Fire Pump Power Calculation: HP and kW with a 3PUMP 1000 GPM Example

Fire Pump Power Calculation: HP and kW with a 3PUMP 1000 GPM Example

Fire pump power calculation starts with two numbers every designer knows: rated flow and rated pressure. Turning them into a motor size in HP or kW needs two more steps: pump efficiency at each point on the curve, and the highest power drawn up to 150% of rated flow.

Below is the formula in metric and US units, worked step by step on a 3PUMP set rated 1000 GPM at 10 bar, one of the fire pump sets supplied by AZEIDK Egypt, and compared with what the actual datasheet shows.

Key takeaways

  • Hydraulic power in kW equals flow in m³/s multiplied by net pressure in kPa.
  • Shaft power (brake horsepower) equals hydraulic power divided by pump efficiency at that point.
  • For the 3PUMP 1000 GPM at 10 bar set, shaft power works out at about 114 HP at the rated point and about 149 HP at 150% of rated flow.
  • That is why the datasheet motor is 150 HP (110 kW): the motor is sized for the highest power on the curve, not for the rated point alone.
  • The manufacturer’s power curve is the final reference; the hand calculation is a checking tool.
In this article
  1. Three different powers in one pump
  2. Fire pump power calculation: the formula
  3. Worked example: 3PUMP set, 1000 GPM at 10 bar
  4. Why 150 HP and not 115? The role of the 150% point
  5. From shaft power to electrical supply: the motor on a 380 V network
  6. Diesel engine power
  7. Jockey pump: a different calculation
  8. Comparing the 3PUMP duty points available in Egypt
  9. Common mistakes in fire pump motor sizing
  10. Frequently asked questions
  11. Conclusion

Three different powers in one pump

Three numbers are often mixed up:

  • Hydraulic power: the energy the water gains per second. It depends only on flow and net pressure, not on the pump type.
  • Shaft power or brake horsepower (BHP): what the driver must deliver to the pump shaft. It is higher than hydraulic power because of friction, internal leakage and turbulence inside the casing, which is what pump efficiency measures.
  • Driver rated power: the figure on the motor or engine nameplate. It must cover the highest shaft power across the operating range.

The pressure used in the calculation is the pump’s net pressure: discharge pressure minus suction pressure. With a ground tank and near-zero suction pressure, the two are close.

Fire pump power calculation: the formula

Metric units

Hydraulic power (kW) = flow (m³/s) × net pressure (kPa)

Shaft power (kW) = hydraulic power ÷ pump efficiency

To convert to HP, divide by 0.746, since one horsepower is about 0.746 kW.

US units

BHP = flow (GPM) × pressure (psi) ÷ (1714 × efficiency)

The 1714 is a conversion constant between these units and horsepower.

QuantityConversion used
1 GPMabout 0.0631 L/s
1000 GPM0.0631 m³/s, about 227 m³/h
1 bar100 kPa, about 14.5 psi
10 bar1000 kPa, about 145 psi
1 HPabout 0.746 kW

Worked example: 3PUMP set, 1000 GPM at 10 bar

The data comes from the 3PUMP datasheet published on the 3PUMP page at AZEIDK Egypt: end suction pump model 3P 5×4-10.2L, INTEM electric motor frame 280S-2 rated 150 HP at 2960 rpm, POWER diesel engine model 6102BZQ rated 150 HP, and an RV10-12 jockey pump rated 4.0 kW. The datasheet records 8.00 bar at 150% flow and 10.90 bar at shutoff. The set is a Non-Listed version, meaning it is not UL listed or FM approved.

The datasheet gives no efficiency figure in numbers, but the attached efficiency curve reads about 74% at 1000 GPM and about 68% at 1500 GPM. These are approximate readings from the graph.

Step 1: power at the rated point

  • Flow: 1000 GPM = 0.0631 m³/s
  • Pressure: 10 bar = 1000 kPa
  • Hydraulic power = 0.0631 × 1000 = 63.1 kW, about 84.6 HP
  • Shaft power = 63.1 ÷ 0.74 = 85.3 kW, about 114 HP

With the US formula: 1000 × 145 ÷ (1714 × 0.74) = about 114 HP.

Step 2: power at 150% of rated flow

  • Flow: 1500 GPM = 0.0946 m³/s
  • Pressure from the datasheet: 8.00 bar = 800 kPa
  • Hydraulic power = 0.0946 × 800 = 75.7 kW
  • Shaft power = 75.7 ÷ 0.68 = 111.3 kW, about 149 HP
Operating pointFlowPressureEfficiency (approx., from curve)Hydraulic powerCalculated shaft power
Rated point, 100%1000 GPM10 bar74%63.1 kWabout 114 HP
150% of rated flow1500 GPM8.00 bar68%75.7 kWabout 149 HP

The power curve on the same datasheet shows a slightly higher value than the calculation at the rated point, around 125 HP, and about 145 HP at 1500 GPM; these are also approximate readings from the graph. The gap is normal, since efficiency is read approximately from a graph and the manufacturer’s curve is built on test data. Use the hand calculation as a check and the manufacturer’s curve as the reference.

Why 150 HP and not 115? The role of the 150% point

NFPA 20 requires a centrifugal fire pump to deliver 150% of its rated flow at no less than 65% of rated pressure, and shutoff (churn) pressure must not exceed 140% of rated pressure. In our example, pressure at 150% flow is 8.00 bar, or 80% of rated pressure, and shutoff is 10.90 bar, about 109%. Both are marked as passing.

The pump can run close to 150% flow, during a flow test for example, and on centrifugal pumps the power curve usually rises with flow. The motor is therefore chosen to carry the full pump load across the whole operating range without exceeding its ratings. That explains a 150 HP motor against a calculated shaft power of about 149 HP at 150% flow.

