Fire extinguisher calculator: how many extinguishers per floor
Enter the floor area, the hazard class and the Class A rating printed on the extinguisher label (for example 2-A, 3-A, 4-A or 6-A). The result is the minimum count per floor for ordinary combustibles under NFPA 10, which SBC 801 applies through Section 906.
Also check travel distance: no point on the floor may be more than 22.9 m (75 ft) of walking distance from an extinguisher, so long or divided floors often need more units than the area result.
Kitchens with cooking oils need a Class K extinguisher, and areas with flammable liquids or electrical rooms need Class B or CO2 units sized separately.
NFPA 10 limits used
| Hazard | Minimum rating | Max floor area per A unit | Max area per extinguisher | Max travel distance |
|---|---|---|---|---|
| Light | 2-A | 279 m² 3,000 ft² | 1,045 m² 11,250 ft² | 22.9 m |
| Ordinary | 2-A | 139 m² 1,500 ft² | 1,045 m² 11,250 ft² | 22.9 m |
| Extra | 4-A | 93 m² 1,000 ft² | 1,045 m² 11,250 ft² | 22.9 m |
Source: NFPA 10, Table 6.2.1.1 (Class A); Saudi Fire Code SBC 801, Section 906. The Civil Defense review and the approved design decide the final number and locations.