Hazen-Williams Formula for Fire Pipe Friction Loss: C Factor, Diameter and How to Calculate

Hazen-Williams Formula for Fire Pipe Friction Loss: C Factor, Diameter and How to Calculate

The Hazen-Williams formula is the equation NFPA 13 uses to calculate friction loss in sprinkler piping, and pipe sizing and fire pump selection are built on it. It links friction loss to four variables: flow, the pipe roughness coefficient C, internal diameter and pipe length. Understanding it helps owners and contractors read and review hydraulic calculations, not replace the designer.

For a comparison of fire pump types (electric, diesel, jockey, end suction, split case and vertical turbine), see our full guide.

This article gives the formula in US and SI units, C values by pipe type and system, a worked example showing the effect of each variable, and the places where calculations usually go wrong. It is part of AZEIDK’s engineering design and calculations service.

Key takeaways

  • US units: p = 4.52 × Q1.85 ÷ (C1.85 × d4.87), with p in psi per foot, Q in gpm and d the internal diameter in inches.
  • SI units: p = 6.05 × 105 × Q1.85 ÷ (C1.85 × d4.87), with p in bar per metre, Q in L/min and d in mm.
  • Black steel takes C = 120 in wet systems and 100 in dry and preaction systems. Copper, plastic and stainless take 150.
  • Doubling the flow raises friction loss about 3.6 times. Dropping C from 120 to 100 raises it about 40%.
  • Diameter has the strongest effect, raised to the power 4.87, so the actual internal diameter must be used, not the nominal size.
In this article
  1. What is the Hazen-Williams formula and why is it used for fire piping?
  2. The formula and its variables
  3. C values by pipe type and system
  4. Worked example: the effect of flow, C and diameter
  5. From friction loss to pump pressure
  6. Common mistakes with the Hazen-Williams formula
  7. How to review a hydraulic calculation sheet quickly
  8. Frequently asked questions
  9. Conclusion

What is the Hazen-Williams formula and why is it used for fire piping?

Water moving through a pipe loses pressure through friction with the wall. In a sprinkler network, water must reach the most remote sprinkler in the design area with enough pressure and flow, so the loss in every section from the source to that sprinkler is calculated, then elevation and fitting losses are added. Hazen-Williams is the accepted tool for this in NFPA 13 because it is simple and proven for water at normal temperatures.

It differs from the pipe schedule method, which sizes pipe from the number of sprinklers using a pipe schedule table. Hydraulic calculation gives actual pressure and flow at every node and compares demand with the supply or pump curve.

The formula and its variables

SymbolMeaningUS unitSI unit
pFriction loss per unit lengthpsi per ftbar per m
QFlow in the sectiongpmL/min
CPipe roughness coefficientDimensionless, from the standard’s table
dActual internal diameterinchmm

US units: p = 4.52 × Q1.85 ÷ (C1.85 × d4.87). SI units: p = 6.05 × 105 × Q1.85 ÷ (C1.85 × d4.87). The result is multiplied by the section length plus the equivalent length of fittings and valves to get the total loss for that section.

C values by pipe type and system

C reflects the smoothness of the bore: the higher it is, the lower the loss. Design values in NFPA 13 are lower than those of new pipe because they allow for ageing, as Canute explains. The references we reviewed agree on these values:

PipeSystemC
Black steelWet and deluge120
Black steelDry and preaction100
Galvanized steelWet120
Stainless steelPer the standard’s table150
CopperWet150
Listed plasticWet150
Unlined cast or ductile ironUnderground100

Sources differ on cement-lined ductile iron, so take that value directly from the NFPA 13 edition adopted for the project. Underground mains have further considerations under NFPA 24.

Worked example: the effect of flow, C and diameter

A 2 inch Schedule 40 pipe has an internal diameter of 2.067 inches. It carries 100 gpm over 50 ft:

CaseLoss per ftLoss over 50 ft
Wet system, C = 120about 0.094 psiabout 4.7 psi
Dry system, C = 100about 0.132 psiabout 6.6 psi
Same pipe at 200 gpm, C = 120about 0.339 psiabout 16.9 psi
2½ inch pipe (2.469 in ID), 100 gpm, C = 120about 0.040 psiabout 2.0 psi

In practice, doubling the flow raised the loss about 3.6 times because flow carries the power 1.85, while one pipe size up cut the loss to less than half. That is why upsizing a main is sometimes cheaper than upsizing the pump, a choice made in the calculations, not on site.

