AFC A-3100 NRS Gate Valve in Egypt: Specs, Dimensions and When to Choose It over OS&Y

AFC A-3100 NRS Gate Valve in Egypt: Specs, Dimensions and When to Choose It over OS&Y

On a site fire main, the valve that isolates a building or a section of the yard network is often buried, sits in a shallow pit, or has no headroom above it. That is where an OS&Y gate valve, whose stem rises as it opens, stops being practical, and a non-rising stem (NRS) gate valve takes its place. This guide covers the American Fire Control A-3100 NRS gate valve: what its submittal states, how it differs from the A-3000 OS&Y, and how to specify it in an Egyptian project without leaving the valve position invisible.

AZEIDK Egypt supplies American Fire Control (AFC) valves as part of its fire fighting systems. The full range is on the American Fire Control brand page.

Key takeaways

  • The A-3100 is a flanged resilient wedge gate valve with a non-rising stem, built to AWWA C515, in sizes 4 to 12 inch.
  • The AFC submittal states 300 psi (21 bar) working pressure, 600 psi (42 bar) test pressure, and UL listing and FM approval.
  • An NRS valve does not show open or closed by itself. The A-3100 has an indicator post flange so a post indicator can be fitted above it.
  • Choose OS&Y (A-3000) inside pump rooms and valve rooms; choose NRS where the valve is buried or headroom is short.
  • Every control valve still needs supervision: a tamper switch, a lock or a seal, plus a written inspection routine.
In this article
  1. What is an NRS gate valve?
  2. What the AFC A-3100 submittal states
  3. Dimensions and weights for the layout
  4. A-3100 NRS or A-3000 OS&Y: which one?
  5. Where the NRS valve fits in an Egyptian project
  6. Indicator post and supervision
  7. How to write the item in the BOQ
  8. Common mistakes
  9. Frequently asked questions
  10. Summary
  11. Sources

What is an NRS gate valve?

In any gate valve a wedge moves up and down across the waterway. In an OS&Y (outside screw and yoke) valve the threaded stem rises out of the yoke as the valve opens, so anyone can see the position from a distance. In an NRS (non-rising stem) valve the thread is inside the body: the stem turns in place and the wedge nut travels along it. The valve keeps the same height when open or closed.

That makes the NRS valve compact in height and suitable for burial, but it also means the position cannot be read from the valve itself. In fire protection this is solved with an indicator post mounted on top of the valve, whose window shows OPEN or SHUT above ground.

What the AFC A-3100 submittal states

The figures below are taken from the American Fire Control fire valves submittal hosted on the AZEIDK website (AFC fire valves submittal, PDF).

ItemA-3100 NRS gate valve
StandardAWWA C515
Sizes4, 6, 8, 10 and 12 inch, with indicator post flange
Working pressure300 psi (21 bar)
Test pressure600 psi (42 bar)
Working temperature0 to 80 °C
End connectionFlanged to ANSI B16.1 Class 125, ANSI B16.42 Class 150 or EN 1092-2 PN16
Operation2 inch square operating nut, non-rising stem, triple O-ring stem seal
Body and bonnetDuctile iron ASTM A536 65-45-12
WedgeDuctile iron with EPDM resilient seal
StemStainless steel 304
CoatingFusion bonded epoxy inside and outside, to AWWA C550
ApprovalsUL listed, FM approved

To check that the listing covers the exact model and size you receive, see how to verify UL and FM certifications in Egypt.

Dimensions and weights for the layout

Face-to-face length and weight matter for the pit size, the pipe supports and the lifting plan. From the same submittal:

SizeFace to face (mm)Height (mm)Flange bolt holesWeight (kg)
4 in (100)229342835.5
6 in (150)267448857
8 in (200)292534891
10 in (250)33063512128
12 in (300)35672012172

The height stays the same open or closed, which is the main reason for choosing NRS in a shallow chamber.

A-3100 NRS or A-3000 OS&Y: which one?

PointA-3100 NRSA-3000 / AG-3000 OS&Y
Position visible on the valveNo, needs an indicator post or a switchYes, from the stem
Height when openFixedIncreases as the stem rises
Sizes in the AFC submittal4 to 12 inch2.5 to 12 inch
EndsFlangedFlanged (A-3000) or grooved (AG-3000)
Typical placeBuried yard mains, hydrant branches, shallow pitsPump rooms, riser rooms, valve rooms above ground

Inside buildings the OS&Y remains the usual choice because its position is obvious at a glance. Its details are in our guide to AFC OS&Y gate valves in Egypt, and the full family of system valves is explained in the fire protection valves guide.

