Every fire pump room has a fire protection check valve on each pump discharge, and more of them on supply lines and at points where water sources meet. The job looks simple: let water pass one way and close when flow reverses. But the wrong type, a reversed arrow or a valve that cannot be isolated for service can leave the network without held pressure.
This article covers two American Fire Control check valves, using figures from the submittal on the AZEIDK website: the flanged A-3150 and the grooved A-3500.
Key takeaways
- The A-3150 is a flanged swing check valve rated 300 psi (21 bar) maximum working pressure and 600 psi test pressure, in sizes 2 to 12 inches.
- The A-3500 is a grooved swing check valve with a spring-assisted SS304 clapper, rated 350 psi (24 bar) working and 700 psi test, in sizes 2 to 12 inches.
- On a pump discharge, the check valve sits between the pump and the discharge control valve, so it can be isolated and opened for service.
- The weakest component sets the line rating. A 350 psi check valve does not upgrade a line with 300 psi valves or couplings.
In this article
- What does a fire protection check valve do?
- AFC A-3150: flanged check valve
- AFC A-3500: grooved check valve with spring-assisted clapper
- The two models side by side
- Where does a fire protection check valve go?
- Installation direction: the arrow and vertical lines
- Flanged or grooved?
- Water hammer and check valve slam
- Inspection and maintenance per NFPA 25
- Common mistakes with check valves
- American Fire Control check valves from AZEIDK Egypt
- Frequently asked questions
- Summary
What does a fire protection check valve do?
A check valve (non-return valve) has a clapper that opens with flow and returns to its seat when flow stops or reverses. In a fire network it:
- Holds system pressure when the pump stops.
- Stops a running pump pushing water back through an idle pump on the same header.
- Keeps pressurised system water out of a lower-pressure supply line.
The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with drawings approved by the General Directorate of Civil Protection (Ministry of Interior). NFPA 20 (fire pumps) and NFPA 25 (inspection, testing and maintenance) are technical references the designer adopts or the contract specifies. For all valve types, see our guide to fire protection valves in Egypt.
AFC A-3150: flanged check valve
The A-3150 is a swing check valve made for fire protection service. The submittal states that it meets or exceeds AWWA C508 (the standard for swing check valves) and has a full waterway, so the open clapper does not reduce the bore.
- Pressure: 300 psi (21 bar) maximum working pressure, 600 psi (42 bar) maximum test pressure.
- Flanges: ANSI B16.1 Class 125 or ANSI B16.42 Class 150.
- Materials: ductile iron ASTM A536 65-45-12 body, cover and disc, bronze seat ring, EPDM seals, SS304 hinge pin.
- Coating and temperature: fusion-bonded epoxy inside and outside to ANSI/AWWA C550; 0 to 80 °C.
- Approvals: the datasheet states UL listed and FM approved. The listing covers the product, not AZEIDK.
Face-to-face length runs from 8 inches (2-inch size) to 27.5 inches (12-inch size), and weight from 15 kg to 280 kg. Large sizes need their own support and a lifting plan.
AFC A-3500: grooved check valve with spring-assisted clapper
The A-3500 is a swing check valve with grooved ends. Its SS304 clapper has an SS304 coil spring that helps it back onto the seat.
- Pressure: 350 psi (24 bar) maximum working pressure, 700 psi (48 bar) maximum test pressure.
- Grooves: to AWWA C606 or metric dimensions.
- Installation: horizontal or vertical, indoor or outdoor, as stated on the datasheet.
- Materials: ductile iron ASTM A536 body, bronze C95400 seat, EPDM seals, SS304 hinge pin and drain plug.
- Coating and temperature: as for the A-3150, with painting available on request.
- Approvals: the datasheet states UL listed and FM approved. The UL Product iQ printout in the same submittal shows the grooved swing checks under codes such as AG-3500 and AF-3500, so match the supplied model code to the directory during approval. The listing covers the product, not AZEIDK.
Weight runs from 2.8 kg (2-inch) to 78.8 kg (12-inch) and length from 6.65 to 21.06 inches, which suits risers and tight pump rooms.
The two models side by side
Figures from the same submittal:
| Item | A-3150 (flanged) | A-3500 (grooved) |
|---|---|---|
| Type | Swing, full waterway, AWWA C508 | Swing, spring-assisted SS304 clapper |
| Max working pressure | 300 psi (21 bar) | 350 psi (24 bar) |
| Max test pressure | 600 psi (42 bar) | 700 psi (48 bar) |
| Ends | ANSI B16.1 Cl.125 / B16.42 Cl.150 | Grooved, AWWA C606 or metric |
| Sizes | 2 to 12 inches | 2 to 12 inches |
| Weight, 4-inch | 34 kg | 8.9 kg |
| Weight, 6-inch | 65 kg | 20.3 kg |
| Weight, 8-inch | 114 kg | 35.7 kg |
| Weight, 12-inch | 280 kg | 78.8 kg |
| Orientation on datasheet | Not stated | Horizontal or vertical |
Where does a fire protection check valve go?
Fire pump discharge
The check valve goes on the discharge pipe between the pump and the discharge control valve, as technical guidance based on NFPA 20 describes. You can then open the check valve for inspection without draining the system. In a complete set with electric, diesel and jockey pumps, such as a 3PUMP set, each pump has its own check valve before its discharge joins the header.
Jockey pump line
The jockey pump discharge also needs a check valve, with an isolating valve after it.