In Egypt, the binding reference is the Egyptian fire protection code (2026 edition) and the drawing approval of the General Directorate of Civil Protection. NFPA 20 is a technical reference the consultant adopts for design details.

From shaft power to electrical supply: the motor on a 380 V network

The motor has its own efficiency, so it draws more than it gives the shaft. In the INTEM 2-pole motor data table attached to the datasheet, frame 280S-2 is rated 110 kW (150 HP), with 93.5% full-load efficiency and a 0.89 power factor.

  • Electrical input at full load = 110 ÷ 0.935 = about 117.6 kW.
  • Full-load current in the table: 201 A at 380 V, 191 A at 400 V and 184 A at 415 V.
  • Locked rotor current (LRC), the current at the moment of direct-on-line starting, in the table: 1330 A at 400 V.

The common three-phase supply in Egyptian buildings is 380 V, 50 Hz, while the datasheet lists the motor at 415 V, 50 Hz. Confirm the required winding voltage with the supplier when ordering. Size cables, controller and supply on the current at site voltage and the starting current, not on horsepower alone. Table values are typical; the motor nameplate governs.

Diesel engine power

The diesel engine in the same set is a POWER 6102BZQ rated 150 HP at 3000 rpm, and the datasheet includes a second pump curve at 3000 rpm. The same principle applies: the engine must cover the highest power the pump draws at its operating speed across the whole operating range.

Diesel output, however, falls with altitude and intake air temperature. For each model, the manufacturer defines the reference conditions for the rated power and how to derate it beyond them. In tight or poorly ventilated Egyptian pump rooms in summer, check derated engine power against the manufacturer’s data before approving the set. To compare the role of each driver, see electric, diesel and jockey fire pumps.

Jockey pump: a different calculation

A jockey pump is not sized for the fire demand. It makes up small leaks and holds system pressure so the main pump does not start without need, so its flow is small and its pressure is set slightly above the main pump start pressure. For the 1000 GPM set, the datasheet lists an RV10-12 jockey pump at 40 GPM, 10.5 bar and 4.0 kW. For start and stop settings, see jockey pump pressure settings.

Comparing the 3PUMP duty points available in Egypt

The ratio of motor power to hydraulic power is not fixed, so a motor cannot be picked with a general multiplier. Each duty point has its own curve and efficiency.

Duty pointPump modelRated hydraulic power (calculated)Electric motorDiesel enginePressure at 150%
500 GPM @ 8 bar3P 4×3-10.2about 34 HP75 HP84 HP7.00 bar
750 GPM @ 9 bar3P 5×4-10.2about 57 HP100 HP108 HP7.60 bar
1000 GPM @ 10 bar3P 5×4-10.2Labout 85 HP150 HP150 HP8.00 bar
1500 GPM @ 10 bar3P 6×5-12.4about 127 HP250 HP240 HP8.50 bar

Ratings and pressures are from each datasheet (first pump curve); hydraulic power is calculated. All these sets are Non-Listed versions, and UL/FM versions are supplied on request. To choose the duty point itself, see choosing a 3PUMP fire pump set by flow and pressure.

Common mistakes in fire pump motor sizing

  • Calculating at the rated point only: about 114 HP here, an undersized motor that overloads at the 150% test.
  • Assuming a fixed efficiency: efficiency changes along the curve; read it at each point from the manufacturer’s curve.
  • Using discharge instead of net pressure: subtract any positive suction pressure.
  • Mixing up HP and kW: 150 HP is 110 kW, not 150 kW.
  • Sizing cables on power alone: the current at 380 V and the starting current drive the electrical design.
  • Ignoring diesel derating: pump room heat and altitude cut available power, per the manufacturer’s data.

Frequently asked questions

How do I quickly calculate fire pump horsepower?

Multiply flow in GPM by pressure in psi, then divide by 1714 times the pump efficiency. This gives BHP at that point. Repeat at 150% of rated flow and take the larger value.

Which efficiency should I use if the datasheet does not give a number?

Read it from the attached efficiency curve at each flow. For the 3PUMP 1000 GPM set it reads about 74% at rated flow and about 68% at 1500 GPM (approximate readings from the graph). Do not assume one value for all pumps.

Is a 125 HP motor enough for a 1000 GPM pump at 10 bar?

Not for this pump. The calculation and the power curve point to about 145 to 149 HP near 150% flow, which is why the set comes with a 150 HP motor. A different pump model with a different curve may need a different power.

How many kW does a 150 HP motor draw from the network?

The 280S-2 motor delivers 110 kW at the shaft and has 93.5% full-load efficiency in the manufacturer’s table, so it draws about 117.6 kW electrically, with a full-load current of 201 A at 380 V per the same table.

Why does diesel power differ from the electric motor in some sets?

Each driver is chosen on its rated power at its own speed, the pump curve at that speed, and its manufacturer’s data. In the 1500 GPM set, for example, the motor is 250 HP and the diesel engine 240 HP, and in both cases the manufacturer’s data governs.

Is the jockey pump included in the set’s power calculation?

It is not added to the main fire pump power, but it needs its own supply and controller. For the 1000 GPM set it is rated 4.0 kW per the datasheet.

Conclusion

Fire pump power calculation does not stop at the rated point. Hydraulic power is the starting point, efficiency turns hydraulic power into shaft power, and the 150% point usually sets the motor size. For the 3PUMP 1000 GPM at 10 bar set, this sequence leads to about 149 HP, which explains the 150 HP motor on the datasheet. Then check the 380 V supply and diesel derating for the pump room.