Where the NRS valve fits in an Egyptian project

  • Compound and factory yard mains: sectional valves that let one part of the ring be isolated while the rest stays live, as described in fire hydrant networks for compounds.
  • Hydrant branches: an isolating valve on the branch to each hydrant such as the AFC FW-9000 wet barrel hydrant, so the hydrant can be serviced without shutting the main.
  • Building lead-ins: the valve on the underground feed into each building, ahead of the riser room.
  • Shallow chambers: where the pit depth or a slab above leaves no room for a rising stem.

The A-3100 is a flanged valve, so in a buried run it is joined with flanged fittings or flange adaptors, and the flanges are protected against corrosion like the rest of the buried work.

Indicator post and supervision

A control valve that nobody can see is a classic cause of a dead system: the valve is closed for a repair and never reopened. NFPA 24, the usual reference for private fire service mains, calls for listed indicating valves on these mains. A buried NRS gate valve becomes an indicating valve when a listed post indicator is fitted on its indicator post flange.

  • The indicator post is a separate item. Its length depends on the bury depth of the valve, so state the depth from finished ground level to the valve centre line in the BOQ.
  • The post window should be set and checked at commissioning: OPEN on the window must match a fully open valve.
  • Add supervision: a tamper switch wired to the fire alarm panel, or a lock or seal, as the design requires.
  • Record every closure and reopening, and check sealed valves weekly and locked or supervised valves monthly, the usual NFPA 25 intervals.

How to write the item in the BOQ

A line such as “gate valve 6 inch” leaves room for any valve. A clear description reads, for example: “Gate valve, resilient wedge, non-rising stem, AWWA C515, flanged PN16, 6 inch, 300 psi, UL listed and FM approved, with indicator post flange; complete with listed post indicator for X m bury depth.” More on wording BOQ items is in our fire works BOQ guide. Check valves and butterfly valves on the same main are covered in AFC check valves and AFC butterfly valves.

Common mistakes

  • Burying an NRS valve with no indicator post and no record, so nobody knows its position later.
  • Ordering a waterworks NRS valve that is not UL listed or FM approved for fire service.
  • Mixing flange standards: a PN16 valve against Class 125 or 150 pipework without checking bolt circles.
  • Leaving the operating nut deep in soil with no valve box or access, so the valve cannot be exercised.
  • Not testing the post window against the real valve position at handover.

Frequently asked questions

What does NRS mean on a gate valve?

Non-rising stem. The stem turns without moving up, so the valve height does not change when it opens. The position is shown by an indicator post or a supervisory switch instead of the stem.

Is the AFC A-3100 UL listed and FM approved?

Yes, the AFC submittal states UL listing and FM approval for the A-3100, with 300 psi working pressure. Check the label and the listing of the delivered size against the submittal.

What sizes does the A-3100 come in?

4, 6, 8, 10 and 12 inch, all with an indicator post flange, according to the submittal.

Can I use an NRS valve inside a pump room?

It can be installed, but an OS&Y valve is usually preferred indoors because its position is visible without a post. Follow the approved design and the Egyptian fire code requirements for the project.

Where can I get the A-3100 datasheet in Egypt?

The AFC fire valves submittal is on the American Fire Control brand page, and the AZEIDK Egypt team can send the pages for your sizes with a quotation.

Summary

The AFC A-3100 is the non-rising stem partner of the A-3000 OS&Y: same 300 psi rating and UL/FM approvals, flanged, 4 to 12 inch, and ready for an indicator post. Use it where a valve is buried or headroom is short, give it a post indicator and supervision, and describe it fully in the BOQ.

Planning a yard fire main or replacing buried valves? Send the network drawing, valve sizes and bury depths, and the AZEIDK Egypt team will propose the valves, indicator posts and supervision with datasheets. Request a quotation from AZEIDK Egypt

Sources

  1. Fire Valves Submittal, American Fire Control (A-3100 and A-3000 pages), hosted by AZEIDK
Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.