Fire Extinguishers for Car Workshops in Egypt: Powder, Foam and CO2 by Area

Fire Extinguishers for Car Workshops in Egypt: Powder, Foam and CO2 by Area

A car workshop in Egypt, whether a small garage in a crafts district or a dealer service center in New Cairo or 6th of October, brings petrol, diesel, oils, grease, batteries, welding and painting under one roof. So fire extinguishers for car workshops are not one type hung by the door. Each area gets a type and size based on what can burn there.

This guide splits the workshop into areas and matches each one with an extinguisher from the PYRAMID extinguisher range supplied by AZEIDK Egypt as part of its fire extinguisher solutions, with the NFPA 10 reference spacing.

Key takeaways

  • NFPA 10 classes vehicle repair as extra hazard and auto showrooms as ordinary hazard.
  • ABC dry powder is the main extinguisher in service bays, AFFF foam suits fuel draining and oil areas, and CO2 suits electrical panels and diagnostic equipment.
  • For flammable liquid fires in extra hazard areas, NFPA 10 limits travel distance to 9.1 m for a 40-B unit, or 15.25 m for an 80-B unit.
  • PYRAMID ratings are stated to EN3, such as 43A-183B for the 12 kg unit, and do not compare directly with the UL ratings in NFPA 10 tables.
  • Workshop licensing includes an inspection with civil protection under Public Establishments Law No. 154 of 2019.
In this article
  1. Why car workshops are extra hazard
  2. Fire extinguishers for car workshops, area by area
  3. Powder, foam and CO2: when to use each
  4. Spacing and quantity per NFPA 10
  5. Installation in the workshop
  6. Electric vehicles in the workshop
  7. Licensing and inspection
  8. Common mistakes in car workshops
  9. Frequently asked questions
  10. Conclusion

Why car workshops are extra hazard

NFPA 10’s annex lists examples of extra hazard areas, including vehicle repair, parking garages, woodworking, painting and coating processes and flammable liquid handling. A typical workshop has all of these: a car on a lift with petrol in the tank, a technician opening a fuel line, another welding on the chassis, used oil drums in the corner and a paint booth at the back.

This classification means a workshop needs bigger extinguishers placed closer together than an office or ordinary shop. The binding reference in Egypt is the Egyptian fire code, 2026 edition, and civil protection requirements. NFPA 10 is a technical reference for layout.

Fire extinguishers for car workshops, area by area

AreaMain hazardSuggested PYRAMID extinguisher
Reception and showroomFurniture and paper, ordinary hazardABC dry powder 6 kg
Service bays and liftsFuel, oils and vehicle electricsABC dry powder 9 or 12 kg, plus a 25 or 50 kg wheeled powder unit in large workshops
Fuel draining and oil change areaFlammable liquid spillsAFFF foam 9 L, or wheeled foam 25 or 45 L in large centers
Oil and used oil storeLiquids in drumsAFFF foam or ABC dry powder 12 kg at the entrance
Welding and cutting areaSparks and nearby materialsABC dry powder 6 or 9 kg next to each welding point
Paint booth and mixing roomSolvents and vapoursAFFF foam and ABC powder outside the booth near the exit; the booth itself per design
Electrical panels, diagnostic and computer equipmentElectrical equipmentCO2 3 to 6 kg
Spare parts and tyre storeCardboard and rubberABC dry powder 9 or 12 kg

The table is engineering guidance. Final quantity and size come from the layout calculation and the design approved by civil protection.

Powder, foam and CO2: when to use each

ABC dry powder

The most widely used extinguisher in a workshop, because it handles solids, liquids and gases. PYRAMID stored pressure powder units come in 1, 3, 6, 9 and 12 kg, conform to EN3 and Egyptian standard ES 8442/2021, with powder to EN 615 and ES 4833. The drawback is residue spreading over engines and equipment, so avoid it on computers and diagnostic gear where another option exists. See PYRAMID dry powder extinguishers.

AFFF foam

Foam forms a film over a burning liquid and prevents reignition, which is what the fuel draining area and oil change pit need. PYRAMID AFFF units come in 6 and 9 L portable and 25 and 45 L wheeled, conforming to EN3 and ES 711. See PYRAMID AFFF foam extinguishers.

