A quick response sprinkler uses a thinner glass bulb, so it heats up and opens earlier than a standard response sprinkler with the same temperature rating. In Saudi Arabia AZEIDK supplies Victaulic V27 sprinklers (FireLock, K5.6), a family that offers both response types in upright, pendent and recessed pendent models, which makes it a practical example for choosing the right head.
This guide explains the difference between quick and standard response as the datasheet shows it, which V27 model fits each case, and what to write in the bill of quantities so the right sprinkler arrives on site.
Key points
- V2703: upright, standard response. V2704: upright, quick response.
- V2707: pendent or recessed pendent, standard response. V2708: pendent or recessed pendent, quick response.
- All models are K5.6 (8.1 S.I.) with a 1/2 in (13 mm) nominal orifice.
- Bulb diameter is 5.0 mm for standard response and 3.0 mm for quick response per the datasheet.
- Maximum working pressure 175 psi (FM) and 250 psi (UL), with a 100% factory hydrostatic test at 500 psi.
In this article
- What is a quick response sprinkler?
- Quick response sprinkler or standard response: when to use each
- Victaulic V27 sprinklers: models compared
- V27 K5.6 technical data
- Temperature ratings and bulb colours
- Recessed V27: 1/2 in and 3/4 in escutcheons
- Common mistakes when buying and installing quick response heads
- How AZEIDK helps you select V27 sprinklers
- FAQ
- Summary
What is a quick response sprinkler?
Every glass bulb sprinkler works the same way: liquid inside the bulb expands with heat until the bulb breaks at its rated temperature, the seal is released, and water hits the deflector and spreads over the area. Response type does not change the rated temperature. It changes how fast the bulb gets there.
A thinner bulb has less mass, so it heats faster when hot fire gases pass over it. A quick response sprinkler therefore tends to open at an earlier stage of fire growth. In the V27 family the datasheet lists a 5.0 mm bulb for standard response models and a 3.0 mm bulb for quick response models.
Response is a separate line in the specification, alongside K-factor, temperature and orientation. We cover all four in our guide to sprinkler head types, K-factor and temperature ratings.
Quick response sprinkler or standard response: when to use each
The choice comes from the hazard classification and the approved design, not from wanting a faster head. As a technical reference, NFPA 13 generally requires quick response sprinklers in light hazard occupancies such as offices, hotel rooms and most residential spaces, with specific exceptions in the standard. In higher hazard occupancies the designer sets the response type according to the design criteria used.
NFPA 13 also generally does not allow quick and standard response sprinklers to be mixed in the same compartment, except where the standard permits it, because different opening times change the operating sequence assumed in the calculations. Before adding heads to an existing office or replacing a damaged one, check what is already installed in that compartment.
These standards are references only. In Saudi Arabia the binding requirements are the Saudi Building Code (SBC 801), Civil Defense requirements and the consultant’s approved drawings. See our article on sprinkler hazard classification.
Victaulic V27 sprinklers: models compared
Victaulic datasheet 40.10 groups four models in one family. K-factor and orifice are shared; orientation and response differ:
| Model | Orientation | Response | Bulb diameter |
|---|---|---|---|
| V2703 | Upright | Standard | 5.0 mm |
| V2704 | Upright | Quick | 3.0 mm |
| V2707 | Pendent / Recessed pendent | Standard | 5.0 mm |
| V2708 | Pendent / Recessed pendent | Quick | 3.0 mm |
Upright heads sit above the pipe with the deflector facing up, typically where there is no false ceiling, such as car parks and plant rooms. Pendent heads hang below the pipe, and the recessed version sits partly inside an escutcheon. See upright vs pendent sprinklers.
V27 K5.6 technical data
- K-factor: 5.6 imperial, 8.1 S.I. When pressure is measured in bar, the datasheet notes to multiply the S.I. value by 10.
- Connection: 1/2 in NPT, 20 mm BSPT or IGS grooved.
- Maximum working pressure: 175 psi (1200 kPa) FM, 250 psi (1725 kPa) UL.
- Minimum operating pressure: 7 psi (48 kPa).
- Factory test: 100% hydrostatic test at 500 psi.
- Materials: bronze deflector, load screw and pip cap, die cast brass frame, beryllium nickel spring, glass bulb with glycerin solution.
- Finishes: chrome, white polyester, black, custom colours, and plain brass with the V9 coupling only.
