguisher from a safe distance with the exit behind; if it is in a large stack or smoke has spread, use the hose cabinet, evacuate and call civil protection at once.

Do not return a used extinguisher to its place before it is recharged, and do not reset the panel before confirming the alarm location and cause. Every shift should know where the extinguishers, hose cabinets, alarm panel and network valves are, and a store map should hang near the entrance so arriving fire crews can see the stacks and the ink store.

The Egyptian framework

In Egypt the obligation comes from Building Law No. 119 of 2008 and its regulations, the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), the Egyptian code for industrial and storage facilities, and drawing review and pre-occupancy inspection by the General Directorate of Civil Protection. NFPA 10, NFPA 13 and NFPA 72 are technical design references.

Common mistakes in printing houses and paper stores

  • Stacking paper up to the roof, blocking the detector beam and weakening any overhead protection.
  • Leaving aisles too narrow for a hose.
  • Storing inks and solvents inside the paper store.
  • Relying on CO2 extinguishers in the store, although paper fires are Class A.
  • Treating the fire as out once the stack surface is extinguished, without checking inside.
  • Neglecting outdoor hydrants around the store.

Frequently asked questions

What is the best extinguisher for a paper store?

ABC powder is the base for paper and cardboard fires, with wheeled units in large stores.

Which extinguisher goes next to a printing press?

ABC powder, AFFF foam where inks or solvents are present, and CO2 near the machine panel.

Which detector suits a high paper store?

Usually a beam detector such as TANDA TX7130 or Context Plus 55000-268, keeping stacks out of the beam path.

Does a paper store need sprinklers?

The consultant decides under the Egyptian code based on store area, storage height and arrangement.

Why does a paper fire flare up again after it is put out?

Fire can continue between the layers of a roll or bale after the surface is out, so the inside must be checked and cooled.

Conclusion

Printing press and paper store fire protection relies on early detection in high stores, ABC powder for paper, AFFF foam for inks and CO2 for electrical panels, a fire network that reaches deep into the store, and orderly storage with aisles and roof clearance. That keeps a fire small and controllable.

Fitting out a printing house or paper and cardboard store? Send us the store layout and storage heights and we will propose detectors, extinguishers and the network. Talk to the AZEIDK Egypt team

References: NFPA 10 Second Draft Report, A2025 (NFPA), TANDA (AZEIDK Egypt), PYRAMID (AZEIDK Egypt)