Many quotation requests from small factories, warehouses and low-rise buildings in Egypt start with one line: we need a 500 GPM fire pump. What they usually mean is a fire pump set rated at 500 US gallons per minute. Flow alone does not define the set, though. The rated pressure decides whether the pump actually serves the building.
This article walks through the 3PUMP 500 GPM @ 8 bar set as shown in the datasheet published by AZEIDK Egypt, when it fits a project and when you need a larger set. It is part of the fire pump solutions supplied by AZEIDK Egypt.
Key takeaways
- The set has an electric main pump and a diesel standby pump of the same model, 3P 4×3-10.2, a jockey pump RV10-10 and three separate controllers.
- The electric motor is 75 HP at 415 V, the diesel engine 84 HP, and the jockey pump 40 GPM at 8.5 bar, 4.0 kW.
- Performance curve results in the datasheet: about 7 bar at 150% flow and about 9.4 to 9.6 bar at churn, both inside NFPA 20 limits.
- The sets supplied in Egypt are Non-Listed. UL/FM listed versions are manufactured and supplied on request.
- 500 GPM equals the demand of one standpipe in NFPA 14, but 8 bar limits the building height the set can serve.
In this article
- What a 500 GPM fire pump means on the datasheet
- Components of the 3PUMP 500 GPM @ 8 bar set
- Electrical data the electrical engineer needs
- Reading the curve: 150% point and churn pressure
- When is a 500 GPM @ 8 bar set enough?
- Jockey pump and controllers
- Non-Listed or UL/FM?
- Common mistakes when ordering a 500 GPM pump
- Frequently asked questions
- Conclusion
What a 500 GPM fire pump means on the datasheet
500 is the rated flow: the water the pump delivers at its duty point. The second number, 8 bar, is the pressure it delivers at that flow. A 500 GPM @ 8 bar set and a 500 GPM @ 10 bar set differ in impeller, motor and price, even though the market calls both a 500 gallon pump.
So do not ask for a price by flow only. Ask for both numbers, as the consultant sets them in the hydraulic calculation, then check the datasheet to confirm the offered set meets that exact duty point, not a nearby one.
The binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with drawings approved by the General Directorate of Civil Protection (Ministry of Interior). NFPA 20 and NFPA 14 are technical references for design and testing.
Components of the 3PUMP 500 GPM @ 8 bar set
The datasheet describes an electric main pump, a diesel standby pump and a jockey pump. Both main pumps are end suction units of the same model. The table below follows the datasheet.
| Item | Electric pump | Diesel pump | Jockey pump |
|---|---|---|---|
| Model | 3P 4×3-10.2 | 3P 4×3-10.2 | RV10-10 |
| Duty point | 500 GPM @ 8 bar | 500 GPM @ 8 bar | 40 GPM @ 8.5 bar |
| Driver | INTEM 225M-2 motor, 415 V, 50 Hz, 3 phase | POWER 4102 diesel engine, 12 V electrical system | 4.0 kW, 50 Hz |
| Power | 75 HP | 84 HP | 4.0 kW |
| Speed | 2970 rpm | 3000 rpm | Not stated in the datasheet |
| Materials | Cast iron casing, bronze impeller, stainless steel shaft, mechanical seal | Same | Stainless steel impeller and shaft |
The datasheet also lists a PACIFIC pressure switch, ONTOR/GALA valves and three individual LS controllers made in Korea. The control panel drawing shows star-delta (Y/Δ) starting. Motor insulation is Class F and protection IP55.
Electrical data the electrical engineer needs
The motor data table attached to the datasheet gives frame 225M-2 as 55 kW (75 HP), 92.1% full load efficiency, and full load current of 99.7 A at 380 V, 94.7 A at 400 V and 91.3 A at 415 V. The locked rotor current in the table is 697 A at 400 V and the approximate motor weight is 405 kg.
These figures size the cable, the feeder breaker and the transformer or generator serving the pump room. A common mistake is sizing the cable on full load current and forgetting starting conditions. Give the electrical engineer the motor data page itself, not only the HP figure. For the method behind the power figure, see fire pump motor power calculation.
Reading the curve: 150% point and churn pressure
The datasheet has two performance curves for model 3P 4×3-10.2, one at 2950 rpm and one at 3000 rpm. Each shows two results marked PASS:
| Curve | Pressure at 150% flow (750 GPM) | Churn pressure (zero flow) |
|---|---|---|
| 2950 rpm | 7.00 bar | 9.42 bar |
| 3000 rpm | 6.89 bar | 9.56 bar |
| NFPA 20 limit for 8 bar rated | Not less than 65%, i.e. 5.2 bar | Not more than 140%, i.e. 11.2 bar |
NFPA 20 requires a centrifugal fire pump to keep churn pressure at or below 140% of rated pressure, and to deliver at least 65% of rated pressure at 150% of rated flow. Both curves sit inside these limits with a clear margin.
