Addressable fire alarm systems
Bosch AVENAR all-in-one 4000 Addressable Sounder-Beacon (FNX-425U)
Brand
Bosch
View Product
→
AZEIDK Solutions
Integrated Engineering Solutions for Safer Facilities
Fire protection, low current systems, and electromechanical solutions.
Fire Protection & Life Safety
Fire Alarm SystemsAddressable and conventional detection and alarm→Fire Fighting SystemsSprinkler networks, fire pumps and components→Special Fire Suppression SystemsGas and aerosol systems for sensitive equipment→Kitchen Fire Suppression SystemsHood and cooking equipment protection→Smoke Extraction & Emergency VentilationSmoke control to keep escape routes usable→Fire-Rated Doors & Emergency ExitsFire-rated doors and exit hardware→Electromechanical & Contracting
HVAC, Electrical & Plumbing WorksElectromechanical (MEP) works coordinated with fire protection and low current systems→Smart Buildings & Systems IntegrationNetworks, CCTV, access control, fire alarm and BMS working as one→General ContractingProject delivery and trade coordination, with life safety built in from day one→Engineering delivery process
Regulatory & compliance support

Fire Alarm Systems
Addressable and conventional fire alarm systems, designed, installed and tested by AZEIDK
Need the right engineering solution?
Talk to the AZEIDK Team →
The Context Plus FirePlus range consists of intelligent analogue addressable fire alarm control panels designed for small and large fire detection applications.
The panels are compatible with Context Plus addressable detectors and interfaces and support XP95 and Discovery protocols. Multiple panels can also be networked for larger systems.
Cause-and-effect programming can be configured using the ConfigManager Plus programming tool or through the panel front controls.
Available Models:
• ULP-CON1L — FirePlus 1-loop panel, expandable to 4 loops.
• ULP-CON2L — FirePlus 2-loop panel, expandable to 4 loops.
• ULP-CON3L — FirePlus 3-loop panel, expandable to 4 loops.
• ULP-CON4L — FirePlus 4-loop panel.
• ULP-CON5L — FirePlus 5-loop panel requiring a separate battery cabinet.
• ULP-CON6L — FirePlus 6-loop panel requiring a separate battery cabinet.
Key Features:
• Available from 1 to 6 loops.
• Supports up to 126 devices per loop.
• Supports up to 64 zones.
• Loop current of 500mA per loop.
• Supplied with 32 zonal LEDs, with an optional board for zones 33 to 64.
• 5.6A power supply.
• Compatible with XP95 and Discovery protocols.
• Networkable for larger systems.
• Cause-and-effect programming.
• Programming through the front panel or ConfigManager Plus.
• RS485 communication for internal and external modules.
• IP30 cabinet rating.
Technical Specifications:
• Cabinet dimensions: 505 × 407 × 150mm.
• Cabinet material: 1.2mm mild steel.
• Operating temperature: -5°C to +40°C.
• Humidity: 25% to 95%, non-condensing.
• Mains input voltage: 195 to 264V AC.
• Power supply operating range: 20 to 28.2V DC.
• Maximum battery capacity: 24Ah.
• Maximum loop cable length: 1km.
• Loop cable size: 1.5 to 2.5mm².
Expansion and Accessories:
• ULP-1L/XT — One-loop extender PCB.
• ULP-TB — Termination board used when extending a 2-loop panel to 3 loops.
• ULP-NIC — Two-wire network interface card.
• ULP-RDC — SmartTerminal repeater driver card.
• ULP-REP — SmartTerminal repeater with a 2A power supply.
• ULP-HLI — High Level Interface board providing RS232, RS485 and Modbus outputs.
• MB3170 — Serial-to-Ethernet gateway for LAN and WAN connections.
• ULP-BCG — Battery cabinet for 5-loop and 6-loop panels.
• ULP-32LED — 32-zone LED extender board for zones 33 to 64.
Note:
The UL certificate included in the submittal lists models ULP-CON1L, ULP-CON2L, ULP-CON3L and ULP-CON4L. Models ULP-CON5L and ULP-CON6L are listed in the product schedule and require a separate battery cabinet.
View the product’s full specifications and technical information in the official catalogue.