A pharmacy in Egypt often stays open late. Its shelves hold medical alcohol, hand sanitisers, sprays, perfumes and cosmetics, and at the back there is a cardboard store, medicine fridges and a small electrical panel. Choosing a fire extinguisher for a pharmacy is the first step, but the standards of Egypt’s General Authority for Healthcare Accreditation and Regulation (GAHAR) for community pharmacies ask for more than an extinguisher: safe storage of flammable materials, an unobstructed exit, early warning, and a documented fire safety process in line with civil protection.
This article explains what standard CPS.14 requires, then how to choose the extinguisher and smoke detector and where to put them in a typical Egyptian pharmacy, with examples from the fire extinguishers and fire alarm systems supplied by AZEIDK Egypt.
Key takeaways
- Community pharmacies fall within the GAHAR ambulatory healthcare handbook, and their safety standard is CPS.14.
- The standard calls for safe storage of flammable materials, a safe and unobstructed exit, early warning such as smoke detectors, and means of fire suppression.
- Evidence of compliance includes an updated, documented fire safety process in line with civil protection, and a smoke-free environment.
- An ABC dry powder unit near the entrance and a CO2 unit near the electrical panel and fridges is a practical choice for most pharmacies.
- The final number and positions of extinguishers are checked against civil protection requirements in the shop license.
In this article
What the GAHAR standard asks of a pharmacy
The GAHAR ambulatory healthcare handbook (first edition, 2022, with a stated validity of April 2022 to April 2026; we found no newer edition as of November 2026) lists community pharmacies among the facilities it covers and gives them their own set of standards. Standard CPS.14 on environment and facility safety is the one that deals with fire:
| What CPS.14 requires | What it means inside the pharmacy |
|---|---|
| Safe storage and handling of flammable materials | Alcohol, sanitisers and sprays in a set place away from the electrical panel and hot lighting |
| Preventing hazards from construction work in or next to the pharmacy | Watching welding or fit-out work in the next shop and moving flammables away while it lasts |
| A safe, unobstructed means of exit in a fire | A clear path to the door, with no cartons stacked in front of the exit |
| Early warning and detection, such as smoke detectors or fire alarms | A smoke detector in the sales area and another in the store, connected to an alarm panel |
| Means of fire suppression, such as water hoses, chemical agents or sprinklers | Suitable portable extinguishers, plus the building’s systems where they exist |
| A smoke-free environment | No smoking in the pharmacy or the store |
The evidence of compliance for this standard includes an updated, documented fire safety process in line with civil protection. This fits with what civil protection reviews when shops are licensed, which we covered in our article on civil protection requirements for shops.
Fire extinguisher for a pharmacy: which type and where?
A pharmacy has two kinds of hazard: ordinary combustibles and flammable liquids in the sales area and store, and electrical equipment at the back. The practical choice therefore combines two types:
| Location | Extinguisher | Why |
|---|---|---|
| Near the entrance and behind the counter | PYRAMID ABC dry powder, 6 kg | Covers cardboard, shelving and flammable liquids |
| Next to the electrical panel, fridges and tills | PYRAMID CO2 | Leaves no residue on electrical equipment |
| Back store | ABC dry powder | Cartons, cosmetics and alcohol bottles |
| Electrical panel in an enclosed space | Fire Search automatic CO2 unit, 3 kg | Operates automatically when heat builds up in a small space |
Portable PYRAMID dry powder extinguishers come in 1, 3, 6, 9 and 12 kg and comply with EN3 and Egyptian standard ES 8442/2021. CO2 units come in 2, 3, 6, 10, 20 and 30 kg and comply with EN3 and ES 735. The EOS-approved products carry the Egyptian quality mark. Fire Search automatic units come as 6 and 12 kg powder and as 3, 6 and 10 kg CO2; our article on PYRAMID automatic extinguishers explains where they are used.
How many extinguishers does a pharmacy need?
Under NFPA 10, the travel distance to a Class A extinguisher should not exceed 22.9 m. A typical pharmacy is small, but distance is not the only factor: the back store is often behind a door, and the electrical panel sits in another corner. Most pharmacies therefore need more than one extinguisher, and the final number is checked against civil protection requirements. Our article on calculating the number and layout of extinguishers explains the method in detail.
