When a project reaches the outdoor fire hydrant line in the BOQ, the usual question is whether a wet barrel hydrant is enough or a dry barrel fire hydrant is needed. With American Fire Control (AFC) that question comes down to three models: the FW-9000 wet barrel hydrant and the F-7700 and F-8700 dry barrel hydrants. The two dry barrel models differ only in how the inlet connects to the buried main.
Below we compare them using AFC’s official datasheet and explain when each fits an Egyptian project. For hydrant basics and acceptance tests, see our article on AFC FW-9000 fire hydrants.
Key takeaways
- The F-7700 and F-8700 are dry barrel hydrants to AWWA C502. The FW-9000 is a wet barrel hydrant.
- The only difference between the F-7700 and F-8700 is the inlet: the F-7700 has an ASME Class 150 or ISO PN16 flange, the F-8700 an AWWA mechanical joint.
- All three models are rated 250 psi (17.2 bar) maximum operating pressure, with a 6 in inlet, two 2½ in hose outlets and one 4½ in pumper outlet, and are UL listed and FM approved.
- Dry barrel pays off where vehicles may hit the hydrant: the break-away coupling, seat and disc are repaired without excavation.
- Order a dry barrel hydrant with its bury depth (dimension G), and plan drainage around the base.
In this article
- Dry vs wet barrel: it is about where the main valve sits
- F-7700 and F-8700 vs FW-9000: datasheet comparison
- F-7700 or F-8700: match the inlet to the buried main
- When to choose a dry barrel fire hydrant in Egypt, and when the FW-9000 is enough
- What to put in the BOQ and submittal for a dry barrel hydrant
- Installation notes specific to the F-7700 and F-8700
- Common mistakes when selecting a dry barrel fire hydrant
- Frequently asked questions
- Conclusion
Dry vs wet barrel: it is about where the main valve sits
In a wet barrel hydrant such as the FW-9000, the barrel is full of water at all times and each outlet has its own valve above ground. In a dry barrel hydrant, the main valve sits below ground at the base, operated by a long stem from the top bonnet, and the barrel stays empty while the hydrant is closed.
To empty the barrel after each use, a dry barrel hydrant has a drain valve at the base. The drawing in AFC’s official F-7700/F-8700 datasheet shows the drain port open when the hydrant is closed and closed when it is opened. AWWA Manual M17 describes modern dry barrel hydrants as having drain valves operated automatically by the main valve mechanism.
Every practical difference below follows from this: impact behaviour, maintenance and site installation.
F-7700 and F-8700 vs FW-9000: datasheet comparison
Values are from AFC’s official datasheets and product pages and the FM Approval Guide pages in the submittal.
| Item | F-7700 | F-8700 | FW-9000 |
|---|---|---|---|
| Type | Dry barrel | Dry barrel | Wet barrel |
| Design reference stated | AWWA C502 | AWWA C502 | See the FW-9000 article |
| Inlet size | 6 in (DN150) | 6 in (DN150) | 6 in (DN150) |
| Inlet connection | ASME B16.5 Class 150 or ISO PN16 flange | AWWA mechanical joint | Flanged |
| Outlets | 2 × 2½ in, 7.5NH thread, and 1 × 4½ in, 4NH thread | Same as F-7700 | 2 × 2½ in and 1 × 4½ in |
| Maximum operating pressure | 250 psi (17.2 bar) | 250 psi (17.2 bar) | 250 psi |
| Factory test | 100% of units at 500 psi | 100% of units at 500 psi | 100% of units at 500 psi |
| Approvals | UL listed, FM approved | UL listed, FM approved | UL listed, FM approved |
| Bury depth | Selected from the dimension G table | Selected from the dimension G table | Not applicable in the same way |
| Repair after impact | Traffic break-away coupling, no excavation | Same as F-7700 | Designed to protect the main valve if hit |
The dry barrel datasheet also lists a ductile iron body, steel stem, bronze seat, 304 stainless below-ground fasteners, red and black AWWA C550 epoxy finish inside and out, and a low-torque seat and disc design.
F-7700 or F-8700: match the inlet to the buried main
The two models are identical above ground, so the buried branch decides.
F-7700: when the branch ends in a flange
The F-7700 suits networks where the hydrant branch is built with flanged fittings, such as a flanged hydrant bend. Check the flange standard: the datasheet gives ASME B16.5 Class 150 or PN16, which must match the mating fitting in bolt count and bolt circle.
F-8700: when the network uses mechanical joints
The F-8700 suits ductile iron networks built with mechanical joint fittings, where the inlet is joined with a follower gland, rubber gasket and bolts instead of flanges. One detail is worth catching at review: the datasheet refers to a mechanical joint per AWWA/ANSI C153/A21.53, while the FM Approval Guide entry for the F-8700 lists a mechanical joint inlet per ANSI/AWWA C111/A21.11. Ask the supplier to confirm the standard that matches your fittings before approval.
For pipe types and joints used in fire networks, see our article on fire protection piping.
When to choose a dry barrel fire hydrant in Egypt, and when the FW-9000 is enough
The classic reason for a dry barrel hydrant is freezing: AWWA C502 covers dry barrel hydrants for use in all climates, including those where freezing occurs. On Egyptian projects, the reason is usually vehicle traffic around the hydrant.
