LPG cylinder shop requirements in Saudi Arabia are set by the document “Requirements for Selling Liquefied Petroleum Gas Cylinders” published on the Ministry of Municipalities and Housing website (1446 AH / 2025). It requires Civil Defense approval before the licence is issued, refers all fire protection requirements to the Saudi Fire Code (SBC 801), and sets rules for shop area, fence, canopy, ventilation and security cameras. This guide collects the safety part only, explains the practical equipment owners ask about before applying on the Salamah platform, and shows how AZEIDK supplies and installs it.
Quick summary
- Civil Defense approval is required before the municipal licence for an LPG cylinder shop is issued (item 3.1).
- Minimum area is 24 m² for a cylinder shop and 6 m² for self-service machines or cages (Table 1).
- Good ventilation is required, and opening the shop in an enclosed place is not allowed (item 6.1).
- The storage canopy must be fire resistant and flame retardant, at least 5.5 m high (item 5.2).
- Security cameras are required under the Security Surveillance Cameras Law and its executive regulations (item 6.4).
In this article
What is the LPG cylinder sales requirements document?
The official reference is the LPG cylinder sales requirements on the Ministry of Municipalities and Housing website, which names the Ministry of Energy as the supervising authority. It covers site, building, operation and maintenance. For safety, four points matter most: Civil Defense approval, the reference to the fire code, ventilation, and fire resistant materials in the storage area.
In practice, the Balady licence will not be issued before the shop is ready from a safety point of view. The right order is to prepare the shop, request the safety certificate, then complete the licence. The steps are in our Salamah certificate for shops and Balady licence guide, and AZEIDK supports the file through its Civil Defense approval support service.
Area, fence and canopy: what the document says
- Area: at least 24 m² for a cylinder shop, and at least 6 m² for self-service machines or cages inside gas shops or as part of a building (Table 1).
- Fence: a solid fence between 4 m and 4.5 m high, with no screens above it (item 5.2).
- Gates: at least 2.5 m high and no more than 3 m wide, with a truck entrance at least 6 m wide.
- Canopy: the cylinder storage canopy is at least 5.5 m high and made of fire resistant, flame retardant materials with moisture and heat insulation.
- Filling area: kept away from entrances and from the cage storage yard.
- Floors: paved with materials that carry heavy loads and truck traffic, such as asphalt, interlock or concrete tiles, with falls for drainage.
These are architectural items, but they affect safety directly: a fire resistant canopy and distance between filling and entrances limit the effect of any incident, and good ventilation stops leaked gas from collecting.
Fire extinguishers for an LPG cylinder shop
The document does not give a number or size of extinguishers, because it refers fire protection to SBC 801 (item 5.4). The number and layout are calculated from area, hazard type and travel distance, and Civil Defense confirms them at inspection.
The main hazard here is a flammable gas, a Class B fire, with a possible electrical fire at the panel and lighting. Typical choices are:
- Multipurpose dry powder extinguisher near the storage area and entrance, such as the Falcon Gold 6 kg dry powder extinguisher.
- CO2 extinguisher near the electrical panel, such as the Falcon Gold 6 kg CO2 extinguisher.
According to our NFPA 10 portable extinguishers guide, Class B extinguishers are placed within 30 or 50 ft depending on their rating, an extinguisher up to 18.14 kg is mounted with its top no higher than 1.5 m, and units are inspected monthly and maintained yearly. For the classes see Class B, C and D extinguishers, and for a first estimate use the fire extinguisher calculator.
Gas leak detection and ventilation
The municipal document requires good ventilation and bans enclosed locations, without naming a specific device. Many owners add a flammable gas detector in the enclosed part of the shop or the attached office, because it warns early before the concentration becomes dangerous. Detector position depends on the gas and its weight compared with air; see our gas detector types guide and the gas detection systems category.
Any additional device follows the approved design and the supervising authority, and no single device replaces the good ventilation the document requires.
Cameras, electrical work and first aid
- Cameras: item 6.4 requires security cameras under the law and its regulations. See CCTV law obligations; AZEIDK installs them as part of its security and surveillance solutions.
- Electrical: the document refers to the electrical requirements of the Saudi Building Code (item 5.1) and asks for good ventilation during maintenance of service lines (item 6.5).
- First aid: a first aid box is good practice in any shop, for example the Falcon Gold medium first aid box; contents are in our first aid box guide.
How AZEIDK prepares an LPG cylinder shop
- Site visit: we review area, ventilation, the electrical panel location and the storage area.
- Equipment selection: extinguishers for the hazard class, a gas detector where needed, and cameras.
- Supply and installation: through technical supply and installation.
- Safety file: Civil Defense requirements support up to inspection, then an annual maintenance contract for periodic checks.
For premises that use a central gas tank rather than cylinders for sale, see central gas tank requirements.
Frequently asked questions
Does an LPG cylinder shop need Civil Defense approval?
Yes. The Ministry of Municipalities and Housing document requires Civil Defense approval before the licence is issued.
How many extinguishers does a gas shop need?
The document gives no fixed number. It is calculated from area, hazard and travel distance under the fire code, and Civil Defense confirms it at inspection.
What is the minimum area for an LPG cylinder shop?
24 m² for the shop and 6 m² for self-service machines or cages, according to Table 1 of the document.
Can a gas shop open in an enclosed place?
No. The document requires good ventilation and does not allow the shop in enclosed places.
Summary
An LPG cylinder shop licence starts with safety: good ventilation, a fire resistant canopy, extinguishers for gas and electrical fires, cameras under the law, then Civil Defense approval. To request a site visit or a quote, send your shop details through the quote request form.
Related guides
- Pharmacy Civil Defense Requirements in Saudi Arabia: Extinguishers, Storage and CCTV
- Site Survey Before Pricing Fire and CCTV Systems: What Is Checked
- Patch Cord Guide: Cat6, Cat6A and Fibre, Lengths, Colours and When to Replace
- Civil Defense Fire Apparatus Access in Saudi Arabia: Fire Lanes, Outdoor Hydrant Locations and the Fire Department Connection