Jockey Pump Settings: Role, Start and Stop Pressures, Short Cycling

Jockey Pump Settings: Role, Start and Stop Pressures, Short Cycling

The jockey pump is the smallest pump in the fire pump room, yet it runs most often. It keeps the system pressurised so the main fire pump starts only when water really flows. Wrong start and stop settings cause one of two opposite problems: a main pump that starts with no fire, or a jockey pump trying to feed an open sprinkler alone.

This article covers the jockey pump’s role, how its settings sit against the main pump settings under NFPA 20 guidance, a worked datasheet example, and the causes and fixes of short cycling.

Key takeaways

  • A jockey pump makes up allowable leakage and normal pressure drops. It is not counted in the firefighting flow.
  • Under NFPA 20, a jockey pump does not have to be listed, but it must be approved, and its controller must be listed.
  • NFPA 20 annex guidance, as summarised by ASPE: stop the jockey at the main pump churn pressure plus the minimum static suction pressure, and start it at least 10 psi (about 0.7 bar) lower.
  • The first fire pump starts about 5 psi (about 0.35 bar) below the jockey start, and each additional pump about 10 psi lower.
  • Short cycling is a symptom. Look for a leak, a passing check valve, a narrow pressure band or a faulty sensing line.
In this article
  1. What does a jockey pump do in a fire protection system?
  2. How is a jockey pump sized?
  3. Setting jockey pump and fire pump start and stop pressures
  4. Worked example from a 3PUMP datasheet
  5. Jockey pump short cycling: causes and fixes
  6. Common jockey pump mistakes
  7. Frequently asked questions
  8. Summary

What does a jockey pump do in a fire protection system?

Every sprinkler or standpipe system loses pressure slowly: small joint leaks, a drain valve that does not seal fully, or water cooling in the pipes. If the main fire pump made up these losses, it would start again and again with no fire, sending a pump-running signal to the alarm panel each time.

The jockey pump, also called a pressure maintenance or make-up pump, is a low-flow, high-pressure pump that starts on a small pressure drop and stops once pressure recovers. According to the NFPA 20 second revision statements for the 2025 edition cycle, published by NFPA, the term “jockey pump” replaces the other names. The change is in terminology only.

In the fire pump solutions from AZEIDK Egypt, the jockey pump is part of a complete set: an electric main pump, a diesel standby pump and a jockey pump, each with its own controller, on a common base.

What NFPA 20 requires for the jockey pump

  • It does not need to be listed by a testing laboratory, but it must be approved by the authority having jurisdiction.
  • It is sized to make up pressure lost to allowable leakage and normal pressure drops, with enough discharge pressure to hold the required system pressure.
  • Its controller must be listed, but does not need to be listed for fire pump service.
  • It has its own pressure sensing line, installed to the same rules as fire pump sensing lines.
  • The main or standby fire pump must not be used to maintain pressure, except in limited cases the standard defines.

In Egypt, the binding reference is the Egyptian Code for the Design and Implementation of Fire Protection for Buildings, 2026 edition (Ministerial Decree No. 355 of 2026), and drawings are approved by the General Directorate of Civil Protection (Ministry of Interior). NFPA 20 is a technical design reference where the designer or contract adopts it.

How is a jockey pump sized?

The most common mistake is oversizing the jockey “to be safe”. The NFPA 20 annex says that on aboveground-only systems the jockey flow should be less than one sprinkler’s flow. When a sprinkler opens, pressure must fall to the main pump start point. If the jockey can feed that sprinkler, the main pump may never start and its running signal never reaches the alarm panel.

Systems with buried mains have a defined allowable leakage. Here the annex suggests a pump that makes it up within 10 minutes, or 1 gpm, whichever is larger.

A practical check against sprinkler flow

Sprinkler flow is Q = K × √P. A standard K5.6 sprinkler (US units) at about 130 psi (roughly 9 bar) discharges about 64 gpm. Compare it with the jockey flow at operating pressure, not only at its design point, since jockey flow rises as pressure falls.

Setting jockey pump and fire pump start and stop pressures

The aim is a clear sequence: jockey first, then the electric pump, then the diesel. The NFPA 20 annex, as summarised by the American Society of Plumbing Engineers (ASPE), gives this guidance for pressure-started pumps. It is explanatory text, not a mandatory requirement:

  1. Jockey stop: main pump churn pressure plus the minimum expected static suction pressure.
  2. Jockey start: at least 10 psi (about 0.7 bar) below the jockey stop.
  3. First fire pump start: 5 psi (about 0.35 bar) below the jockey start.
  4. Each additional pump: 10 psi (about 0.7 bar) below the previous one.

These gaps limit water hammer, because the large pump starts close to the pressure it will deliver. If switch differentials do not allow these exact values, set the closest possible and confirm them with a calibrated gauge, not the controller display alone.

Controller start/stop logic, the minimum run timer and the sensing line are covered in our guide to fire pump controllers.

