Every total flooding design starts with one question: how many kilograms of agent bring the room to its design concentration? FM-200 quantity calculation is not a rule of thumb. It is a defined formula based on net volume, design concentration, the lowest expected temperature and site altitude.
FM-200 is a trade name for the agent HFC-227ea. The same agent is used in the AFC-227 systems from American Fire Control that AZEIDK Egypt offers under special fire suppression systems, a service that includes the hazard study and agent quantity calculation ahead of supply and installation. This guide explains the formula, then applies it to a server room with a raised floor.
Key takeaways
- Agent mass (kg) = (net volume ÷ specific vapour volume) × (design concentration ÷ (100 − design concentration)).
- The specific vapour volume of HFC-227ea is S = 0.1269 + 0.000513 × T, where T is the lowest expected temperature in °C.
- Design concentration comes from the system’s listed design manual and the hazard class, not from another project.
- Each protected space, such as the room, the raised floor void and the ceiling void, is calculated separately and the quantities are added.
- After the quantity, check the concentration at the highest temperature, pick the cylinder from the datasheet fill range, and run the hydraulic calculation in listed software.
In this article
- The legal reference and the technical references
- FM-200 quantity calculation: the HFC-227ea formula
- Design concentration: where the number comes from
- Net volume, temperature and altitude
- Worked example: server room with a raised floor
- From quantity to an approvable system
- Common mistakes in quantity calculations
- Frequently asked questions
- Conclusion
The legal reference and the technical references
The legally binding reference in Egypt is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026). The General Directorate of Civil Protection (Ministry of Interior) reviews and approves fire protection drawings and systems. The quantity method comes from technical references:
- NFPA 2001: the clean agent standard, latest edition 2025. A design reference, not a law in Egypt on its own.
- ISO 14520-9: the HFC-227ea part of ISO 14520, with specific volume constants and extinguishing concentrations.
- The listed design manual for the system: approved design concentration, nozzle limits and hydraulic method for the supplied model.
Where a generic table conflicts with the system manual or the authority, the manual and what Civil Protection accepts take priority.
FM-200 quantity calculation: the HFC-227ea formula
NFPA 2001, ISO 14520-9 and manufacturers’ manuals use the total flooding formula for halocarbon agents. It assumes some air leaves the room during discharge as the concentration rises (free efflux):
W = (V ÷ S) × [C ÷ (100 − C)]
| Symbol | Meaning | Unit |
|---|---|---|
| W | Required agent quantity | kg |
| V | Net volume of the protected space | m³ |
| S | Specific vapour volume of the agent at the lowest expected temperature | m³/kg |
| C | Design concentration by volume | % |
| T | Lowest expected temperature in the space | °C |
The specific vapour volume of HFC-227ea follows the linear relation S = k1 + k2 × T, with k1 = 0.1269 and k2 = 0.000513 in ISO 14520-9 and in the Viking HFC-227ea design manual. Some tables round k2 to 0.0005; the difference is small, but follow the supplied system’s manual.
The term (1 ÷ S) × C ÷ (100 − C) is the flooding factor: agent mass per cubic metre. At 20 °C, S is about 0.1372 m³/kg, so the flooding factor is about 0.549 kg/m³ at 7%, 0.634 kg/m³ at 8% and 0.721 kg/m³ at 9%.
Design concentration: where the number comes from
Design concentration is the input most often got wrong. It starts from the minimum extinguishing concentration for the fuel class (cup burner test for liquids, surface fire tests for solids), multiplied by a safety factor. According to SFPE’s review of the 2012 edition of NFPA 2001, the standard has set these factors since that edition; confirm them against the edition adopted for the project:
| Hazard class | NFPA 2001 safety factor | Note |
|---|---|---|
| Class A (surface fires in solids) | 1.2 | Use the higher of 1.2 × the minimum extinguishing concentration and the heptane-equivalent value set by the standard |
| Class B (flammable liquids and gases) | 1.3 | Each fuel has its own value; heptane is the common reference |
| Class C (energized electrical equipment) | 1.35 | Applied to the Class A surface fire minimum extinguishing concentration |
The final value differs between references and listed systems. ISO 14520-9 gives a minimum design concentration of 7.9% for Class A surface fires, 8.5% for higher hazard Class A and 9.0% for heptane. The Viking HFC-227ea manual quotes NFPA 2001 values of 6.9% for Class A, 7.3% for Class C and 9.0% for heptane, while the Fike manual gives other values for its own system. The reference is the listed AFC-227 design manual and the actual hazard class.
Concentration limits in occupied spaces
ISO 14520-9 gives HFC-227ea a NOAEL (no observed adverse effect level) of 9.0% and a LOAEL (lowest observed adverse effect level) of 10.5%. NFPA 2001 sets conditions for people’s exposure above these values, and the Fike manual limits exposure in occupiable spaces to 5 minutes. Check the actual concentration at the highest expected temperature and tie it to the pre-discharge delay and evacuation.
Net volume, temperature and altitude
Net volume
Take the actual internal dimensions of the space. Racks, cabinets and equipment are normally not deducted, because they are not solid, permanent structural elements. Deductions follow the standard and the manual. Every connected void, such as the raised floor and ceiling voids, is protected and calculated on its own.
