A fire alarm break glass unit, known technically as a manual call point, is the red device a person presses or breaks to raise the alarm before any detector senses the fire. Not every model uses glass any more: some have a resettable element reset with a key, some are addressable with a built-in isolator, and some are waterproof for outdoor use. The models AZEIDK supplies are part of its fire alarm systems, including the CP550CP smash glass call point and the SA5900-908IMC addressable call point.
For how conventional and addressable systems compare, see our guide to choosing a fire alarm system for Saudi projects.
This guide compares the types, lists each model’s data as published on AZEIDK’s product pages, and explains how to choose for each location, where to mount it and which mistakes recur at handover. For call points together with audible and visual notification appliances, see manual call points and notification appliances.
Key points
- Conventional call points sit on a zone circuit of a conventional panel; addressable ones carry an address so the panel shows their exact location.
- Resettable models need no replacement glass, and each operation is a full functional test of the device, per the product pages.
- For outdoor areas or locations exposed to water and dust: the addressable 58200-951IMC rated IP67.
- Where the specification calls for UL: the 56000-005IMC dual-action addressable pull station, stated to comply with UL 38.
- Yellow call points release gas suppression systems and never replace the red fire alarm call point.
In this article
- What is a fire alarm break glass and how does it work?
- Break glass or resettable: what is the difference?
- Conventional break glass models
- Addressable models: SA5900-908IMC, 58200-951IMC and 56000-005IMC
- Red break glass or yellow release point?
- Where and at what height is a fire alarm break glass mounted?
- Choosing the right model
- Common mistakes with manual call points
- FAQ
- Summary
What is a fire alarm break glass and how does it work?
A manual call point is an input device on the fire alarm system, just like a detector, except that a person operates it. Operation changes an internal contact, the alarm signal reaches the panel, and the panel starts the programmed sequence: sounders and beacons, and signals to linked systems per the cause and effect matrix.
On a smash glass model such as the CP550CP, wired for open-circuit operation the contact closes as soon as the glass breaks, per the product page. On resettable models, a plastic element is pressed, flips to show it has operated, and is reset with a key without any spare parts.
In Saudi Arabia, Section 907 of the Saudi Fire Code SBC 801 sets fire alarm requirements, including manual alarm initiation, by occupancy, and designers refer to NFPA 72 or the standard named in the project specification for detail.
Break glass or resettable: what is the difference?
| Item | Break glass | Resettable |
|---|---|---|
| Operation | Breaking a glass pane | Pressing a plastic element that flips to show activation |
| After operation | Needs replacement glass (CP550CP/G for the CP550CP) | Reset with a key and immediately reusable |
| Routine testing | Instant test with a dedicated key on the CP550CP | Every activation is a full functional test, per the CP500CPR/C page |
| Injury and debris | Foil-labelled glass to reduce injury risk | No glass, no fragments |
| Typical sites | Where the owner or specification asks for it | Escape routes, stair landings and exits in hospitals, malls, hotels and schools, per the CP500CPR/C page |
Both can take the CP500/550/C transparent polycarbonate cover, which reduces accidental operation and tampering in busy corridors and schools.
Conventional break glass models
These connect to a zone circuit on a conventional panel, such as Context Plus FP conventional panels or FG panels:
| Model | Type | Highlights from the product page |
|---|---|---|
| CP550CP (Context Plus) | Smash glass, surface mount | Instant key test, 3/4 inch conduit entries top, bottom and rear, brass and phosphor bronze metal parts, designed to BS 5839 Part 2 and EN 54 Part 11, approved to AS1603 Part 5 |
| CP500CPR/C (Context Plus) | Resettable, with clear cover | No glass to break or lose, every activation a full test, double terminals for in and out, suited to escape routes, stair landings and exits |
| MCP1A-525IMC (Context Plus) | Resettable, plug and play | First-fix terminal block that plugs into the unit with no re-termination, resistor or normally open contact options, unauthorised lid removal raises an alarm, EN 54-11 and LPCB approved |
| FA-505 (FG) | Conventional with clear cover | 24 V DC, standby current up to 100 µA, -10 to 65 °C, 87 x 87 x 52.5 mm |
The MCP1A-525IMC helps on projects where devices go in long after cabling: cables are terminated on the block at first fix and the unit is fitted later. See the MCP1A-525IMC and CP500CPR/C pages.