CO2

Leaves no residue and does not conduct electricity, so it suits distribution boards, computer diagnostics and battery chargers. It disperses fast in open spaces, so it is not a main extinguisher for a bay open to the street.

Spacing and quantity per NFPA 10

NFPA 10 tables for extra hazard set the following, using the UL ratings the standard is written in:

ItemOrdinary combustibles (Class A)Flammable liquids (Class B)
Minimum rating per extinguisher4-A40-B at 9.1 m travel distance, or 80-B at 15.25 m
Maximum area per unit of A92.9 m²Not applicable
Maximum area per extinguisher1,045 m²Not applicable
Maximum travel distance22.9 m9.1 or 15.25 m by rating

In a workshop the Class B rule usually governs because its distance is shorter. A technician at a lift should reach a suitable extinguisher in a few steps, not at reception. PYRAMID units are rated to EN3, and EN3 ratings do not convert directly to UL ratings, so the consultant confirms sizes against the standard used in the design. The general method is in how many fire extinguishers a space needs.

Installation in the workshop

  • Mount extinguishers so the top is no higher than 1.53 m and the bottom at least 102 mm above the floor.
  • Place them on walkways and exits, not behind lifts or between cars where they get blocked.
  • Park wheeled units on level ground from where they can be pushed to any bay. See wheeled fire extinguishers.
  • Put a clear sign above each extinguisher, because workshops are crowded with cars and parts.
  • Place an extinguisher next to any welding job before starting, not after the first spark.

Electric vehicles in the workshop

As electric and hybrid cars reach service centers in Egypt, a new case appears: traction battery fires. They behave differently from fuel fires and can reignite after being knocked down. Portable extinguishers here deal with early fire in surrounding materials and buy time to move people away; they are not for extinguishing the battery itself. Follow the vehicle manufacturer’s instructions, the emergency plan and call civil protection early.

Licensing and inspection

Licensing of public establishments, including workshops, falls under Public Establishments Law No. 154 of 2019. The Ministry of Local Development and Environment guide reported by Masrawy in July 2026 explains that the pre-licence inspection includes a civil protection representative, and that violating safety and civil protection requirements can lead to administrative closure after a correction period. For the equipment usually checked, see civil protection requirements for shops.

Common mistakes in car workshops

  • One extinguisher by the door for a workshop with four lifts.
  • A small CO2 unit as the main extinguisher in an open bay.
  • Extinguishers buried behind spare parts or tyres.
  • Welding next to oil drums with no extinguisher nearby.
  • Expired or discharged units never refilled, covered in fire extinguisher maintenance and refilling.
  • Relying on extinguishers without training technicians to use them.

Frequently asked questions

What is the best fire extinguisher for a car workshop?

ABC dry powder in 9 or 12 kg is the base in service bays, with AFFF foam for fuel and oil areas and CO2 for electrical panels.

How many extinguishers does a 400 m² workshop need?

The layout calculation decides, and the Class B travel distance usually governs, not area alone. So the number depends on lifts, fuel points and exits.

Does a CO2 extinguisher work on a petrol fire in a workshop?

It works on a small fire in a fairly enclosed space, but powder or foam is more effective in an open bay.

Are PYRAMID extinguishers approved in Egypt?

Yes. PYRAMID powder, CO2 and foam extinguishers conform to the Egyptian standard for each type and are approved by the Egyptian Organization for Standardization and Quality.

Does a paint booth only need an extinguisher?

Extinguishers go outside the booth near the exit. Protection of the booth itself is set by the design and code.

How should we handle an electric car fire in the workshop?

Move people away, call civil protection at once and follow the manufacturer’s instructions. Portable extinguishers are for surrounding materials, not the battery.

Conclusion

A car workshop is an extra hazard area, and its extinguishers are chosen area by area: ABC powder in bays and stores, AFFF foam at fuel and oil points, CO2 for electrics and diagnostics, and a wheeled unit in large workshops. Then they are placed so a technician reaches one within a few steps of the lift, maintained regularly, and staff are trained to use them.

Fitting out a new service center or reviewing a workshop’s extinguishers before licensing? Send us the workshop layout with lifts, fuel and paint areas, and we will propose types, sizes and locations from the PYRAMID range. Talk to the AZEIDK Egypt team

Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.