A conventional beam detector such as the Context Plus BeamRay RFX70 sends an infrared beam from the detector head to a reflector on the opposite side and signals an alarm when smoke obscures a set share of the beam. The RFX70 covers 7 to 70 m with a single reflector and up to 160 m with extra reflector kits, and aligns itself with motorised stepper drives. Details are on the BeamRay RFX70 beam detector page within AZEIDK’s fire alarm systems.
For how conventional and addressable systems compare, see our guide to choosing a fire alarm system for Saudi projects.
This guide follows the installation manual and datasheet published on the AZEIDK site: range kits, mounting height and coverage width, wiring to a conventional zone, sensitivity and delay settings, commissioning and testing, and the mistakes that cause faults or false alarms in warehouses and halls.
Key points
- Range: 7 to 70 m with the standard kit, 70 to 140 m with the 70KIT140 kit, 140 to 160 m with the 140KIT160 kit.
- Mounted 0.3 to 0.6 m below the ceiling, up to 40 m above the floor, covering 7.5 m either side of the beam under a flat roof.
- A conventional device powered at 12 to 30 V DC, with fire and fault relays rated 2 A at 30 V.
- Fire threshold factory set at 35%, adjustable 25% to 50%; time to fire 10 s, adjustable 2 to 30 s.
- The product page states EN 54-12:2015 compliance and VdS approval.
In this article
- What is a conventional beam detector and when do you need one?
- BeamRay RFX70 range and reflector kits
- Mounting height and coverage of a conventional beam detector
- Electrical data and wiring
- Sensitivity, time to fire and time to fault
- Commissioning and testing per the manual
- Common mistakes with beam detectors
- FAQ
- Summary
What is a conventional beam detector and when do you need one?
In large spaces with high ceilings, such as warehouses, exhibition halls, atriums, hangars and sports halls, point smoke detectors are hard and costly to install and maintain: dozens of heads at a height that needs a lift for every test. A beam detector covers a wide area with one head and one reflector, and its low level controller sits within reach for reading and testing.
“Conventional” means the detector is wired to a zone circuit on a conventional panel such as Context Plus FP. The manual notes it can be made addressable through the panel manufacturer’s interface. For fully addressable projects, AZEIDK also supplies addressable beam detectors, covered in Context Plus intelligent reflective beam detectors.
For the beam versus point decision by storage height, see warehouse smoke detectors: beam or point, and the sector page for warehouses and logistics.
BeamRay RFX70 range and reflector kits
| Distance to reflector | What you need | Manual note |
|---|---|---|
| 7 to 20 m | Standard kit with short range mask | Mask supplied, fitted on the single reflector |
| 20 to 70 m | Standard kit | Head unit, low level controller and one reflector |
| 70 to 140 m | Standard kit + 70KIT140 | Backing plate and 3 extra reflectors; the standard reflector is added to them |
| 140 to 160 m | Standard kit + 140KIT160 | Backing plate and 8 extra reflectors; the standard reflector is added to them |
The product page quotes an auto-align time of 3 min 02 s at 40 m. The manual also lists an anti-fog kit (specially coated reflector and lens cover) for damp areas or spaces with rapid temperature swings.
Mounting height and coverage of a conventional beam detector
The installation manual gives these rules, with an explicit note to check local regulations:
- Flat roof: a roof counts as flat unless the apex is more than 0.6 m high. Mount 0.3 to 0.6 m below the roof, up to 40 m above the floor.
- Coverage width: 7.5 m either side of the beam, 15 m in total.
- Pitched roof: mount 0.3 to 0.6 m down from the apex; coverage grows by 1% per degree of pitch. The manual’s example: a 10 degree pitch gives 15 m + 10% = 16.5 m, or 8.25 m each side.
- Clearances: at least 0.5 m from any protrusion, and a clear 1 m diameter path along the whole beam.
- Reflector: on a solid surface; on shiny or glass walls the manual says to mount reflectors on a 1 m board.
These are manufacturer figures. Spacing on your project is set by the design under Section 907 of the Saudi Fire Code SBC 801 and the technical standard the designer adopts, which may be more conservative. General spacing methods are in smoke and heat detector spacing calculation.