Listings (cULus, FM and others) vary by model, connection and temperature, and the datasheet gives separate tables for threaded and IGS versions. Do not write “UL and FM approved” in general terms; check the row for the exact model, temperature and connection you will supply.
Temperature ratings and bulb colours
The temperature rating is chosen from the highest expected ambient temperature at the ceiling. The classification table in the datasheet:
| Classification | Rating | Max ambient | Bulb colour |
|---|---|---|---|
| Ordinary | 57°C | 38°C | Orange |
| Ordinary | 68°C | 38°C | Red |
| Intermediate | 79°C | 65°C | Yellow |
| Intermediate | 93°C | 65°C | Green |
| High | 141°C | 107°C | Blue |
| Extra High | 182°C | 149°C | Purple |
The datasheet notes that the 182°C rating and the 260°C (black) rating are standard response only. A quick response head for a very hot area is therefore a limited option to review with the designer. In normal air conditioned interiors 68°C is the most common choice.
Recessed V27: 1/2 in and 3/4 in escutcheons
V2707 and V2708 can be installed as recessed pendents with a 1/2 in or 3/4 in adjustment escutcheon. The adjustment absorbs small differences between drop length and ceiling level, so drops do not need to be cut to the millimetre.
- IGS connections are not available for recessed applications, so recessed heads are threaded.
- Use the V27 open end wrench for standard heads and the V27-2 wrench for recessed heads, never a tool that grips the frame.
Where the interior design calls for no visible heads, a concealed sprinkler is the usual answer. See recessed vs concealed and extended coverage sprinklers.
Common mistakes when buying and installing quick response heads
- Writing only “K5.6 pendent sprinkler” in the BOQ: that fits both V2707 and V2708. Specify model, response, temperature, finish and connection.
- Painting heads on site: the datasheet prohibits painting or coating other than factory finishes, because it can delay or prevent operation.
- Installing a head with a cracked bulb: any dropped head or one that has lost bulb fluid must be discarded.
- Working on a pressurised system: Victaulic requires the system to be depressurised and drained before installing or removing heads.
- Ignoring obstructions: obstruction rules for beams, ducts and lights must be followed, or the head will not cover its design area.
How AZEIDK helps you select V27 sprinklers
AZEIDK reviews drawings and BOQs, assigns the right V27 model to each area by response, temperature and finish, and prepares datasheets and listing pages for the submittal. The work can extend to installation, testing and commissioning. See the rest of the brand in Victaulic in Saudi Arabia and the full network under fire fighting systems.
These heads are widely used in malls and commercial buildings, offices and hotels, where light hazard is the usual classification.
FAQ
What is the difference between quick and standard response sprinklers?
The quick response bulb is thinner, so it heats and breaks sooner at the same rated temperature. In the V27 family it is 3.0 mm for quick response and 5.0 mm for standard.
Which V27 models are quick response?
V2704 (upright) and V2708 (pendent or recessed pendent). V2703 and V2707 are standard response.
What is the working pressure of Victaulic V27 sprinklers?
Maximum 175 psi per FM and 250 psi per UL, minimum operating pressure 7 psi, and each head is factory tested at 500 psi.
Can quick and standard response heads be mixed in one room?
As a general NFPA 13 rule no, except where the standard allows it. The final decision is the designer’s under SBC 801 and Civil Defense requirements.
Is a recessed V27 available with an IGS grooved connection?
No. The datasheet states IGS is not available for recessed applications.
Which temperature rating suits air conditioned offices?
Usually 68°C (red bulb), as ambient stays below 38°C, but areas near heat sources need a higher rating per the design.
Summary
A quick response sprinkler is not an optional upgrade; the hazard and the approved design decide it. Victaulic V27 offers both response types at K5.6, so the job is to name the model: V2704 or V2708 for quick response, V2703 or V2707 for standard, plus temperature, finish and connection.
Need V27 sprinklers for your project? Send drawings or the BOQ with ceiling type and hazard classification, and we will send the matching models and datasheets for your submittal. Contact the AZEIDK team
Related guides
- Fire Pump Rooms in Saudi Arabia: Components, Design and Installation
- Hikvision PTZ Camera DS-2SF8C442MXG-ELW/26 (TandemVu): Specifications and When It Suits Large Yards and Car Parks
- Hazen-Williams Formula for Fire Pipe Friction Loss: C Factor, Diameter and How to Calculate
- Magnetic Door Holder and Fire Alarm Release: Keeping Fire Doors Open the Right Way