The diesel fire pump fuel tank is often sized last, by eye or copied from a previous project. The result is a tank too small for the required run time, or an oversized one holding diesel that ages inside it.
This article applies the NFPA 20 tank rule, number by number, to the four 3PUMP fire pump sets available in Egypt (500, 750, 1000 and 1500 GPM), starting from the diesel engine in each datasheet: power, specific fuel consumption, litres per hour, tank capacity by both methods, the two-thirds level and diesel stock for weekly runs.
Key takeaways
- Since the 2022 edition, NFPA 20 asks for a tank (as cited by the Clarke calculator and PHCP Pros) that holds 12 hours of engine run time at the fuel consumption rate at rated horsepower, plus 5% for sump and 5% for expansion.
- If the consumption rate is not known, the older rule applies: 1 gallon per horsepower (5.07 L/kW), with the same two allowances.
- Diesel engines in the 3PUMP sets: 84 HP for 500 GPM, 108 HP for 750, 150 HP for 1000 and 240 HP for 1500 GPM, as stated in each set’s datasheet.
- The consumption method gives estimated tanks of about 240 to 565 litres. The 1 gal/hp method gives about 350 to 1,000 litres.
- Per PHCP Pros on NFPA 20, the low fuel signal operates at two-thirds of tank capacity, so never let the level drop below it.
In this article
- Where the numbers come from
- The diesel engine in each 3PUMP set
- From specific fuel consumption to litres per hour
- Diesel fire pump fuel tank capacity by both methods
- The two-thirds rule: the level you never go below
- Diesel stock for weekly runs
- Common mistakes in sizing the fuel tank
- What to ask the supplier for in the quotation
- Frequently asked questions
- Summary
Where the numbers come from
All figures come from the official 3PUMP datasheets published on the AZEIDK website. Each set includes an electric main pump, a diesel standby pump, a jockey pump and controllers on a common base. Sets supplied in Egypt are Non-Listed; UL/FM listed versions are available on request. For the role of each pump in the set, see electric, diesel and jockey fire pumps.
The first data page gives engine model, HP and speed (3,000 rpm for all four); the engine table adds kW and the “minimum specific fuel consumption at full load”.
Note: the table prints the specific fuel consumption (238, 205 and so on) without a unit. The usual unit in diesel engine tables is g/kWh, and our estimate assumes it. Since the printed value is the minimum, actual full-load use may be slightly higher. So the litres per hour here are an engineering estimate; the engine maker’s stated consumption for the supplied engine governs.
The diesel engine in each 3PUMP set
| Set | Pump model | Diesel engine model | Power (HP) | Power (kW) | Printed specific fuel consumption |
|---|---|---|---|---|---|
| 500 GPM @ 8 bar | 3P 4×3-10.2 | 4102 | 84 | 63.8 | 238 |
| 750 GPM @ 9 bar | 3P 5×4-10.2 | 4105BZ | 108 | 80 | 238 |
| 1000 GPM @ 10 bar | 3P 5×4-10.2L | 6102BZQ | 150 | 110 | 205 |
| 1500 GPM @ 10 bar | 3P 6×5-12.4 | 6120Ti | 240 | 179 | 201 |
Each set uses the power on its own data page and the matching value in the same file. To calculate the power the pump itself needs from flow and pressure, see fire pump motor power calculation.
From specific fuel consumption to litres per hour
Three steps:
- Consumption in kg/h = power in kW × specific fuel consumption ÷ 1,000.
- Consumption in L/h = kg/h ÷ diesel density. We assumed 0.84 kg/L, a typical average for diesel.
- Round up when choosing the tank, never down.
Example for the 1000 GPM set: 110 kW × 205 ÷ 1,000 = about 22.6 kg/h. Divided by 0.84, that is about 26.8 L/h, or about 7.1 US gallons per hour.
This is at full rated power. Weekly no-flow runs load the engine less, but design is based on full load.
Diesel fire pump fuel tank capacity by both methods
According to the Clarke calculator, NFPA 20 (2022 edition, 11.4.1.3.1) sets the minimum tank capacity as the engine’s fuel consumption rate at rated horsepower multiplied by 12 hours, plus 5% of volume for sump and 5% for expansion. PHCP Pros reports that no public inputs on this item were received for the 2025 edition cycle. If the engine maker’s consumption rate is not available, the older rule still applies: 1 gallon per horsepower with the same two allowances. Here we combine both allowances into a factor of 1.10, as the Clarke calculator does.
| Set | Estimated consumption (L/h) | Consumption method: 12 h + 10% | 1 gal/HP method + 10% |
|---|---|---|---|
| 500 GPM | 18.1 | about 239 L (63 gal) | about 350 L (92 gal) |
| 750 GPM | 22.7 | about 299 L (79 gal) | about 450 L (119 gal) |
| 1000 GPM | 26.8 | about 354 L (94 gal) | about 625 L (165 gal) |
| 1500 GPM | 42.8 | about 565 L (149 gal) | about 999 L (264 gal) |
The 1 gal/HP fallback gives a tank about 1.5 to 1.8 times larger. The consumption method is more precise only when the engine maker documents the rate.
How to choose the final figure
- Documented consumption rate available: 12 hours + 10%, then the next standard tank size up.
- No documented rate: 1 gallon per HP + 10%.