Temperature
The lower the temperature, the smaller S becomes and the more agent you need. So use the lowest expected temperature in the space, not the average. In an air-conditioned server room, that is the lowest temperature the cooling reaches.
Altitude
Lower air pressure at altitude means less agent for the same concentration. The Fike HFC-227ea manual gives correction factors including 1.00 at sea level, 0.89 at 1,000 m, 0.82 at 1,500 m and 0.78 at 2,000 m. Most Egyptian cities are close to sea level, so the factor is about 1.00, but elevated sites need the correction from the approved manual’s table.
Worked example: server room with a raised floor
The inputs below are assumed, only to show the method; the design concentration is not a project recommendation:
- Room: 8 m × 6 m, 3.0 m high from the raised floor surface to the ceiling.
- Raised floor void: 0.4 m deep. No suspended ceiling.
- Lowest expected temperature: 18 °C. Highest expected temperature: 30 °C.
- Assumed design concentration: 7.0%. Site close to sea level (correction factor 1.00).
| Step | Calculation | Result |
|---|---|---|
| Room volume | 8 × 6 × 3.0 | 144.0 m³ |
| Floor void volume | 8 × 6 × 0.4 | 19.2 m³ |
| Specific volume at 18 °C | 0.1269 + 0.000513 × 18 | 0.1361 m³/kg |
| Flooding factor | (1 ÷ 0.1361) × (7 ÷ 93) | 0.553 kg/m³ |
| Room quantity | 144.0 × 0.553 | 79.6 kg |
| Floor void quantity | 19.2 × 0.553 | 10.6 kg |
| Total quantity | 79.6 + 10.6 | 90.2 kg |
Checking concentration at the highest temperature
The same mass gives a higher concentration in a warmer room. The actual concentration is C = 100 × (W × S) ÷ (V + W × S). At 30 °C, S is about 0.1423 m³/kg, so the concentration is about 7.3%. That is below the 9.0% NOAEL, so the example needs no extra measures linked to exceeding that value.
Effect of altitude
If the same room were on a site at 1,000 m, the quantity would be multiplied by 0.89, giving about 80.3 kg.
Selecting the cylinder
Per the available AFC-227 datasheet, the AFC-89 cylinder has a fill range of 44.1 to 85.6 kg, and the AFC-115 a range of 57.2 to 111.0 kg. The 90.2 kg total falls inside the AFC-115 range and exceeds the AFC-89 maximum. The final arrangement depends on the hydraulic calculation and nozzle layout.
From quantity to an approvable system
Per the available AFC-227 datasheet, the agent is stored as a liquid in cylinders superpressurized with nitrogen to 24.8 bar (360 psi) at 21 °C, and the agent cylinders and most system components are UL listed and FM approved. Both nozzle types, 180° and 360°, cover up to 12.62 × 12.62 m, in enclosures 0.3 to 4.5 m high, mounted no more than 0.3 m below the ceiling. Orifice sizes come from listed flow calculation software.
The Viking and Fike manuals, following NFPA 2001, require halocarbon agents to discharge in 10 seconds or less, and the enclosure must hold the concentration long enough. So check enclosure tightness after installation, as covered in room integrity testing for clean agent systems, and review the releasing panel, the release sequence and the ventilation openings that must close before discharge. For a comparison of clean agents, see clean agent fire suppression in Egypt.
Common mistakes in quantity calculations
- Copying the design concentration from another project: it differs by hazard class and listed system.
- Forgetting the raised floor or ceiling void: the whole space ends up below design concentration.
- Using the summer temperature: quantity uses the lowest expected temperature.
- Skipping the maximum concentration check: occupied spaces need the NOAEL and LOAEL check.
- Choosing the cylinder by size, not fill range: each cylinder has a minimum and maximum fill.
- Treating the hand calculation as the final design: pipe sizes, nozzles and discharge time come from listed hydraulic software.
Frequently asked questions
Are FM-200, HFC-227ea and AFC-227 the same thing?
FM-200 is a trade name for the agent HFC-227ea, and AFC-227 is the American Fire Control system that uses the same agent. The quantity formula is the same, but design concentration, nozzle limits and the hydraulic calculation come from the supplied system’s manual.
Why use the lowest temperature in the calculation?
The specific vapour volume drops as temperature falls, so more agent is needed for the same concentration.
Is the raised floor void calculated separately?
Yes. Each protected space is calculated from its own volume, the quantities are added, and each space gets its own nozzles.
Is altitude correction needed in Egypt?
Most Egyptian cities are close to sea level, so the factor is about 1.00. Elevated sites need the quantity corrected using the table in the approved system manual.
Is a hand calculation enough for a Civil Protection submission?
The hand calculation is a first step to estimate the quantity and cylinder size. The technical file usually also needs a listed hydraulic calculation, nozzle and piping drawings and product documents, as the authority requires.
Conclusion
FM-200 quantity calculation rests on four inputs: the net volume of each space, the design concentration from the listed manual, the lowest expected temperature and the altitude correction. Then check the concentration at the highest temperature, pick the cylinder from its fill range, and complete the design with the hydraulic calculation and the room integrity test.
Need the agent quantity for a server or electrical room? Send us the space dimensions, temperatures and equipment type, and our team will review the hazard study and propose a suitable American Fire Control system. Talk to the AZEIDK Egypt team