Tank fill lines and source connections
Where a public main or tank fill line connects to the network, or two sources at different pressures meet, a check valve stops water moving from the higher-pressure side to the lower. The authority may require a backflow preventer on the public main connection.
Fire department connection line
A check valve on the fire department connection (FDC) line, before it joins the network, keeps system water from escaping while letting water pumped in from outside enter.
Installation direction: the arrow and vertical lines
The body carries a flow arrow. A reversed check valve blocks flow, and the mistake usually shows at the first pump run, so check the arrow before bolting up.
In vertical runs, swing check valves are installed with flow upward. Downward flow leaves the clapper hanging open and is used only if the manufacturer explicitly allows it. The A-3500 datasheet allows horizontal or vertical installation; the A-3150 datasheet does not mention vertical, so keep it on horizontal runs unless the manufacturer confirms otherwise.
On horizontal runs, keep the cover on top so the clapper moves freely and maintenance is easy. Avoid fitting it straight after an elbow or reducer, where turbulence makes the clapper flutter.
Flanged or grooved?
- Flanged A-3150: suits pump rooms and mains where the other components are flanged, such as the A-3000 gate valve. Match the pipe flange class, bolt count and bolt circle to the datasheet.
- Grooved A-3500: suits grooved lines and risers and saves weight. It pairs with the grooved AG-3000 gate valve. The grooved couplings must themselves be listed for at least the actual working pressure.
The usual control valve after the check valve is an OS&Y gate valve. The A-3000 and AG-3000 are rated 300 psi working pressure in the same submittal. See our article on AFC OS&Y gate valves. If the design uses a butterfly valve instead, see AFC butterfly valves. A 350 psi A-3500 next to a 300 psi valve does not raise the line rating.
Water hammer and check valve slam
When a pump stops, the water column starts to flow back. If the clapper closes late, after reverse flow has picked up speed, the sudden stop creates a pressure surge heard as a loud bang (check valve slam). Manufacturer research shows a valve avoids slam by closing before significant reverse flow develops, helped by a light disc, short travel and a spring. Swing checks without a spring slam most, especially on vertical lines.
This is general engineering guidance, not a code requirement:
- If the bangs repeat, check the pump start and stop settings and how often the jockey pump cycles.
- The A-3500 datasheet lists a coil spring among its parts, and a spring-assisted clapper usually closes faster than one relying on its weight alone.
- For large sizes, ask the manufacturer about orientation.
Inspection and maintenance per NFPA 25
NFPA 25, 2023 edition (section 13.4.2.1, as quoted in technical references), calls for valves to be inspected internally every 5 years to confirm their components operate correctly, move freely and are in good condition. Alarm valves and system riser check valves are inspected externally every quarter. The current edition is 2026, so follow the edition adopted in the project. These are NFPA frequencies, not Egyptian legal requirements.
For an internal inspection, isolate the valve, relieve pressure, remove the cover and check the clapper, seal ring, seat and hinge. The A-3500 drain plug makes draining easier.
Common mistakes with check valves
- Installing the valve with the arrow reversed, or a swing check on a vertical line with downward flow.
- Placing the check valve after the discharge control valve instead of before it, so it cannot be isolated without draining the system.
- Leaving out a check valve on the jockey pump discharge, or on each pump before the header.
- Not comparing the valve rating with the highest actual pressure at that point, including pump churn plus suction pressure.
- Leaving a heavy flanged valve hanging on the pipe without support.
- Accepting a UL or FM logo in a catalogue without checking the model and size in the official directories.
American Fire Control check valves from AZEIDK Egypt
The American Fire Control page on the AZEIDK Egypt website lists check valves among the brand’s products, alongside OS&Y, butterfly and ACV-300 wet alarm check valves, and hosts the submittal used here. They are supplied as part of AZEIDK Egypt’s fire fighting systems solutions, with the datasheet for consultant approval.
Frequently asked questions
What is the difference between the AFC A-3150 and A-3500?
The A-3150 is a flanged swing check valve rated 300 psi maximum working pressure. The A-3500 is a grooved swing check valve with a spring-assisted stainless steel clapper, rated 350 psi.
Can a check valve be installed vertically?
The A-3500 datasheet allows horizontal or vertical installation. As general swing check practice, flow in vertical runs is upward. For the A-3150, confirm with the manufacturer before using it on a riser.
Where does the check valve go on a fire pump discharge?
Between the pump and the discharge control valve, so it can be isolated for service. Each pump, including the jockey, has its own.
What causes the loud bang when the pump stops?
Usually check valve slam after reverse flow has started. A spring-assisted valve closes faster.
How often should a check valve be inspected internally?
NFPA 25 (2023 edition) calls for internal valve inspection every 5 years and quarterly external inspection of system riser check valves.
Summary
Choosing a fire protection check valve starts with its location in the network, then the end type that matches the rest of the line: the A-3150 with flanged valves such as the A-3000, and the A-3500 with the AG-3000 or on risers. Then check pressure against rating, the arrow, orientation and isolation for maintenance.
Preparing the BOQ for a pump room or risers? Send us the sizes, end types and highest expected working pressure, and we will send the matching AFC check valve datasheets. Talk to the AZEIDK Egypt team
Related guides
- Hospital Fire System Maintenance in Egypt: Testing While Operational
- Special Hazard Fire Suppression in Egypt: Technologies Compared
- Food Court Kitchen Fire Suppression in Egyptian Malls: Per-Unit Systems, Alarm Link and Gas Shutoff
- Falcon Gold Fire Hose Reels and Hoses in Egypt: Types and Installation