Cases that favour the F-7700 or F-8700
- Hydrants on internal road kerbs used by trucks or forklifts, as in factories, warehouses, container yards and car parks.
- Locations where impacts are frequent and digging around the hydrant later is difficult because of paving or nearby services.
- Projects whose specifications explicitly call for dry barrel hydrants to AWWA C502.
Here the traffic break-away feature at ground line pays off. AWWA M17 describes traffic hydrants as having ground-line parts designed to break on impact to protect the rest of the hydrant, with the hydrant designed to stay closed automatically so there is no leakage. The datasheet lists a traffic repair kit with a new connecting sleeve, clamp ring, pins and O-rings, fitted above ground.
Cases where the wet barrel FW-9000 is enough
- Hydrants in protected locations away from heavy vehicles, such as gardens and internal walkways in residential compound fire hydrant networks.
- Where you want to use one outlet while the others stay closed on their own independent valves.
- Where you would rather not rely on barrel water draining into the soil around the base.
In both cases, hydrant number and location are governed by the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), and by the drawings approved by the General Directorate of Civil Protection (Ministry of Interior). NFPA 24, which covers private fire service mains, is used as a technical reference for design and installation.
What to put in the BOQ and submittal for a dry barrel hydrant
Part of a dry barrel hydrant is buried, so the order needs more data. From the datasheet options:
- Model and inlet connection: F-7700 flanged, stating Class 150 or PN16, or F-8700 mechanical joint, with the joint standard confirmed.
- Bury depth (dimension G): the datasheet offers lengths from 1063 mm (42 in) to 2130 mm (84 in). Pick the length that puts the traffic break-away coupling at finished ground level.
- Outlet thread: standard is 7.5NH on the 2½ in outlets and 4NH on the 4½ in outlet. Other threads and an optional 4 in adapter are available; match the thread to the fire service equipment.
- Approval pages for the exact model: the dry barrel hydrants appear in UL file EX28963 under Base-Valve Design for models F-7700 and F-8700, and in the FM Approval Guide under dry barrel hydrants. Include both in the submittal.
- Repair kits as spares: a seat repair kit and a traffic repair kit, especially for locations exposed to impact.
The American Fire Control page at AZEIDK Egypt shows the AFC products available in Egypt, and our AFC product guide for Egypt maps where each valve and hydrant sits in the network.
Installation notes specific to the F-7700 and F-8700
General installation steps and acceptance tests are in the FW-9000 article and our article on fire fighting network installation stages. Specific to dry barrel hydrants:
- Ground line level: the datasheet drawing places the traffic break-away coupling at ground line. Set it higher or lower and it no longer does its job on impact.
- Drainage around the base: the drain port opens when the hydrant closes, so the ground around the base must let the water out as the manufacturer instructs. AWWA C502 leaves the purchaser to state whether the drain outlet is retained or omitted; decide this per site with the supplier.
- Lubrication: the datasheet shows a stem lube port in the top bonnet and a cold-temperature lube oil. Check it as part of routine maintenance.
- Full open, full close: because the drain valve is tied to the main valve movement, operate the hydrant to the end of its travel in both directions.
Common mistakes when selecting a dry barrel fire hydrant
- Writing “6 in fire hydrant” in the BOQ without stating dry or wet barrel.
- Ordering the F-7700 for a network built with mechanical joint fittings, or the F-8700 for a branch that ends in a flange.
- Leaving out the bury depth, so the hydrant arrives at a length that does not put the break-away coupling at ground line.
- Not matching the flange standard (Class 150 or PN16) to the mating fitting.
- Choosing a dry barrel hydrant for a site whose soil cannot drain barrel water, without checking with the supplier.
- Relying on UL and FM logos in the catalogue instead of attaching the listing page that names the model.
Frequently asked questions
What is the difference between the AFC F-7700 and F-8700?
Only the inlet: an ASME Class 150 or PN16 flange on the F-7700, an AWWA mechanical joint on the F-8700. Body, outlets, pressure rating and approvals are the same.
Do projects in Egypt need a dry barrel fire hydrant when there is no freezing?
Not for freezing. They help where vehicles may hit the hydrant, since the traffic break-away coupling, seat and disc can be repaired without excavation. In protected locations the FW-9000 is usually enough.
Is the F-7700 or F-8700 rated lower than the FW-9000?
No. All three models are rated 250 psi maximum operating pressure per their datasheets, and all are 100% factory tested at 500 psi.
How do I select the length of a dry barrel hydrant?
Take the depth of the buried main to finished ground level, then select dimension G from the datasheet table so the traffic break-away coupling sits at ground line.
Are the F-7700 and F-8700 available from AZEIDK Egypt?
Yes, within the American Fire Control range supplied by AZEIDK Egypt, with a submittal file including the datasheet and UL and FM pages.
Conclusion
The F-7700 and F-8700 share performance, outlets and approvals; the buried main fitting decides between them. Dry barrel suits vehicle traffic and repair without digging, while the FW-9000 is simpler in protected locations. State model, inlet, bury depth and thread, and attach the listing pages for that model.
Not sure whether your project needs dry or wet barrel hydrants? Send us the buried main fittings, depth and site conditions, and we will help you pick the model and prepare the submittal. Talk to the AZEIDK Egypt team