From friction loss to pump pressure

Friction loss is only one part of demand. Add:

  • Elevation: each metre of height needs about 0.098 bar (about 0.433 psi per ft).
  • Equivalent lengths: elbows, tees and valves are converted to equivalent pipe length from the standard’s table and added to the actual length.
  • Remote sprinkler pressure: from the sprinkler K-factor and its required flow.
  • Hose stream allowance: added at the point the standard specifies.

The total is then compared with the supply or pump curve, as in our fire pump calculation article. Software runs these steps automatically, but inputs remain the designer’s responsibility, as explained in sprinkler design software.

Common mistakes with the Hazen-Williams formula

  • Using nominal instead of actual internal diameter, a large error given the 4.87 exponent.
  • Using C = 120 for a dry or preaction system instead of 100.
  • Ignoring fitting equivalent lengths on short, heavily branched runs.
  • Calculating on Schedule 40 then supplying Schedule 10, or the reverse, without recalculating, although internal diameters differ.
  • Relying on an old supply flow test that no longer reflects current pressure. See our hydrant flow test guide.

The AZEIDK team checks these points before calculations are approved and matches them to the materials actually supplied, such as KDI pipe in Schedule 10 and 40. The topic matters most for warehouses, where design areas and flows are larger.

How to review a hydraulic calculation sheet quickly

An owner or project manager does not need to redo the calculation, but a few questions catch most errors before approval:

  1. Are input units consistent throughout the file, gpm and inches or L/min and mm?
  2. Does the C value in each section match the system type (wet or dry) and the pipe material in the specification?
  3. Do the internal diameters match the pipe wall that will actually be supplied?
  4. Have fitting equivalent lengths and elevation to the most remote point been added?
  5. When was the supply flow test done, and does it reflect current site pressure?
  6. Does the demand curve sit below the pump or supply curve with a clear margin?

If materials or routes change during construction, the calculations are rerun on the shop drawings before handover, not after.

Frequently asked questions

What is the Hazen-Williams formula for sprinklers?

An equation for friction loss in pipe: p = 4.52 × Q1.85 ÷ (C1.85 × d4.87) in US units, used by NFPA 13 for hydraulic calculations.

What C value applies to steel fire pipe?

120 for black steel in wet systems, 100 in dry and preaction systems, and 120 for galvanized in wet systems, per the NFPA 13 table.

Should I use nominal or internal diameter?

The actual internal diameter for the pipe wall used, since any error is magnified by the 4.87 exponent.

Why is C lower for dry systems?

Design C values allow for pipe ageing, and dry and preaction piping is more exposed to internal corrosion, so the standard uses a lower value.

What happens to friction loss if flow doubles?

It rises about 3.6 times, because flow is raised to the power 1.85.

Is Hazen-Williams enough to size a fire pump?

Not on its own. Elevation, equivalent lengths, remote sprinkler pressure and hose allowance are added, then demand is compared with the pump or supply curve.

Conclusion

The Hazen-Williams formula is simple to write, yet its result is very sensitive to internal diameter, C value and flow. Checking these three inputs and matching them to the materials actually supplied prevents the costliest calculation errors: an oversized pump, or a network that cannot deliver the required pressure. In Saudi Arabia the binding references are the Saudi Fire Protection Code SBC 801 and Civil Defense requirements, with NFPA 13 used as a technical reference adopted by the designer.

Need your hydraulic calculations reviewed? Send us the drawings, calculation file and supply flow test, and our team will check inputs and results before approval. Contact the AZEIDK team

References: The Hazen-Williams Formula (Richard C. Schulte, Building Code Resource Library); The Hazen-Williams formula for use in fire sprinkler systems (Canute)