A fire protection butterfly valve appears in almost every sprinkler and hose cabinet BOQ. Yet it is often written as “butterfly valve, UL/FM, 4 inch”, with no end connection, no approved model per size and no switch wiring.
This article covers the American Fire Control (AFC) BFW-300 wafer and BFG-300/301 grooved butterfly valves available from AZEIDK Egypt: choosing the type, reading the approval table by size, and wiring and testing the position switches.
Key takeaways
- The BFW-300 is a wafer valve clamped between two flanges. The BFG-300/301 is a grooved-end valve to AWWA C606.
- The manufacturer’s datasheets give a 300 psi (21 bar) working pressure and a 0 to 80°C temperature range for both.
- In the FM Approvals guide printout (October 2024), the model number changes with size: 300 covers 2½ to 8 inch, 301 covers 2, 10 and 12 inch.
- The FM approval for these models covers aboveground installation only. Listings and approvals belong to the product, not the supplier.
- Each valve has two switches: a supervisory switch for the panel’s supervisory circuit and an auxiliary switch for a local device. Wire colours differ between the two datasheets.
In this article
- Where is a butterfly valve used in a fire system?
- Wafer or grooved fire protection butterfly valve: BFW-300 vs BFG-300/301
- Model number by size: reading the approval table
- The position switch: two switches inside the gearbox
- Installation points specific to butterfly valves
- Testing the position switch at handover
- Common mistakes when supplying and installing butterfly valves
- Frequently asked questions
- Conclusion
Where is a butterfly valve used in a fire system?
A butterfly valve is an indicating control valve. A disc turns a quarter turn (90°) through a gearbox and handwheel, and a flag indicator on top shows its position. Being short, it is common on floor and zone branches, sprinkler and hose cabinet lines, and pump discharge lines.
The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), together with the project drawings approved by the General Directorate of Civil Protection (Ministry of Interior). NFPA 13 (sprinklers), NFPA 24 (private fire service mains) and NFPA 72 (fire alarm) are technical references that the designer adopts or the contract specifies. For all fire valve types, see our fire protection valves guide.
Wafer or grooved fire protection butterfly valve: BFW-300 vs BFG-300/301
Both share the body, disc and gear operator; only the pipe connection differs. The table follows the manufacturer’s datasheets in the AFC submittal.
| Item | BFW-300 (wafer) | BFG-300 / BFG-301 (grooved) |
|---|---|---|
| Installation | Between two flanges, with bolts running around the body | Two grooved ends joined with grooved couplings |
| Design standard | MSS SP-67 and API 609 | API 609 |
| End standard | ANSI B16.1 Class 125 or ANSI B16.5 Class 150 flanges | Groove dimensions to AWWA C606 |
| Sizes in the datasheet | 2 to 12 inch | 2 to 12 inch |
| Working pressure | 300 psi, 2 to 12 inch | 300 psi (21 bar) |
| Working temperature | 0 to 80°C | 0 to 80°C |
| Body and disc | Ductile iron ASTM A536 65-45-12, disc fully encapsulated in EPDM | Ductile iron ASTM A536 65-45-12, disc fully encapsulated in EPDM |
| Stem | Stainless steel 416 | Stainless steel 416 |
| Coating | Fusion-bonded epoxy powder to AWWA C550 | Fusion-bonded epoxy powder to AWWA C550 |
| Gearbox mounting flange | ISO 5211/1 | ISO 5211 |
When does a wafer valve fit?
The BFW-300 suits flanged lines such as pump rooms. Both flanges must match a class in the datasheet, with bolts tightened in a cross pattern. Removing the valve means opening the joint on both sides.
When does a grooved valve fit?
The BFG-300/301 suits grooved risers and branches and installs faster. NFPA 13 (2022 edition, as quoted by QRFS) requires grooves, couplings and gaskets to be a listed, compatible combination, so match the groove type to the project couplings.
Model number by size: reading the approval table
The AFC valve submittal on the AZEIDK website includes a printout, dated 31 October 2024, from the FM Approvals guide for indicating valves, butterfly type (Class 1112). It shows that the model number changes with size:
| Model | Ends | Approved sizes (inch) | Rated working pressure |
|---|---|---|---|
| BFW-300 | Wafer | 2½, 3, 4, 5, 6, 8 | 300 psi (2065 kPa) |
| BFW-301 | Wafer | 2, 10, 12 | 300 psi (2065 kPa) |
| BFG-300 | Groove x groove | 2½, 3, 4, 5, 6, 8 | 300 psi (2065 kPa) |
| BFG-301 | Groove x groove | 2, 10, 12 | 300 psi (2065 kPa) |
The same table carries three remarks: the models are available with or without supervisory switches, they are approved for indoor and outdoor service, and they are approved for aboveground installation only. The UL Product iQ printout in the same submittal, under butterfly valves, names the BFG-300 and BFW-300.
Note that the BFW-301 is not in the AZEIDK Egypt product range. If the project needs a 2, 10 or 12 inch wafer valve, confirm the available model for that size with the AZEIDK Egypt team before the item is approved.
In practice, write model and size together in the BOQ and submittal, for example “BFG-301, 10 inch”, and check the current listing for that model and size in each body’s official directory. A UL listing or FM approval belongs to the product, not to the supplier or contractor. For step-by-step checks, see our UL and FM verification guide.
The position switch: two switches inside the gearbox
Both datasheets list a built-in supervisory switch. The wiring diagram shows two separate switches in the gearbox, plus a green actuator case ground wire (the S-1/S-2 labels and terminal descriptions below come from the BFW-300 diagram):
- Supervisory switch (S-1): connects to the supervisory circuit of the fire alarm panel. It continues to the end-of-line (EOL) resistor or next device.
