A patch panel is the rack-mounted panel where the network cables from office outlets terminate, and from which short patch cords run to the switch. Three things decide the right choice: the cable category (Cat6 or Cat6A), the shielding (UTP or STP), and the port count with spare space in the rack.
The structured cabling and network products AZEIDK supplies are listed under network systems.
This guide explains what a patch panel does in structured cabling, how to read its datasheet and how to lay it out in the cabinet, using the Legrand LCS³ 033770 Cat6A panel that AZEIDK supplies within its passive network systems range as a worked example.
Key points
- The patch panel is a fixed termination point for horizontal cable; wall cable should not plug straight into the switch.
- Panel, cable and jacks should share one category. A channel performs only as well as its weakest component.
- Shielded (STP) panels go with shielded cable and need proper rack bonding; UTP panels go with unshielded cable.
- The Legrand 033770 is a 1U panel with 24 Cat 6A RJ45 ports in four removable cassettes and, per its datasheet, supports PoE up to 90 W (Type 4).
- Lay panels out with cable managers and switches so patch cords stay short and labelled.
What is a patch panel, and why not connect cable directly to the switch?
Structured cabling splits every link into a fixed part and a flexible part. The fixed part is the horizontal cable that runs through ceilings and walls from the wall outlet to the rack and terminates on the back of the patch panel. The flexible part is the short patch cord between the panel front and the switch port. Choosing that cord, its category and length is covered in the patch cord guide.
- Solid horizontal cable does not tolerate repeated bending; a damaged patch cord is simply replaced.
- Moving a user or reassigning an outlet from the data network to the CCTV network means changing one patch cord, not opening a ceiling.
- Every panel port carries a number that matches the outlet on site, which makes fault tracing and documentation simple.
- Switch ports are protected from the weight and strain of heavy cable bundles.
That is why the patch panel is a basic part of any network and communication system, from a small office with a wall rack to a building with several telecom rooms.
Patch panel types: how to choose the right one
By category: Cat6 or Cat6A
The panel is rated in the same category as the cable. If a project is designed on Cat6A to carry 10 Gbit/s over a full-length channel, the cable, jacks, panel and patch cords should all be Cat6A. Fitting a Cat6 panel to Cat6A cable gives you a Cat6 channel. For more on categories see our structured cabling guide.
By shielding: UTP or STP
UTP panels are used with unshielded cable and are the most common choice in offices. Shielded (STP/FTP) panels are used with shielded cable where electromagnetic interference is high, for example near motors or heavy power cables. Shielding only works when it is continuous from the jack through the panel to the rack earth. In the Legrand LCS³ range, 033770 is the UTP version and 033772 is the shielded version.
By construction: fixed ports or modular
Some panels have ports built into the body; others are modular, taking separate keystone jacks or cassettes. Modular panels are easier to maintain because a damaged port is replaced without replacing the panel. The Legrand 033770 holds 24 RJ45 connectors in four cassettes of six that slide out from the front.
By port count and height
The common size is 24 ports in 1U; some manufacturers offer 48 ports in 1U or 2U. Count the outlets on the drawings, add spare ports for future expansion, and spread them over 24-port panels, which are easier to label and to match with 24-port switches.
Legrand LCS³ 033770 datasheet values
| Item | Value |
|---|---|
| Ports | 24 x RJ45 Category 6A, unshielded (UTP) |
| Cassettes | 4 removable cassettes, 6 connectors each |
| Format | 19-inch panel, 1U |
| Termination | Toolless insulation displacement (IDC), 568A/B marking |
| Standards | ISO/IEC 11801 edition 3.0 (2017); EIA/TIA 568 C2-1 |
| Endurance | 2,500 plug insertion/withdrawal cycles |
| PoE | Up to 90 W (Type 4) |
| Conductors | Solid or stranded, 0.4 to 0.65 mm (AWG 26 to 22) |
| Dimensions | 43.85 x 482.5 x 321.7 mm |
| Material | DC01 galvanised sheet steel |
| Related codes | 033772 STP panel; 033773 set of 6 UTP connectors; 033775 set of 6 STP connectors |
Source: Legrand’s official product page and datasheet, as published on the AZEIDK product page. Note the 321.7 mm depth when choosing a shallow wall cabinet.
Laying out patch panels in the rack
- Panel, cable manager, switch: mount a 24-port panel, a horizontal cable manager next to it, then the switch. Patch cords stay very short; 30 and 50 cm cords such as the AZ-Link Cat6 patch cords suit this layout.
- Fibre at the top: a 1U fibre drawer such as the Legrand LCS³ 032165 sits close to the switch uplink ports.
- Heavy equipment at the bottom: UPS and PDU go low in the cabinet or at the rear.
- Leave empty units: one or two spare units avoid re-racking everything later.
For cabinet sizes see our network cabinet sizes guide, and for power and cooling see server and network room preparation.
Installation points to check before handover
- One wiring scheme: use T568A or T568B throughout the project; mixing them reverses pairs.
- Minimal untwisting: untwisting pairs more than needed at the termination degrades performance, especially on Cat6A.
- Bend radius: avoid sharp bends behind the panel and support bundles with rear bars.
- Labelling: panel port numbers match the outlet numbers on site and on the shop drawings.
- Bonding: shielded panels are bonded to the rack earth bar.
- Testing and records: every link is tested after termination and a schedule of port, outlet location and result is handed over.
These points are normally reviewed in shop drawings and coordination and in testing, commissioning and handover.
Common mistakes
- Buying a Cat6 panel for a Cat6A cable run to save money, which downgrades the whole channel.
- Mixing shielded panels with unshielded cable, or the reverse, without understanding the effect.
- Long patch cords that pile up in front of the switch and block airflow.
- No spare ports, so a new panel ends up wherever there is space.
- Unlabelled panels, or labels that do not match the drawings.
FAQ
What is a patch panel in networking?
A rack-mounted panel where horizontal cable from wall outlets terminates, connected to the switch with short patch cords.
Do I need a patch panel with only one switch?
In most cases, yes. It protects the switch ports, simplifies moves and labelling, and makes a future switch replacement quick.
24-port or 48-port patch panel?
24-port panels are easier to organise with 24-port switches; 48-port panels save space in crowded racks.
Does a patch panel support PoE for cameras and access points?
The panel does not supply power but must carry it. The Legrand 033770 datasheet states PoE support up to 90 W (Type 4).
Can I use a Cat6A panel with Cat6 cable?
It will work, but the channel performs as Cat6. Keep all components in one category.
How much rack space does a patch panel take?
A 24-port panel usually takes 1U, often paired with a 1U cable manager.
Summary
The patch panel is a small part of the rack, but it decides how organised and maintainable the network stays for years. Match it to the cable category and shielding, size the ports with spares, lay it out with cable managers and label it to the drawings.
Related reading: HPE Aruba Instant On Switches in Saudi Arabia, Cat6 vs Cat6A and UTP vs FTP Cable.
Fitting out a network room or rack? Send us the outlet count and cable category, and the AZEIDK team will review panels, cabinets and cable with the datasheet for each product. Contact AZEIDK
Related guides
- Victaulic Sprinkler Installation: The Right Wrench, Torque Limits, Thread Sealant and the Mistakes That Fail Acceptance
- Smoke Detector Placement: AC Diffusers, Beams, High Ceilings, Ceiling Voids and Raised Floors
- Fire Alarm Cable: FPLR Shielded vs BS 6387 Fire-Resistant Cable (Belden 9581 and 79001FS)
- Hikvision NVR 8 Channel DS-7608NXI-K1(B): PoE Budget, Hard Drive, Cameras and Recording Days