Addressable models: SA5900-908IMC, 58200-951IMC and 56000-005IMC
On an addressable system each call point has an address, so the panel shows exactly where it was operated. AZEIDK supplies three Context Plus addressable models:
| Item | SA5900-908IMC | 58200-951IMC | 56000-005IMC |
|---|---|---|---|
| Use | Indoor | Outdoor, wet or dusty areas | Indoor, UL projects |
| Operation | Resettable element | Resettable element, no glass | Dual action, PUSH handle latches down |
| Isolator | Built-in short-circuit isolator | Built-in short-circuit isolator | Not stated on the page |
| Protection | IP44 | IP67 | Not stated on the page |
| Operating voltage | 17 to 35 V DC | 17 to 35 V DC | 17 to 28 V (UL listed range 20 to 28) |
| Standby / alarm current | 100 µA / 4 mA | 100 µA / 4 mA | 200 µA at 24 V / 3.6 mA plus quiescent |
| Size | 89 x 89 x 63 mm | 114 x 114 x 74 mm | 108 x 140 x 28 mm |
| Standard per page | EN 54-11 and EN 54-17 | EN 54-11 and EN 54-17 | UL 38 |
The 58200-951IMC waterproof call point is surface mounted only. Its page recommends bringing the cable in from the bottom through correctly rated glands, sealing every gland and blanking plug, and using PTFE or similar thread sealant so the rating is not compromised. The 56000-005IMC pull station can be opened for maintenance and addressing without causing an alarm, and takes the 56000-006IMC surface back box.
Because every addressable device draws loop current, standby and alarm figures belong in the addressable loop design.
Red break glass or yellow release point?
Gas suppression rooms often have a yellow call point next to the red one. Yellow units such as the CP100RLR and BF372 are extinguishant release call points that connect to the suppression panel and discharge the agent, while the red one only raises the fire alarm. Mixing them up in installation or signage is a serious error; see the gas suppression release sequence.
Where and at what height is a fire alarm break glass mounted?
Locations and heights come from the approved design under SBC 801 and Civil Defense requirements, which are binding in Saudi Arabia, and installers follow them on site. As a reference value only, EC&M’s article on paragraph 17.15 of NFPA 72 (2022 edition) states that the operable part sits between 42 and 48 inches (about 1.07 to 1.22 m) above the finished floor, and that horizontal travel distance to the nearest call point on the same floor does not exceed 200 feet (61 m), with units placed near exits.
In practice call points go at floor exits, stair doors and building exits, on the latch side of the door, in a visible spot not hidden by furniture or open doors. For drawing symbols see fire alarm symbols on drawings.
Choosing the right model
- Panel type: a conventional panel means CP550CP, CP500CPR/C, MCP1A-525IMC or FA-505; an addressable panel means an addressable model on its protocol.
- Location: dry indoor, or outdoor and exposed to water and dust, such as open car parks, roofs and loading yards.
- Approval: EN 54 or UL. Do not mix approval systems on one loop; see UL vs EN 54.
- Users: in schools and malls, resettable units with clear covers cut malicious alarms and glass costs.
- Isolation: on addressable systems, a model with an isolator keeps the rest of the loop running during a short circuit.
Common mistakes with manual call points
- Fitting an indoor model in an open car park or on a roof, where moisture and dust damage the terminals.
- Leaving cable entries unsealed on the waterproof model, which defeats the IP67 rating in practice.
- Mounting the call point behind a door that stays open, or covering it with a notice board or shelf.
- No spare glass or reset keys held by the maintenance team.
- Confusing the yellow release point with the red break glass in gas suppression rooms.
FAQ
Is a fire alarm break glass the same as a manual call point?
Yes, same function. “Break glass” is the common market name; “manual call point” is the technical term and covers both glass and resettable models.
Are resettable call points acceptable instead of glass?
The resettable models AZEIDK supplies are designed to EN 54 Part 11 per their pages; acceptance is confirmed against the project specification and consultant.
How is a call point reset after operation?
Resettable models use the supplied key from the front. On the CP550CP, fit a CP550CP/G replacement glass, then reset the panel.
Is there a call point for outdoor use?
Yes, the addressable 58200-951IMC rated IP67 with a built-in isolator, surface mounted only with properly sealed glands.
What mounting height applies?
The approved design sets it. EC&M reports that NFPA 72 (2022, paragraph 17.15) places the operable part between 42 and 48 inches above the floor.
What does the built-in isolator do?
If the cable shorts, it isolates only the affected section and the rest of the loop keeps working, per the SA5900-908IMC and 58200-951IMC pages.
Summary
Choosing a fire alarm break glass starts with the panel, conventional or addressable, then the location, indoor or exposed, then the approval the specification requires. Resettable models save glass and simplify testing, addressable models with isolators protect the loop, and the IP67 model solves outdoor locations provided the glands are fitted properly.
Preparing a call point schedule? Send us the panel type, locations and required approval, and we will propose the right model for each location with datasheets. Contact the AZEIDK team
Related guides
- Honeywell Fire Alarm Systems in Saudi Arabia: Gent Vigilon Plus vs Notifier NFS2-640 vs Farenhyt IFP-2100
- Fire Sprinkler System Cost in Saudi Arabia: What Drives the Price (Hazard Class, Pipework, Pump and Approvals)
- Context Plus in Saudi Arabia: Fire Alarm Systems by AZEIDK
- TYCO vs Victaulic Fire Sprinklers: Comparing the Models AZEIDK Supplies by Application and K-Factor