- Auxiliary switch (S-2): connects to a separate voltage source to drive a local device such as a bell or horn. It is not part of the panel circuit.
The wire colours differ between the two datasheets: the supervisory switch common is black on the BFW-300 diagram and white on the BFG-300/301 diagram. Do not rely on colour. Read the gearbox label and check continuity, valve fully open and again as it starts to close, before connecting.
Programming at the fire alarm panel
Program the input as a separate supervisory signal, not a fire signal, with the valve location and zone. On addressable panels an input module lets each valve appear by name. The accepted supervision method (electrical, locking or sealing) is set by the project documents and the authority. For suitable panels and modules, see our fire alarm solutions.
Installation points specific to butterfly valves
- Disc clearance: the disc extends beyond the valve body when open. NFPA 13 (2022 edition, as quoted by QRFS) requires that wafer valves with extending parts do not interfere with other system components. Do not fit the valve directly against a check valve, strainer or reducer without enough pipe between them.
- Aboveground only: the FM approval for these models covers aboveground installation only. Valves on buried mains need a suitable type and indicating arrangement, set by the designer under NFPA 24.
- Fire pump suction: a Consulting-Specifying Engineer article based on an earlier NFPA 20 edition states that no valve other than an OS&Y gate valve is allowed in the suction pipe within 50 ft (about 15 m) of the pump suction flange. Check this against the edition adopted for the project before putting a butterfly valve on a suction line.
- Operating space: leave room to turn the handwheel, read the indicator and open the terminal cover.
- Weight: the BFG-300/301 datasheet gives weights from 7.8 kg (2 inch) to 73 kg (12 inch). Support large valves properly and do not leave them hanging on the couplings.
BFW-300 operating torque
Maximum operating torque at 300 psi per the BFW-300 datasheet:
| Size (inch) | 2 | 2½ | 3 | 4 | 6 | 8 | 10 | 12 |
|---|---|---|---|---|---|---|---|---|
| Max torque (N·m) | 5 | 5 | 5 | 6 | 20 | 21 | 35 | 40 |
Testing the position switch at handover
The test proves that closing shows at the panel and clears on reopening:
- Confirm the valve is fully open, the indicator shows it, and the panel shows no supervisory signal for this input.
- Inform the monitoring party and owner first: closing the valve isolates part of the system.
- Start closing the valve slowly. Record when the supervisory signal appears and the input name shown.
- Confirm that any local device on the auxiliary switch operates.
- Return the valve to fully open. Confirm the signal clears at the panel and at the monitoring point.
- Record the result in the acceptance report with the valve number and location.
Signal timing criteria and NFPA 25 inspection frequencies are covered in our AFC OS&Y gate valves article. They apply to supervised control valves in general.
Common mistakes when supplying and installing butterfly valves
- A BOQ item without the end type, so a wafer valve arrives for a grooved line, or the reverse.
- Using one model number for all sizes, although the FM guide lists 2, 10 and 12 inch under the 301 number.
- Wiring the auxiliary switch into the panel circuit instead of the supervisory switch, or trusting wire colours without reading the gearbox label.
- Programming the valve input as a fire signal or general fault.
- Fitting a wafer valve directly against a check valve, so the disc hits it when opening.
- Using these models on a buried line, although their approval covers aboveground installation only.
- Accepting a valve because the catalogue shows UL and FM logos, without checking the model and size in the official directory.
Frequently asked questions
What is the difference between the BFG-300 and the BFG-301?
The datasheet shows no difference in the main specifications. In the FM Approvals guide, the BFG-300 covers 2½ to 8 inch and the BFG-301 covers 2, 10 and 12 inch. Both have grooved ends and a 300 psi rating.
Can the butterfly valve be ordered without a supervisory switch?
The FM guide lists them with or without switches. But a control valve still needs a supervision method accepted by the project and the authority, most often electrical.
Is 300 psi enough for every project?
300 psi is above the 175 psi minimum in NFPA 13, but it must still cover the highest actual pressure at the valve, including pump churn pressure plus suction pressure. For the BFW-300, also check the class of the mating flanges.
Do the UL listing and FM approval belong to AZEIDK?
No. They belong to specific American Fire Control models and sizes. AZEIDK Egypt supplies the product with its datasheet and submittal documents.
Can a butterfly valve go on a fire pump suction line?
According to a Consulting-Specifying Engineer article based on an earlier NFPA 20 edition, only an OS&Y gate valve is allowed in the suction pipe near the pump. Check the adopted edition with the designer first.
Conclusion
Choosing a fire protection butterfly valve starts with the line type: wafer for flanged, grooved for grooved. Write model and size together and verify that exact model. After installation, read the switch label, wire each switch to the right circuit, and test that the signal appears and clears before handover.
Preparing a butterfly valve submittal for your project? Send us the sizes, end connections and system pressure, and we will review the available AFC model for each size with you, with datasheets and submittal documents. Talk to the AZEIDK Egypt team
Related guides
- How Many Fire Extinguishers Do You Need? Quantity, Spacing and Height
- Paint Factory Fire Protection in Egypt: Chemical Plants, AFFF Foam, Solvents and Detection
- Fire Extinguishers for Hotels in Egypt: Type and Size for Corridors, Kitchens, Laundry and Car Parks
- Residential Building Fire Protection in Egypt: Common Areas and Upkeep