Worked example from a 3PUMP datasheet

The official datasheet for the 3PUMP 500 GPM @ 8 bar set (Non-Listed) shows churn pressure of 9.42 bar on the electric pump curve and 9.56 bar on the diesel curve. The jockey pump is model RV10-10, rated 40 GPM at 8.5 bar, 4.0 kW. The suction pressure is not from the datasheet: for this example only, assume a water tank with positive suction and a minimum static suction pressure of 0.2 bar. Use the actual value on each project.

Set pointGuidance ruleApproximate value in the example (assumed 0.2 bar suction)
Jockey stopChurn + minimum static suction9.42 + 0.2 (assumed) ≈ 9.6 bar
Jockey startAt least 0.7 bar below stop8.9 bar
Electric pump start0.35 bar below jockey start8.55 bar
Diesel pump start0.7 bar below electric start7.85 bar

Notes on the example:

  • These are factory curve figures. On site, recalculate with the churn pressure measured at acceptance.
  • The jockey must reach its stop point. Its design point is 8.5 bar, but the RV10-10 performance table in the same datasheet shows about 104 m head at 2 m³/h (roughly 10.2 bar) and 101 m at 4 m³/h (roughly 9.9 bar), which is above 9.6 bar at low flow.
  • Maximum system pressure (churn plus highest suction pressure) must not exceed component ratings.

The datasheet also shows a separate pressure switch and controller for each of the three pumps, so each set point is adjusted independently. To choose the set by flow and pressure, see our fire pump selection guide.

Jockey pump short cycling: causes and fixes

Short cycling means the jockey starts and stops at very short intervals. It wears the motor and contactor and usually hides a system problem. Treat the jockey as an indicator: a sudden change in its run pattern means something has changed.

CauseWhat you seeFix
Leak in the systemRegular cycles at roughly fixed intervals, even at nightIsolate sections with control valves; check drains, test connections and grooved joints
Check valve not sealingFast drop right after stopping; backflow through an idle pumpInspect discharge check valves; clean or replace the clapper
Narrow start/stop bandVery short cycles even on a tight systemWiden the band to at least 10 psi (about 0.7 bar) per NFPA 20 annex guidance
Oversized jockeyPressure rises very fast and the pump stops within secondsReview capacity against allowable leakage; use a minimum run timer if the controller has one
Faulty sensing lineUnstable readings, or the jockey reacting when another pump startsSeparate line per pump, tapped between check and isolation valves, air bled
Trapped airPressure swings and slow settling after fillingVent air from the high points after filling or after any modification
Temperature changesCycling at certain times of day with no leakCheck peak pressure; keep the stop point clear of the relief valve setting

Practical diagnosis steps

  1. Log starts per hour and cycle length over several days.
  2. Close the jockey discharge valve after it stops and watch the gauge. A fast drop means losses in the system or through check valves.
  3. Isolate parts of the system one at a time to find the leak.
  4. Compare a calibrated gauge with the controller set points.
  5. After repair, re-measure the cycle interval against the log.

Common jockey pump mistakes

  • Setting the jockey stop below the main pump churn pressure, so the main pump starts on any small fluctuation.
  • Setting the main pump start too close to the jockey start, so the two pumps overlap.
  • A jockey able to feed an open sprinkler, so the main pump does not start in a fire.
  • Sharing one sensing line between pumps, or taking it from the wrong point.
  • Trusting the controller display without checking against a calibrated gauge.
  • Fixing short cycling only by widening the band, without looking for the leak.
  • Switching the jockey off, leaving the main pump to maintain pressure.

For installation requirements in the pump room see our fire pump room guide, and for the periodic test programme see our fire pump testing guide.

Frequently asked questions

Does a jockey pump have to be UL listed?

Under NFPA 20, the jockey pump need not be listed but must be approved, and its controller must be listed. Project documents and Civil Protection requirements decide what is accepted.

What should the gap be between jockey start and stop pressure?

NFPA 20 annex guidance is at least 10 psi (about 0.7 bar). A narrower band makes short cycling more likely.

Why does the main fire pump start even though the jockey is running?

Usually the main pump start is too close to the jockey start, the sensing line picks up surges, or the loss exceeds jockey capacity. It may also be real flow, so check that first.

How often should a jockey pump run normally?

There is no single figure. Log the run rate after handover as a baseline, and investigate whenever it rises clearly.

Do 3PUMP sets include a jockey pump?

Yes. AZEIDK Egypt sets include an electric main pump, diesel standby pump, jockey pump and controllers on one base. In Egypt they are Non-Listed; UL/FM versions are supplied on request.

Summary

A jockey pump stops the main pump starting without reason, if it is small enough and its pressures sit above the main pump start point. Start from actual churn and minimum suction pressure, space the set points with the NFPA 20 annex guidance gaps, and confirm with a calibrated gauge. If the jockey runs more than usual, find the cause in the system before changing settings.

Jockey pump running constantly, or setting up a new pump set? Send us the datasheet, acceptance test results and suction arrangement, and we will review the settings and the right 3PUMP set with you. Talk to the AZEIDK Egypt team