Fire Protection Check Valves Compared: AFC, Shurjoint and United Brass Works by Type, Size and Approval

Fire Protection Check Valves Compared: AFC, Shurjoint and United Brass Works by Type, Size and Approval

A fire protection check valve lets water flow one way and closes automatically when flow stops or reverses. AZEIDK supplies four models from three brands in Saudi Arabia, and each has its own place in the system: the AFC A-3150 (flanged) and A-3500 (grooved) for 2 to 12 in lines, the Shurjoint RCV grooved riser check valve for wet sprinkler risers, and the United Brass Works 99S threaded bronze valve for small-bore lines. This comparison uses AZEIDK’s product pages only.

All four sit within AZEIDK’s fire fighting systems scope, alongside the gate, butterfly and alarm valves AZEIDK supplies and installs.

Key points

  • AFC A-3150: flanged swing check, 2 to 12 in, 300 psi working pressure, UL listed and FM approved per the catalogue.
  • AFC A-3500: grooved swing check with spring-assisted closing, 2 to 12 in, 350 psi, horizontal or vertical.
  • Shurjoint RCV: grooved riser check for wet systems, single clapper with dual springs for non-slam closing, tested to UL 312, 300 psi, 2½ in and up.
  • United Brass Works 99S: threaded bronze, 1/4 to 2 in, 200 WOG, for small lines such as jockey pump discharge, trim piping and test connections.
  • Selection starts with the valve’s position, line size and end type, then working pressure and the required approval.
In this article
  1. Check valve comparison table
  2. AFC A-3150 and A-3500: main line valves
  3. Shurjoint RCV: a riser check valve
  4. United Brass Works 99S: for small-bore lines
  5. Which check valve should you choose?
  6. Common mistakes
  7. Frequently asked questions
  8. Summary

Check valve comparison table

ItemAFC A-3150AFC A-3500Shurjoint RCVUBW 99S
TypeSwingSwing, spring assistedSingle clapper, dual springs (non-slam)Swing, soft disc
EndsFlanged, ANSI B16.1 Class 125 / B16.42 Class 150Grooved (AWWA C606 or metric)Grooved, NPT or BSP side portsThreaded
Sizes2 to 12 in2 to 12 in2½ in and up1/4 to 2 in
Max working pressure300 psi (21 bar)350 psi (24 bar)300 psi (20 bar)200 WOG at 180°F
Test pressure600 psi700 psiNot stated100% pressure tested
Published approvalUL and FM per catalogueUL and FM per catalogueTested to UL 312Not stated on the page
BodyEpoxy-coated ductile ironEpoxy-coated ductile iron, stainless disc and springDuctile ironBronze
OrientationNot statedHorizontal or verticalHorizontal or verticalPer datasheet; not on its side

AFC A-3150 and A-3500: main line valves

The AFC A-3150 is a flanged swing check with ductile iron body and disc, EPDM seal, bronze seat ring and 304 stainless hinge pin, epoxy coated inside and out to AWWA C550 and meeting AWWA C508. The AFC A-3500 is grooved, with stainless disc, spring and fasteners, a C95400 bronze seat and a higher 350 psi rating, installed horizontally or vertically. In practice the choice between them is the end type: flanged for pump rooms and flanged mains, grooved for grooved networks. Where each goes is covered in our article on the AFC swing check valve.

Shurjoint RCV: a riser check valve

The Shurjoint RCV is designed for wet sprinkler risers, with a single clapper and dual springs that close without slamming, a streamlined low-loss body and vertical or horizontal installation. It is tested to UL 312 and rated 300 psi, with NPT or BSP side ports for trim. More in our article on the Shurjoint RCV riser check valve.

United Brass Works 99S: for small-bore lines

The UBW 99S is a bronze swing check with a soft Buna-N disc, stainless hinge and threaded ends from 1/4 to 2 in, rated 200 WOG at 180°F and 100% pressure tested. Listed uses are back-flow prevention on small lines such as jockey pump discharge, trim piping and test connections. The manufacturer notes it is not recommended for pulsating or vibrating service, must not be installed on its side, and contains lead, so it is not for potable water. It also appears in our article on UBW and Apollo valves.

Which check valve should you choose?

  1. Fix its position: fire pump discharge and mains, a sprinkler riser, or a small line such as jockey pump discharge or the fire department connection.
  2. Match the size: small threaded lines up to 2 in suit the 99S; 2 to 12 in lines point to AFC or RCV depending on the ends.
  3. Match the ends: flanged (A-3150) or grooved (A-3500 or RCV).
  4. Check working pressure: in towers and high-pressure systems the difference between 300 and 350 psi can matter.
  5. Read the required approval and match it to each product page and datasheet.

At the fire department connection the check valve is part of the assembly; see our fire department connection guide.

Common mistakes

  • Installing a check valve against the flow arrow cast on the body.
  • Using a small threaded bronze valve on a main line beyond its range.
  • Installing a valve vertically when its datasheet does not allow it, or fitting the 99S on its side.
  • Ignoring water hammer when flow stops in a riser; the Shurjoint RCV is designed to close without slamming for this reason.

Frequently asked questions

What does a check valve do in a fire protection system?

It lets water flow one way and closes automatically when flow stops or reverses, protecting pumps and piping from back-flow.

What is the difference between the AFC A-3150 and A-3500?

The A-3150 is flanged and rated 300 psi; the A-3500 is grooved with spring-assisted closing and rated 350 psi. Both cover 2 to 12 in.

Which check valve suits a sprinkler riser?

The Shurjoint RCV is designed for wet system risers, closes without slamming and is tested to UL 312.

Which check valve suits a jockey pump discharge?

The line is usually small, and the threaded bronze UBW 99S (1/4 to 2 in) lists this use among its applications.

Can a check valve be installed vertically?

The AFC A-3500 and Shurjoint RCV can be installed horizontally or vertically per their pages; for the others, follow the datasheet.

Summary

There is no single check valve for every position. The AFC A-3150 and A-3500 serve main lines by end type, the Shurjoint RCV serves sprinkler risers, and the UBW 99S serves small-bore lines. Fix the position, size, ends, pressure and approval, then choose. The AZEIDK team handles supply, installation and testing.

Need check valves for a project? Send your drawings or BOQ with sizes and end types, and the AZEIDK team will recommend the right model for each position. Contact AZEIDK

Share this article
This site is registered on wpml.org as a development site. Switch to a production site key to remove this banner.