Why churn matters: pipes, valves and hose cabinets must withstand it. If city or roof tank pressure adds to the pump pressure, add the two when checking component pressure ratings. For site testing, see fire pump testing in Egypt.
When is a 500 GPM @ 8 bar set enough?
NFPA 14 (2019 edition) sets standpipe demand at 500 GPM for the hydraulically most remote standpipe plus 250 GPM for each additional standpipe, capped at 1,000 GPM in a fully sprinklered building. It requires 100 psi residual pressure, about 6.9 bar, at the most remote valve outlet. So in flow terms, 500 GPM covers a building with one standpipe, or a sprinkler and hose system whose calculated demand does not exceed 500 GPM.
Pressure is the real limit. Take an illustrative two-storey factory in 10th of Ramadan City, with the highest outlet 9 m above the pump centreline and the pump drawing from a ground tank with no added pressure:
- Required pressure at the outlet: 6.9 bar.
- Elevation: 9 m ÷ 10.2 = about 0.9 bar.
- Friction loss in pipes and valves: assumed 0.8 bar for this example only; the real figure comes from the consultant’s calculation.
- Total: about 8.6 bar, above 8 bar.
In this example the set falls short if the design relies on 2.5 inch outlets at 100 psi, and a 750 GPM @ 9 bar set or higher is considered; the available sets are compared in selecting 3PUMP fire pump sets by flow and pressure. In a single-storey warehouse or factory, or a system where the approved design needs lower pressure, 500 GPM @ 8 bar may be enough. The hydraulic calculation decides, not floor area or storey count alone.
Jockey pump and controllers
The RV10-10 jockey pump in this set is rated 40 GPM at 8.5 bar. It makes up small leaks and holds system pressure so the main pump does not start on every small drop. Its start and stop settings sit above the electric pump start pressure, with the diesel start set lower. Settings are covered in jockey pump pressure settings.
Three separate controllers mean each pump has its own panel. At handover, check each controller’s signals to the fire alarm system, such as pump running, failure to start and power loss, as the approved design requires.
Non-Listed or UL/FM?
The sets AZEIDK Egypt supplies at the listed duty points, including 500 GPM @ 8 bar, are Non-Listed, and the datasheet title itself reads NON-UL TECHNICAL SUBMITTAL. The words NFPA PERFORMANCE on the datasheet describe the curve, not a UL or FM listing. If the owner, insurer or consultant requires a listed set, UL/FM versions are manufactured and supplied on request, and this should be written into the specification before pricing.
Common mistakes when ordering a 500 GPM pump
- Asking for flow without pressure, then comparing offers with different duty points.
- Choosing 8 bar for a building taller than the hydraulic calculation allows.
- Sizing the motor cable on HP alone, without full load and starting current.
- Forgetting churn pressure when choosing valve and pipe pressure ratings.
- Writing UL/FM in the BOQ, then receiving a Non-Listed set without changing the specification.
- Ignoring the diesel tank and fuel consumption, covered in diesel fire pump fuel tank sizing.
Frequently asked questions
Which model is used in the 3PUMP 500 GPM set?
Model 3P 4×3-10.2, end suction, for both the electric and diesel pumps, with an RV10-10 jockey pump.
What is the electric motor rating?
75 HP (55 kW) at 415 V, 50 Hz and 2970 rpm, per the datasheet.
Is a 500 GPM fire pump enough for a ten-storey building?
Usually not on pressure, because 8 bar does not cover the elevation plus the pressure required at the top outlet. The hydraulic calculation sets the right pump.
Is the set UL or FM listed?
No. The set supplied in Egypt is Non-Listed. UL/FM versions are available on request.
What is the churn pressure of this set?
The datasheet shows 9.42 bar on the 2950 rpm curve and 9.56 bar on the 3000 rpm curve, both below the NFPA 20 140% limit.
Where can I get the datasheet?
It is published on the AZEIDK Egypt 3PUMP page and can be requested with the submittal when you ask for a quotation.
Conclusion
The 3PUMP 500 GPM @ 8 bar set is a complete package: a 75 HP electric pump, an 84 HP diesel pump and a 40 GPM jockey pump, with a curve inside NFPA 20 limits. In flow terms it suits a one-standpipe building or a system demanding up to 500 GPM, but its pressure usually keeps it to low-rise buildings, factories and warehouses. Always start from the hydraulic calculation, then choose the set that meets the duty point.
Have a hydraulic calculation for a factory or warehouse and want to know if 500 GPM @ 8 bar is enough? Send us the duty point and the network drawings, and we will check them against the datasheet and propose the right set. Talk to the AZEIDK Egypt team