Mounting and height
Under NFPA 10, an extinguisher weighing up to 18.14 kg is mounted with its top no higher than 1.53 m and its bottom at least 102 mm above the floor. In a pharmacy, hang it where it is clearly visible and not hidden by shelving or promotional displays.
Smoke detector and alarm panel in a pharmacy
CPS.14 names early warning and smoke detectors explicitly. For a small pharmacy, a conventional Context Plus system is usually enough: a CFP or FP panel, a Series 65A photoelectric smoke detector in the sales area and another in the store, a manual call point near the door, and an audible sounder. In larger or 24-hour pharmacies, it helps to place the panel where the pharmacist on duty can see it.
The back store is where a fire can start unseen, especially if there is a heater or a lamp close to the cartons. A smoke detector in the store matters more than an extra one in the sales area, where the pharmacist stands all day.
Daily storage habits that cut the fire risk
- Set aside a shelf or cabinet for alcohol, sanitisers and sprays, away from the electrical panel, hot lighting and direct sun on the shop front.
- Do not stack cartons in front of the store door or the back exit.
- Avoid piled-up multi-socket extensions behind the fridges.
- Check each extinguisher monthly: gauge in the green zone, seal intact, tag up to date.
These are simple operating habits, but they are part of what the standard means by safe storage and handling, and they belong in the documented safety process it asks for.
A pharmacy inside a mall, office building or hospital
If the pharmacy sits inside a mall, an office building or a hospital, it is part of the building’s system: its detectors may report to the main alarm panel, a sprinkler line may run through it, or a hose cabinet may stand next to it. Coordinate with building management before installing a stand-alone detector, so it does not conflict with the existing system, while the portable extinguishers stay inside the pharmacy itself. The split of responsibilities between owner and tenant is covered in our article on fire protection in malls.
Maintenance and license renewal
An extinguisher needs a simple monthly check, periodic maintenance, a refill after use or when pressure drops, and replacement at the end of its life. We explained when to refill and when to replace in our article on fire extinguisher service life. AZEIDK Egypt provides supply, maintenance and technical support through its services.
Common mistakes
- One extinguisher behind the counter that nobody can see, and none in the store.
- A powder extinguisher next to the electrical panel and tills instead of CO2.
- Medicine cartons blocking the way to the back door.
- Alcohol bottles and sprays on a shelf above the electrical panel.
- An expired extinguisher or one with no inspection tag, an easy finding to avoid with a simple monthly check.
Frequently asked questions
What is the best fire extinguisher for a pharmacy?
A 6 kg ABC dry powder unit for the sales area and store, and a CO2 unit next to the electrical panel, fridges and equipment, because CO2 leaves no residue.
Does a pharmacy need a smoke detector?
The GAHAR pharmacy standard CPS.14 names early warning and detection such as smoke detectors. A simple conventional system usually serves a small pharmacy.
How many extinguishers does a pharmacy need?
Usually more than one: one for the sales area, one for the store and a CO2 unit for the electrical panel. The final number is checked against civil protection requirements.
Where should alcohol and sanitisers be stored?
On a set shelf or in a cabinet away from the electrical panel and heat sources, because the standard requires safe storage and handling of flammable materials.
Do PYRAMID extinguishers meet Egyptian standards?
Yes. Dry powder units comply with ES 8442/2021 and CO2 units with ES 735, and the approved products carry the Egyptian quality mark.
Conclusion
Fire safety in a pharmacy rests on a few clear elements: the right extinguisher in each part, smoke detection in the store and sales area, a clear exit and orderly storage of flammable materials. These are the same elements the GAHAR standard asks for and that civil protection reviews at licensing.
Opening a new pharmacy or renewing a license? Send us the sales area and store sizes and the panel location, and we will propose the right extinguishers and smoke detectors. Talk to the AZEIDK Egypt team
Related guides
- 750 GPM Fire Pump at 9 bar (3PUMP Set): Reading the Datasheet, 150% Point, Churn and Jockey
- Upgrading a Conventional Fire Alarm to Addressable: Steps and Cables
- PYRAMID CO2 Extinguishers: Sizes and Use in Electrical and Server Rooms
- Fire Triangle and Fire Classes A, B, C, D and K: Choosing the Right Extinguisher