Electrical data and wiring
| Item | Datasheet value |
|---|---|
| Supply voltage | 12 to 30 V DC |
| Current | 3.5 mA constant in all states, 17 mA in fast commissioning |
| Fire and fault relays | Changeover contacts rated 2 A at 30 V DC |
| Temperature and humidity | -10 to +55 °C, 10% to 95% RH non-condensing |
| Protection | IP65 when suitably mounted and terminated |
| Wavelength | 870 nm |
| Beam head | 180 x 155 x 137 mm, 1.1 kg |
| Controller | 185 x 120 x 62 mm |
| Maximum angular alignment | ±5° |
The detector takes a two-wire supply (+ and -), and its fire and fault relays connect to the zone circuit with the alarm resistor and end-of-line component specified by the panel manufacturer, as shown in the manual’s wiring diagrams. When checking the cable between head and controller, the manual gives 110 ohm for a sound connection and 220 ohm if one end is not connected. Because the device draws continuous power, its consumption belongs in the panel battery calculation.
Sensitivity, time to fire and time to fault
| Setting | Factory | Range | When to change it |
|---|---|---|---|
| Fire threshold | 35% | 25% (most sensitive) to 50% | Per the design and the environment |
| Time to fire | 10 s | 2 to 30 s | Where objects briefly cross the beam, such as birds or forklifts |
| Time to fault | 10 s | 2 to 60 s | A fault only occurs when the beam is fully blocked within one second |
| Reset | Auto | Auto or latching | As the system requires |
| Auto alignment | On | On or off | Consider switching off where welding smoke is common, with the head on a solid structure |
| Align time | 4 h | 0 to 12 h | Per building movement and environment |
| Phase | 0 | 0 to 6 | Where facing beams could interfere |
False alarms from beam detectors usually come from temporary obstructions or structural movement rather than the sensitivity itself, so review causes before raising the threshold, as in fire alarm false alarms: causes and fixes.
Commissioning and testing per the manual
- Cover the reflector or leave it off, power up and run pre-alignment without the reflector.
- Fit or uncover the reflector: the air quality (AQ) reading jumps; if not, go to manual alignment.
- Align manually with the direction keys until the reading is at least 80 to 100%, ideally above 100%.
- Run auto alignment: the head finds all four reflector edges and centres itself.
- Test at the reflector, not the head: for fault, cover the reflector with a non-reflective card within one second; for fire, cover it slowly up to 70%.
Record each detector and result as part of fire alarm testing and commissioning before handover.
Common mistakes with beam detectors
- Fixing the head to light framing or steel that moves with heat, leading to repeated alignment messages and faults.
- Racking, signs or overhead cranes crossing the beam path.
- Using the standard kit beyond 70 m without the extra reflector kit.
- Forgetting the short range mask under 20 m.
- Testing by covering the head instead of the reflector, which does not prove the beam sees the right reflector.
- Two facing detectors left on the same phase.
FAQ
What is the maximum range of the BeamRay RFX70 conventional beam detector?
70 m with the standard kit, up to 140 m with 70KIT140 and up to 160 m with 140KIT160, per the manual.
What is the maximum mounting height?
The manual gives up to 40 m above the floor, mounted 0.3 to 0.6 m below the ceiling or apex. The approved design may set further limits.
How wide is the coverage?
7.5 m each side under a flat roof, 15 m in total, increasing by 1% per degree of pitch on sloped roofs per the manual.
Does the RFX70 work with an addressable panel?
It is a conventional detector; the manual says it can be made addressable with the panel manufacturer’s interface. Context Plus addressable beam detectors are also available.
Why does a beam detector show a fault?
The datasheet lists full beam obstruction within one second, power loss or supply below 9 V, or the unit being in alignment or maintenance mode.
Where is a beam detector tested?
At the reflector: cover it gradually up to 70% for a fire test, or fully within one second for a fault test.
Summary
The BeamRay RFX70 is a practical answer for large, high-ceiling spaces on a conventional system: one head and reflector covering up to 160 m with extra kits, and a low level controller that makes testing easy. Site success depends on a rigid fixing, a clear path, the right kit for the distance, and time and threshold settings matched to the space.
Protecting a warehouse or high-ceiling hall? Send us the layout, ceiling height and panel type, and we will define the number of beam detectors and reflector kits with datasheets. Contact the AZEIDK team