- Either way, the Civil Protection approved documents and the consultant have the final word.
In Egypt the binding framework is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), with drawings reviewed by the General Directorate of Civil Protection (Ministry of Interior). NFPA 20 is a design reference when project documents adopt it, not a law on its own.
The two-thirds rule: the level you never go below
According to PHCP Pros, NFPA 20 places the low fuel signal at two-thirds of tank capacity. In practice: in a tank sized for 12 hours, the fuel left at two-thirds covers about 8 hours at full load. So only the top third should be treated as usable stock for routine runs, and the tank should be refilled before it reaches two-thirds.
With the 3PUMP sets and consumption-method tanks:
- 500 GPM: 239 L tank, two-thirds level at about 159 L.
- 750 GPM: 299 L tank, two-thirds at about 199 L.
- 1000 GPM: 354 L tank, two-thirds at about 236 L.
- 1500 GPM: 565 L tank, two-thirds at about 377 L.
The tank therefore needs a clear level gauge, with the low fuel signal wired to the diesel controller. For pump room layout and tank location, see fire pump rooms in Egypt.
Diesel stock for weekly runs
EMC Insurance’s fire pump testing guide calls for running the diesel engine weekly for 30 minutes at rated speed, as part of NFPA 25 based programs. Test details are in diesel fire pump maintenance; here we count the diesel it burns.
| Set | Maximum use per 30-minute run | Maximum yearly use (52 runs) |
|---|---|---|
| 500 GPM | about 9 L | about 470 L |
| 750 GPM | about 11.3 L | about 590 L |
| 1000 GPM | about 13.4 L | about 700 L |
| 1500 GPM | about 21.4 L | about 1,115 L |
These are full-load upper limits; no-flow runs use less, and the annual flow test adds more.
The top third of a consumption-method tank equals 4.4 hours at full load, about 8 weekly runs in the worst case. Left alone, a full tank can reach two-thirds in about two months, so plan refills from a weekly level reading.
Common mistakes in sizing the fuel tank
- Sizing the tank on the electric motor rating instead of the diesel engine rating. In the 1500 GPM set, for example, the electric motor is 250 HP and the diesel engine is 240 HP.
- Taking the consumption value from another engine’s column in the general table instead of the model named on the data page.
- Forgetting the 10% for sump and expansion, which leaves a tank that holds 12 hours only on paper.
- Treating the full nominal capacity as usable, when the bottom two-thirds sits below the low fuel signal.
- Using an estimated litres-per-hour figure instead of the engine maker’s documented rate.
- Leaving a large tank for months without checking the diesel and the water at the bottom.
What to ask the supplier for in the quotation
When comparing fire pump set offers, as covered in fire pump set prices in Egypt, ask for the following in writing:
- Diesel engine model and rated power in HP and kW.
- Fuel consumption at rated power, in a clear unit (litres or gallons per hour).
- Whether the fuel tank is in the scope of supply, and if so its capacity, material and fittings.
- Sizes of the fuel supply and return lines and where they connect on the engine.
If flow and pressure are open, start with selecting 3PUMP fire pump sets by flow and pressure, then size the tank on the engine of the chosen set. See also AZEIDK Egypt fire pump solutions.
Frequently asked questions
How many litres of diesel does a diesel fire pump use per hour?
Our full-load estimate from the datasheets: about 18 L/h (500 GPM), 23 (750), 27 (1000) and 43 (1500 GPM). The engine maker’s figure governs.
Should the fuel tank cover 8 hours or 12 hours?
The older rule was based on 8 hours. Since 2022, NFPA 20 asks for 12 hours at rated-power consumption, plus 5% sump and 5% expansion.
When do I use the 1 gallon per horsepower rule?
When there is no documented consumption rate. For the 3PUMP sets it gives a tank 1.5 to 1.8 times larger.
What does “never below two-thirds” mean?
Per PHCP Pros, the NFPA 20 low fuel signal operates at two-thirds of capacity. In a 12-hour tank, the fuel left at that level covers about 8 hours at full load, so refill before you reach it.
How much diesel do I need per year for weekly runs?
At full load, an upper limit of about 470 L a year (500 GPM) up to about 1,115 L (1500 GPM). No-flow runs use less.
Does the Egyptian code set the diesel tank size?
The binding reference is the 2026 Egyptian code (Decree No. 355 of 2026) and what Civil Protection approves. We cite no specific clause here; NFPA 20 serves as the technical reference when project documents adopt it.
Summary
Size a diesel fire pump fuel tank from the engine, not from a ready-made size. For the 3PUMP sets that means about 240 to 565 litres by consumption, or 350 to 1,000 litres by 1 gal/HP. Add the 10% and treat only the top third as routine stock.
Sizing the fuel tank for a fire pump set on your project? Send us the required flow and pressure, and we will send the datasheet for the matching set and the diesel engine data the calculation is based on. Talk to the AZEIDK Egypt team
Related guides
- Data Center Fire Protection in Egypt: Exchanges, Server Rooms and Battery Rooms
- Siamese Connection (Fire Department Connection): Location, Size, Check Valve and Fire Truck Use
- Fire Extinguishers for Factories in Egypt: Choosing Type and Size for Production Halls, Stores and Electrical Rooms
- High-Rise Office Fire Protection in Egypt: Pressure Zones, Pumps, Valves and Alarm