Fire door rating is the time a door, with its frame and hardware, resists fire in a standard test, shown on the label in minutes or hours: 20, 45, 60 or 90 minutes, or 3 hours. The owner does not pick it to suit the budget. It follows the wall the door sits in, and the door is typically rated at about three quarters of the wall rating.
This article answers a common site question, “do I order a 1-hour or a 90-minute door?”, with the usual ratings by location, how to read the label, and what voids a rating after installation.
Key takeaways
- The door rating follows the wall rating on the approved drawing.
- The common US rule: a door at about three quarters of the wall rating, so a 2-hour wall usually takes a 90-minute door.
- Protected stair and shaft doors differ from ordinary corridor doors, which may only need 20 minutes.
- The rating covers the whole assembly: door, frame, hinges, latch and closer, proven by the listing agency’s label.
- In Saudi Arabia the references are SBC 201, SBC 801 and the drawing approved by Civil Defense.
In this article
- What does a fire door rating mean?
- How is the fire door rating set by location?
- 1-hour or 90-minute door for a stair?
- Electrical rooms, generator rooms and internal stores
- Where is the rating shown on the door?
- What voids a rating after installation?
- How to write the fire door rating in the door schedule
- Falcon Gold steel fire doors from AZEIDK
- FAQ
- Conclusion
What does a fire door rating mean?
A fire-rated door is tested installed in its frame with its hardware and rated by how long it stops flame passing. The Steel Door Institute’s SDI-118 lists the usual ratings for swinging doors: 3 hours maximum, then 1½ hours (90 min), 1 hour (60 min), ¾ hour (45 min) and ⅓ hour (20 min).
Labels can carry more: an S after the rating means the door is also tested for smoke leakage, and “20-minute rating tested without hose stream” marks a specific 20-minute category. The duration alone does not fully describe the door in a door schedule.
How is the fire door rating set by location?
A door is an opening in a fire-resisting wall, so it cannot be much weaker than the wall. SDI-118 notes that doors are typically rated at about three quarters of the wall rating. The table summarises common values as presented by Allegion, based on the 2015 International Building Code table and NFPA 80 classes:
| Door location | Typical wall rating | Typical door rating |
|---|---|---|
| Fire walls dividing a building into fire areas | Usually 3 hours | 3 hours |
| Stair enclosures connecting 4 or more storeys | 2 hours | 90 minutes |
| Stair enclosures connecting fewer than 4 storeys | 1 hour | 60 minutes |
| Shafts, exit passageways, 2-hour horizontal separations | 2 hours | Usually 90 minutes |
| Some partitions and hazardous areas, walls of 1 hour or less | 1 hour or less | 45 minutes |
| Many corridor walls | 1 hour or less | 20 minutes |
| Exterior walls, severe / moderate exposure | Per drawing | 90 / 45 minutes |
These are common US reference values that explain the logic. On a Saudi project the designer sets each wall rating under SBC 201 and SBC 801, it appears on the approved drawing, and the door schedule follows from it. For exit requirements, see emergency exits under SBC 201.
1-hour or 90-minute door for a stair?
In IBC-based references, a stair connecting four or more storeys needs a 2-hour enclosure with 90-minute doors, and one connecting fewer than four storeys needs a 1-hour enclosure with 60-minute doors. Basements count as storeys; mezzanines do not. So a request for a “2-hour fire door” usually means the door for a 2-hour wall, which is a 90-minute door, and the schedule should state the correct duration to avoid rejection at submittal.
Electrical rooms, generator rooms and internal stores
Service rooms have no single fixed rating. If the drawing makes the room wall fire-resisting, the door follows that wall. Some electrical rooms also need a particular swing and panic hardware, as explained in our emergency exit door guide. Ask the consultant for the wall rating first, then order the door.
Where is the rating shown on the door?
SDI-118 places the door label on the door edge between the top and middle hinges and the frame label on the frame rabbet, each carrying the listing agency’s mark and the rating. Labels must stay legible for the life of the door. A door intended for fire exit hardware must carry a label stating it is to be equipped with fire exit hardware. Inspectors check both labels, match them to the schedule and look for labels painted over or removed.
What voids a rating after installation?
- A rated door in an unrated frame, or the reverse.
- Cutting or drilling on site for a lock, louver or glass not covered by the listing. SDI-118 notes louvers are not allowed in 20-minute doors.
- Glazing of a size or type outside the manufacturer’s listing.
- Replacing the listed self-latching device with a deadbolt.
- Removing the closer or wedging the door open.
- Fitting hardware not listed for fire doors.
For periodic checks, see fire door inspection and maintenance to NFPA 80.
How to write the fire door rating in the door schedule
The door schedule is what the consultant checks the submittal against and what the site is accepted on. For each door, state:
- Door number, location and the rating of its wall.
- Door rating in minutes and whether smoke leakage testing (S) is required.
- Opening size, number of leaves and swing.
- Hardware: hinges, self-latching device or fire exit hardware, closer, and magnetic holder if any.
- Glazing, with size and type within the manufacturer’s listing.
- Frame rating, equal to the door rating.
Falcon Gold steel fire doors from AZEIDK
Under its fire-rated doors and emergency exit solutions, AZEIDK supplies Falcon Gold steel fire doors to project requirements, with hinges, escape handles, locks and installation accessories, installs them and inspects them under maintenance contracts. Rating, size and hardware for each door come from the approved schedule, and the submittal and datasheet go to the consultant before supply. See also how to order and accept fire-rated doors and fire-rated door price factors.
FAQ
What is the difference between a 1-hour and a 2-hour fire door?
The time the door resists fire in testing. In common practice a 60-minute door goes in a 1-hour wall and a 90-minute door in a 2-hour wall, as set by the drawing.
Do electrical rooms and stairs need fire doors?
Protected stairs need fire-rated doors. An electrical room door follows the rating of its wall on the approved drawing, confirmed by the consultant.
Where is the fire rating written?
On the listing label on the door edge between the top and middle hinges, with a matching label on the frame.
Is a 90-minute door enough for a 2-hour wall?
That is the usual IBC-based practice, but the approved door schedule under the Saudi code is the final reference.
Can a fire door have glass?
Yes, if the glass, its size and glazing method are within the manufacturer’s listing. Additions made on site outside the listing void the rating.
Does a fire door stop smoke?
Not necessarily. Doors tested for smoke leakage carry an S after the rating.
Conclusion
Start from the wall rating on the drawing, set the door rating from it, order the complete listed assembly and check the labels on delivery. That avoids re-supply at approval and inspection.
Have a door schedule? Send us the drawings and schedule and we will review rating, sizes and hardware for each door and quote supply and installation. Talk to the AZEIDK team
Related guides
- Smoke and Heat Detector Spacing: How to Calculate a Layout to NFPA 72
- Fire Pumps: Types (Electric, Diesel and Jockey, End-Suction, Split-Case and Vertical Turbine) and NFPA 20 Basics
- Hospital Fire Sprinkler Systems: Quick-Response Sprinklers for Patient Rooms, Theatres and Laboratories
- CCTV Advantages and Disadvantages: Benefits for Businesses and Homes, Privacy and Hacking Risks, and How to Reduce Them